VRF Air-Conditioner IOM

 

 

4

indoor  unit  horizontally  and  maintain  the  main 
body  vertical to the floor. Dismantle pump, small 
defrosting  tray  and  water  level  switch  before 
installation,  strip  off  the  insulated  shield  of water 
level  switch  connecting  line  and  then  screw 
together  to  make  short  circuit,  directly  connect 
drainage pipe in accessories to the main defrosting 
tray  outlet  (select  left  or  right  water  outlet  of 
defrosting  tray  according  to  actual  installation 
condition). 

 

 

 

Model 

B  C 

G  H 

YDEC028-112 1245 680 150  760  450 1119 200 240 

YDEC140-160 1670 680 150 1070 450 1542 200 240 

5.

 

Installation of Refrigerant Piping 

 

The  piping  at  gas  side  and  liquid  side  of 
refrigerant shall be subjected to thermal insulation, 
if not, the piping surface will have dew. 

 

Please  use  thermal  insulation  material  which  is 
capable  of  withstanding  above  120

  high 

temperature.  Please  strengthen  thermal  insulation 
for refrigerant  piping according to the installation 
environment, otherwise, the surface of the thermal 
insulation material may dew and frost. 

 

Please comply with the following items: 

 

Coat  fatty  oil  or  ether  oil  at  horn  mouth  (inside 
and outside) when connecting horn mouth nut. 

 

Only use the horn mouth nut attached by the unit. 
Other  horn  mouth  nut  may  lead  to  refrigerant 
leakage. 

 

Please  clamp  flat  or  seal  the  pipe  end  in  order  to 

prevent  dust,  moisture  or  other  foreign  matter 
entering into pipe. 

 

Except  designated  refrigerant,  anything,  for 
example,  air,  shall  not  mix  into  refrigerating 
circuit. 

 

Before welding refrigerant  piping, please conduct 
nitrogen replacement or fill nitrogen into piping in 
welding,  and  finally  connect  with  indoor  unit  by 
horn mouth. 
 

 

 

When  filling  nitrogen  into  piping  in  welding, 
guarantee  to  control  the  pressure  with  reducing 
valve  as  0.02MPa  (0.2kgf/cm

2

)  (like  the  feel  of 

breeze blowing cheek). 

 

Do not use welding flux when welding refrigerant 
piping  connector.  Please  use  copper  base  brazing 
filler metal without welding flux. 

The  use  of  welding  flux  containing  chlorine  or 
fluorine  may  corrode  the  purity  of  piping  or 
refrigerating system. 

5.1

 

  Piping connection 

 

When  connecting  and  dismantling  piping  to/from 
air  conditioner,  simultaneously  use  an  ordinary 
spanner and a torque spanner. 

 

 

 

For  relevant  tightening  torque,  please  refer  to  the 
following table. 
 

Pipe diameter 

Tightening torque 

(N.m) 

6.35(1/4") 

14.2~17.2 

9.53(3/8") 

32.7~39.9 

12.7(1/2") 

49.5~60.3 

15.88(5/8") 

61.8~75.4 

 

 

If  it  is  necessary  to  install  unit  without  torque 
spanner, comply with the following method: 

When using spanner to tighten the horn mouth nut, 
the tightening torque on some point may suddenly 
increase. Further tighten the horn mouth nut from 
this  position  to  the  angle  shown  in  the  following 
table. 

   

Pipe diameter 

Angle 

tightened 

further 

Length of 

recommended 

tool arm 

6.35(1/4") 

60°~90° 

~150mm 

9.53(3/8") 

60°~90° 

~200mm 

12.7(1/2") 

45°~75° 

~250mm 

15.88(5/8") 

45°~75° 

~300mm 

Caution 

Caution 

Hook 

Dismantle pump assembly 

Connect defrosting tray with   
drainage pipe 

Bolt 

 
Gasket 

Torque spanner

Ordinary spanner 

Piping connector 

Horn mouth nut 

Summary of Contents for York YDEC028

Page 1: ...VRF Air Conditioner Installation Manual FORM NO YDEC IOM EN 1212 ...

Page 2: ...cting Pipes Liquid Gas φ mm 6 35 9 52 6 35 12 7 6 35 12 7 6 35 12 7 9 52 15 88 Drainage Pipe φ mm 16 O D Model YDEC080 YDEC090 YDEC112 YDEC140 YDEC160 Cooling Capacity kW 8 0 9 0 11 2 14 0 16 0 Heating Capacity kW 9 0 10 0 12 5 16 0 18 0 Power supply 220V 50Hz Rated Power W 210 210 210 250 250 Rated Current A 0 97 0 97 0 97 1 20 1 20 Air Flow Rate m3 h 1550 1550 1550 1950 1950 External Static Pres...

Page 3: ... Contents 1 SAFETY CAUTIONS 1 2 BEFORE INSTALLATION 1 3 SELECTION OF INSTALLATION POSITION 2 4 INSTALLATION OF INDOOR UNIT 2 5 INSTALLATION OF REFRIGERANT PIPING 4 6 INSTALLATION OF DRAINAGE PIPING 5 7 ELECTRIC CONNECTION 6 ...

Page 4: ...ge earthing breaker is not installed there will be electric shock hazard or fire hazard Please arrange drainage piping according to this instruction to guarantee smooth drainage and insulate the piping in case of condensed water accumulation Improper piping may lead to water leakage and soak household items Air conditioner power line and connecting line shall be far away from more than 1m at least...

Page 5: ...nd the superhard walls as much as possible in holing the hole inside shall be 0 5cm 1cm higher than outside considering drainage wall hole passing through outlet pipe of indoor unit side shall be slightly lower than the indoor unit downside for holing with diamond plastic cloth shall be sticked to wall or other method may be adopted to prevent water flow to wall for holing with electric hammer dus...

Page 6: ... must be opened on the ceiling before installation with the specification as follows 1170 610 for 028 112 type and 1600 610 for 140 160 type take down the right and left cover plates of indoor unit and then embed one half of main body into the ceiling and only expose rear cover plate and head cover For seat installation use gradienter to install Hoisting bolt Hoisting bolt Hoisting support Hoistin...

Page 7: ... designated refrigerant anything for example air shall not mix into refrigerating circuit Before welding refrigerant piping please conduct nitrogen replacement or fill nitrogen into piping in welding and finally connect with indoor unit by horn mouth When filling nitrogen into piping in welding guarantee to control the pressure with reducing valve as 0 02MPa 0 2kgf cm2 like the feel of breeze blow...

Page 8: ... good thermal insulation Field piping must be connected to the piping connecting part all the time If poor thermal insulation for piping there will be dew outside and scald if any touch 6 Installation of Drainage Piping 6 1 Drainage piping installation In delivery the drainage outlet is PVC pipe in connecting water pipe please use auxiliary sealing material and sleeve Conduct thermal insulation fo...

Page 9: ...ional electrician Line breaker or leakage breaker must be arranged at power supply Earthing resistance must below 4Ω Air conditioner must be earthed reliably Earthing wire shall not be connected to gas pipe tap water pipe lightening rod or telephone line Do not power on before the end of all the electric operation The terminal of the same power supply shall not be connected with two wires with dif...

Page 10: ...on wire of TB3 outlet connects to the communication port of the next indoor unit TB2 inlet Inlet and outlet lines TB2 inlet and TB3 outlet of indoor unit shall not be reversed otherwise there will be fault and the unit can t be started Connect according to the diagram do not allow A and B polarity connection error otherwise communication failure or controller damage may be caused In order to avoid...

Page 11: ...roller can connect to max 4 indoor units The indoor units in one group should be connected in one and same power supply to guarantee normal initialization of wire controller when power on Connection sketch of indoor unit and wire controller a When one wire controller connecting only one indoor unit refer to Fig 13 b When one wire controller connecting multi indoor units refer to Fig 14 Fig 13 One ...

Page 12: ...9 YDEC IOM EN 1212 NONE YDEC IOM 0812 ...

Reviews: