5.2
PRINT Key
The 'PRINT' key allows the operator to obtain a printout
of real-time system operating data or a printout of
system data at the "instant of the fault" on the last six
faults which occurred on the unit. An optional printer is
required for the printout.
Operating Data Print-out
Pressing the 'PRINT' key and then 'OPER DATA' key
allows the operator to obtain a printout of current system
operating parameters. When the 'OPER DATA' key is
pressed, a snapshot will be taken of system operating
conditions and panel programming selections. This data
will be temporarily stored in memory and transmission of
this data will begin to the printer. A sample operating
data printout is shown opposite.
1
-
22
Form 201.26.OI1(11/09)
YORK INTERNATIONAL CORPORATION
MILLENNIUM LIQUID CHILLER
UNIT STATUS
10:01AM 11 APR 08
SYS 1
COMPRESSORS RUNNING 2
SYS 2
COMPRESSORS RUNNING 3
OPTIONS
CHILLED LIQUID
WATER
LOCAL/REMOTE MODE
REMOTE
LEAD/LAG CONTROL
AUTOMATIC
POWER FAIL RESTART
MANUAL
EXPANSION VALVE
THERMOSTATIC
REMOTE TEMP RESET
0 TO 10 V
YORK HYDRO KIT PUMPS
= 1
HOT GAS BYPASS TYPE
NONE
PROGRAM VALUES
DSCH PRESS CUTOUT
38.6 BARG
SUCT PRESS CUTOUT
5.59 BARG
LOW AMBIENT CUTOUT
-3.9 DEGC
LEAVING LIQUID CUTOUT
3.0 DEGC
ANTI RECYCLE TIME
600 SECS
FAN CONTROL ON PRESS
23.1 BARG
FAN DIFF OFF PRESS
5.5 BARG
NUMBER OF COMPRESSORS
6
SYS1 NUMBER OF FANS
4
SYS2 NUMBER OF FANS
4
REFRIGERANT TYPE
R-410A
REMOTE UNIT ID PROGRAMMED
0
RATE SENSITIVITY
2.0 DEGC/MIN
RATE CONTROL RANGE TMP 6.1 DEGC
UNIT DATA
RETURN LIQUID TEMP
11.2 DEGC
LEAVING LIQUID TEMP
6.2 DEGC
COOLING RANGE
6.1 +/- 1.1 DEGC
REMOTE SETPOINT
6.1 DEGC
AMBIENT AIR TEMP
11.3 DEGC
LEAD SYSTEM
SYS 2
EVAPORATOR PUMP
ON
EVAPORATOR HEATER
OFF
ACTIVE REMOTE CONTROL
TEMP
EVAP PUMP TOTAL RUN HOURS
83
SOFTWARE VERSION
C.M17.16.02
SYSTEM 1 DATA
COMP STATUS
1=OFF 2=ON 3=ON
RUN TIME
0- 1- 8-33 D-H-M-S
SUCTION PRESSURE
8.14 BARG
DISCHARGE PRESSURE
24.4 BARG
LIQUID LINE SOLENOID
ON
CONDENSER FAN STAGE
LO 4
SYSTEM 2 DATA
COMP STATUS
1=ON 2=ON 3=ON
RUN TIME
0- 1-13-44 D-H-M-S
SUCTION PRESSURE
7.45 BARG
DISCHARGE PRESSURE
27.1 BARG
LIQUID LINE SOLENOID
ON
CONDENSER FAN STAGE
HI 4
DAILY SCHEDULE
S M T W T F S
*=HOLIDAY
SUN START=00:00AM
STOP=00:00AM
MON START=00:00AM
STOP=00:00AM
TUE START=00:00AM
STOP=00:00AM
WED START=00:00AM
STOP=00:00AM
THU START=00:00AM
STOP=00:00AM
FRI START=00:00AM
STOP=00:00AM
SAT START=00:00AM
STOP=00:00AM
HOL START=00:00AM
STOP=00:00AM