WT-BAC-IP Gateway Installation Instructions
9
Explanation of Key Attributes
The following table lists the descriptions of key attributes of the WT-BAC-IP Gateway.
Technical Specifications
Table 2: WT-BAC-IP Key Attributes
Attribute
Description
WT-BAC-IP Version
Version level for the BACnet application software
MAC Address
Unique 12-Digit HEX address for the WT-BAC-IP
Port
UDP Port (default value 47808); editable if changes are necessary
Device Instance
BACnet Instance ID; can be modified
Point Map
View
shows currently mapped BACnet objects.
Create
maps currently connected devices
and creates a new Point Map.
Online Device Count
View
shows the Grid View of currently connected devices.
Update
refreshes the count to
check for newly connected devices.
Wireless Network Info
Shows information about the WT-BAC-IP’s GID, DID, and Channel; all three fields are
editable.
Connection Mode
Allows the user to switch the WT-BAC-IP between DHCP and Static IP Addressing
WT-BAC-IP Gateway
(Part 1 of 2
)
Power Requirements
12 VDC external supply
Communications
Interface: Ethernet 10Base-T/100Base-TX with RJ-45 Connector
Protocol: BACnet IP
Wireless Band
Direct-Sequence, Spread-Spectrum, 2.4 GHz ISM Band
Operating Frequency
Range
2,405 to 2,480 MHz
Channels
Quantity: 15
Spacing: 5 MHz
Transmissions
Power: 18 dBm maximum
Rate: 250 Kbits for each second
Ambient Conditions
Operating: 50 to 104°F (10 to 40°C), 5 to 95% RH, noncondensing
Storage: -4 to 158°F (-20 to 70°C), 5 to 95% RH, noncondensing
Materials
Gray ABS plastic housing
Figure 10: WT-BAC-IP LED Functions