Functions and Control
26
Domestic Air Conditioner
N
Decreasing at the speed of 1HZ/1 second
P
Decreasing at the speed of 1Hz/10 seconds
Q
Continue to keep the last-time instruction cycle
R
Increasing at the speed of 1Hz/10seconds
Remarks: the outdoor unit
During the starting process of the compressor, if the current of the compressor is greater than
17A for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state
appears 3 times in 20 minutes, stop the compressor and alarm, and confirm the malfunction.
Then continue to run it only after the power is off.
During the starting process of the compressor, if the AC current is greater than 12A, the
frequency of the compressor decreases at the speed of 1HZ/second.
During the starting process of the compressor, if the AC current is greater than 10A, the
frequency of the compressor decreases at the speed of 0.1HZ/second.
During the starting process of the compressor, if the AC current is greater than 9A, the
frequency of the compressor increases at the prohibited speed.
During the starting process of the compressor, if the AC current is greater than 8A, the
frequency of the compressor increases at the speed of no faster than 0.1HZ/second.
During the starting process of the compressor, if the AC current is greater than 15A, the
frequency of the compressor decreases at the speed of 1HZ/second.
During the starting process of the compressor, if the AC current is greater than 13A, the
frequency of the compressor decreases at the speed of 0.1HZ/second.
During the starting process of the compressor, if the AC current is greater than 11A, the
frequency of the compressor increases at the prohibited speed.
During the starting process of the compressor, if the AC current is greater than 10A, the
frequency of the compressor increases at the speed of no faster than 0.1HZ/second.
Remarks: when the outdoor temperature is high, there’s compensation for AC current protection.
When the outdoor environment temperature is higher than 40
, AC current protection value
decreases by 10AD
When the outdoor environment temperature is higher than 46
,AC current protection value
decreases by 15AD
When the outdoor environment temperature is higher than 50
,AC current protection value
decreases by 20AD
When refrigerating/heating, prevent freezing.
Tpg_indoor is the minimum value of the effective indoor unit (start it and it is in accord with the
running state).
5.2.5.3 The control of preventing the overcurrent of the compressor
5.2.5.4 The protection function of AC current:
5.2.5.5 Antifreezing protection of the indoor heat exchanger
Summary of Contents for York FREE MATCH EK-Series
Page 70: ...WARNING CAUTION 68 Installation ...
Page 76: ...74 Installation ...
Page 79: ...Pressurize for over 3 minutes at 4 2MPa After above 77 Installation ...
Page 83: ...81 Domestic air conditioner Removal of procedure 9 ...
Page 86: ...84 Domestic air conditioner Removal of procedure three 3 HOOKS ...
Page 87: ...85 Domestic air conditioner Removal of procedure horizontal flap flap flap flap flap ...
Page 89: ...87 Domestic air conditioner Removal of procedure ...
Page 90: ...Domestic air conditioner Removal of procedure 3 88 ...
Page 91: ...Domestic air conditioner Removal of procedure 89 ...
Page 92: ...Domestic air conditioner Removal of procedure 90 ...
Page 93: ...Domestic air conditioner Removal of procedure Outdoor Unit Removal of Outdoor Panel 91 ...
Page 95: ...93 Domestic air conditione Removal of procedure Loosen the csrews and pull the panel ...
Page 97: ...95 Domestic air conditioner Removal of procedure ...
Page 98: ...96 Domestic air conditioner Removal of procedure ...
Page 100: ...98 Domestic air conditioner Removal of procedure ...
Page 101: ...99 Domestic air conditioner Removal of procedure and remove the reactor Loosen the screw ...
Page 110: ...The end ...