![Johnson Controls York YHAU-C Installation, Operation And Maintenance Manual Download Page 125](http://html1.mh-extra.com/html/johnson-controls/york-yhau-c/york-yhau-c_installation-operation-and-maintenance-manual_2023471125.webp)
Trend screen
Figure 59: Trend screen
To view the Trend Screen, press the
Trend
button above the History Menu section on the Data
screen.
This screen graphically illustrates the trend of the temperature and the pressure for the following:
•
Chilled Water In:
Temperature of the chilled water measured as it enters the evaporator
•
Chilled Water Out:
Temperature of the chilled water measured as it leaves the evaporator
•
Cooling Water In:
Temperature of the cooling water as it enters the absorber
•
Cooling Water Out:
Temperature of the cooling hot water as it leaves the condenser
•
Generator Temperature:
Temperature of the concentrated solution in the generator.
The graphs are updated constantly regardless of the operating status of the chiller.
The display ranges in the Trend screen can be changed.
123
YHAU-C Single Effect Steam-Fired Absorption Chiller
Summary of Contents for York YHAU-C
Page 2: ......
Page 33: ...Figure 11 Location of rupture disk 31 YHAU C Single Effect Steam Fired Absorption Chiller...
Page 103: ...Figure 49 Cooling start diagram 101 YHAU C Single Effect Steam Fired Absorption Chiller...
Page 104: ...Figure 50 Cooling stop diagram YHAU C Single Effect Steam Fired Absorption Chiller 102...
Page 166: ...Figure 73 Steam and drain system YHAU C Single Effect Steam Fired Absorption Chiller 164...
Page 167: ...Figure 74 Duhring diagram PTX chart F 165 YHAU C Single Effect Steam Fired Absorption Chiller...
Page 168: ...Figure 75 Duhring diagram PTX chart C YHAU C Single Effect Steam Fired Absorption Chiller 166...