Functions and Control
24
Domestic Air Conditioner
After the compressor is started for 5 seconds, the outdoor fan is started at the medium speed at
first, after 30 seconds it begins to control the airflow speed according to the temperature
conditions of the outdoor environment.
Remarks: Ta:The temperature of the outdoor air; Te: The temperature of the outdoor coil.
The temperature of the outdoor
air
Ta
Airflow speed
Ta
22
Low
19
Ta<22
Keeping the speed
16
Ta<22
Medium
14
Ta<16
Keeping the speed
Ta<14
High
Remarks: Ta:The temperature of the outdoor air; Te: The temperature of the outdoor coil.
5.2.3
The control of the outdoor electronic expansion valve
When starting the compressor: the opening size of the valve must be guaranteed to have entered
into the standard opening size, and then the compressor can be started.
When refrigeration is in vain (the machine is shut down or is in the state of retrograde operation),
the opening size of the expansion valve of the indoor unit is 5 steps;
When heating is in vain, the opening size of the expansion valve of the indoor unit is 55 steps;
When the outdoor unit is shut down, the valve is opened completely for 2 minutes, and then
begin initialization.
The scope of refrigerationg valve 90-----480 steps
The scope of heating valve 80-----480 steps
The valves are adjusted according to the degree of superheat
SHa
SHa.
5.2.4
Four way control
For the details of Defrost four-way valve control, see the Defrost process.
Four way working in other ways:
Under the mode of heating, open the four-way valve, when the compressor is not started or
changed to non-heating mode, make sure the compressor is stoped for 2 minutes, and then
close the four-way valve.
The temperature of the
outdoor air
Ta
The temperature of the outdoor
coil
Te
Airflow speed
Ta
30
High
26
Ta<30
Keeping the speed
24
Ta<26
Medium
23
Ta<24
Keeping the speed
5
Ta<23
Low
Ta<5
15
Te
Low
15
>Te
Stop
5.2.2.1 The outdoor fan control when refrigerating or dehumidifying
5.2.2.2 The outdoor fan control when heating
Summary of Contents for York FREE MATCH EK-Series
Page 70: ...WARNING CAUTION 68 Installation ...
Page 76: ...74 Installation ...
Page 79: ...Pressurize for over 3 minutes at 4 2MPa After above 77 Installation ...
Page 83: ...81 Domestic air conditioner Removal of procedure 9 ...
Page 86: ...84 Domestic air conditioner Removal of procedure three 3 HOOKS ...
Page 87: ...85 Domestic air conditioner Removal of procedure horizontal flap flap flap flap flap ...
Page 89: ...87 Domestic air conditioner Removal of procedure ...
Page 90: ...Domestic air conditioner Removal of procedure 3 88 ...
Page 91: ...Domestic air conditioner Removal of procedure 89 ...
Page 92: ...Domestic air conditioner Removal of procedure 90 ...
Page 93: ...Domestic air conditioner Removal of procedure Outdoor Unit Removal of Outdoor Panel 91 ...
Page 95: ...93 Domestic air conditione Removal of procedure Loosen the csrews and pull the panel ...
Page 97: ...95 Domestic air conditioner Removal of procedure ...
Page 98: ...96 Domestic air conditioner Removal of procedure ...
Page 100: ...98 Domestic air conditioner Removal of procedure ...
Page 101: ...99 Domestic air conditioner Removal of procedure and remove the reactor Loosen the screw ...
Page 110: ...The end ...