3

 

 

 
 
 

 

Seat installation method. 
Please  use  embedded  bolt,  expansion  bolt,  etc.; 
the bolt material shall be high-quality carbon steel 
(subjected  to  surface  copper  plating  or  other 
rust-proof treatment) or stainless steel. 

 

4.3

 

  Install indoor unit 

 

Use  pulley,  etc.  to  hoist  indoor  unit  to  hoisting 
bolt;  use  gradienter,  etc.  to  install  indoor  unit 
horizontally;  otherwise,  it  may  cause  water 
leakage. 
 

 

 

 

 

 

 

 

 

 

For  embedded  type  installation,  the  procedure  is 
similar to hoisting mode, but hole must be opened 
on  the  ceiling  before  installation,  with  the 
specification  as  follows:  1170×610  for  028-112 
type  and  1600×610  for  140-160  type;  take  down 
the  right  and  left  cover  plates  of  indoor  unit  and 
then embed one half of main body into the ceiling, 
and only expose rear cover plate and head cover. 

 

 

 

For  seat  installation,  use  gradienter  to  install 

Hoisting bolt 

Hoisting bolt 

Hoisting support 

Hoisting support 

Hoisting parts 

Nut 

Gasket 

Side plate 

Wall 

Wedge bolt   

Drainage outlet 

Connector at gas side of cooling medium piping 

Connector at liquid side of cooling medium piping 

(Blade    shape 
Insertion) 

(Slide insertion) 

Steel bar 

Embedding screw bolt 

(Pipe hanging and embedding 
screw bolt) 

Summary of Contents for York YDEC028

Page 1: ...VRF Air Conditioner Installation Manual FORM NO YDEC IOM EN 1212 ...

Page 2: ...cting Pipes Liquid Gas φ mm 6 35 9 52 6 35 12 7 6 35 12 7 6 35 12 7 9 52 15 88 Drainage Pipe φ mm 16 O D Model YDEC080 YDEC090 YDEC112 YDEC140 YDEC160 Cooling Capacity kW 8 0 9 0 11 2 14 0 16 0 Heating Capacity kW 9 0 10 0 12 5 16 0 18 0 Power supply 220V 50Hz Rated Power W 210 210 210 250 250 Rated Current A 0 97 0 97 0 97 1 20 1 20 Air Flow Rate m3 h 1550 1550 1550 1950 1950 External Static Pres...

Page 3: ... Contents 1 SAFETY CAUTIONS 1 2 BEFORE INSTALLATION 1 3 SELECTION OF INSTALLATION POSITION 2 4 INSTALLATION OF INDOOR UNIT 2 5 INSTALLATION OF REFRIGERANT PIPING 4 6 INSTALLATION OF DRAINAGE PIPING 5 7 ELECTRIC CONNECTION 6 ...

Page 4: ...ge earthing breaker is not installed there will be electric shock hazard or fire hazard Please arrange drainage piping according to this instruction to guarantee smooth drainage and insulate the piping in case of condensed water accumulation Improper piping may lead to water leakage and soak household items Air conditioner power line and connecting line shall be far away from more than 1m at least...

Page 5: ...nd the superhard walls as much as possible in holing the hole inside shall be 0 5cm 1cm higher than outside considering drainage wall hole passing through outlet pipe of indoor unit side shall be slightly lower than the indoor unit downside for holing with diamond plastic cloth shall be sticked to wall or other method may be adopted to prevent water flow to wall for holing with electric hammer dus...

Page 6: ... must be opened on the ceiling before installation with the specification as follows 1170 610 for 028 112 type and 1600 610 for 140 160 type take down the right and left cover plates of indoor unit and then embed one half of main body into the ceiling and only expose rear cover plate and head cover For seat installation use gradienter to install Hoisting bolt Hoisting bolt Hoisting support Hoistin...

Page 7: ... designated refrigerant anything for example air shall not mix into refrigerating circuit Before welding refrigerant piping please conduct nitrogen replacement or fill nitrogen into piping in welding and finally connect with indoor unit by horn mouth When filling nitrogen into piping in welding guarantee to control the pressure with reducing valve as 0 02MPa 0 2kgf cm2 like the feel of breeze blow...

Page 8: ... good thermal insulation Field piping must be connected to the piping connecting part all the time If poor thermal insulation for piping there will be dew outside and scald if any touch 6 Installation of Drainage Piping 6 1 Drainage piping installation In delivery the drainage outlet is PVC pipe in connecting water pipe please use auxiliary sealing material and sleeve Conduct thermal insulation fo...

Page 9: ...ional electrician Line breaker or leakage breaker must be arranged at power supply Earthing resistance must below 4Ω Air conditioner must be earthed reliably Earthing wire shall not be connected to gas pipe tap water pipe lightening rod or telephone line Do not power on before the end of all the electric operation The terminal of the same power supply shall not be connected with two wires with dif...

Page 10: ...on wire of TB3 outlet connects to the communication port of the next indoor unit TB2 inlet Inlet and outlet lines TB2 inlet and TB3 outlet of indoor unit shall not be reversed otherwise there will be fault and the unit can t be started Connect according to the diagram do not allow A and B polarity connection error otherwise communication failure or controller damage may be caused In order to avoid...

Page 11: ...roller can connect to max 4 indoor units The indoor units in one group should be connected in one and same power supply to guarantee normal initialization of wire controller when power on Connection sketch of indoor unit and wire controller a When one wire controller connecting only one indoor unit refer to Fig 13 b When one wire controller connecting multi indoor units refer to Fig 14 Fig 13 One ...

Page 12: ...9 YDEC IOM EN 1212 NONE YDEC IOM 0812 ...

Reviews: