SECTION 5 – TECHNICAL DATA
TABLE 12 -
GROUND LUG SIZING
CIRCUIT BREAKER OPTION
RATING
INCOMING WIRE
GROUND WIRE
60A
# 14 - 1/0 AWG
# 14 - 6 AWG
70A
# 14 - 1/0 AWG
# 14 - 6 AWG
80A
# 14 - 1/0 AWG
# 14 - 6 AWG
90A
# 14 - 1/0 AWG
# 14 - 6 AWG
100A
# 14 - 1/0 AWG
# 8 - 2 AWG
125A
# 14 - 1/0 AWG
# 8 - 2 AWG
125A
# 2 - 4/0 AWG
# 8 - 2 AWG
150A
# 2 - 4/0 AWG
# 8 - 2 AWG
175A
# 4 - 300 KCM
# 6 - 1/0 AWG
200A
# 4 - 300 KCM
# 6 - 1/0 AWG
225A
# 4 - 300 KCM
# 6 - 1/0 AWG
250A
# 6 - 350 KCM
# 4 - 3/0 AWG
400A
# 250 - 500 KCM
# 2 - 4/0 AWG
400A
(2) # 3/0 - 250 KCM
(2) # 6 - 1/0 AWG
600A
(2) # 250 - 500 KCM
(2) # 2 - 4/0 AWG
TERMINAL BLOCK OPTION
RATING
INCOMING WIRE
GROUND WIRE
130A
# 12 - 1 AWG
# 8 - 2 AWG
165A
# 10 - 3/0 AWG
# 6 - 1/0 AWG
240A
# 10 - 300 KCM
# 4 - 3/0 AWG
320A
# 4 - 500 KCM
# 2 - 4/0 AWG
480A
(2) # 10 - 300 KCM
(2) # 4 - 3/0 AWG
Notes:
1. Start in correct power option table (breaker, terminal block)
2. Match engineering guide value for Amperage
3. Match engineering guide value for wire range
4. Note corresponding ground wire range