Johnson Controls WT-BAC-IP Installation Instructions Manual Download Page 9

WT-BAC-IP Gateway Installation Instructions

9

Explanation of Key Attributes

The following table lists the descriptions of key attributes of the WT-BAC-IP Gateway. 

Technical Specifications

Table 2:  WT-BAC-IP Key Attributes

Attribute

Description

WT-BAC-IP Version

Version level for the BACnet application software

MAC Address

Unique 12-Digit HEX address for the WT-BAC-IP

Port

UDP Port (default value 47808); editable if changes are necessary

Device Instance

BACnet Instance ID; can be modified

Point Map

View

 shows currently mapped BACnet objects. 

Create

 maps currently connected devices 

and creates a new Point Map.

Online Device Count

View

 shows the Grid View of currently connected devices. 

Update

 refreshes the count to 

check for newly connected devices.

Wireless Network Info

Shows information about the WT-BAC-IP’s GID, DID, and Channel; all three fields are 
editable.

Connection Mode

Allows the user to switch the WT-BAC-IP between DHCP and Static IP Addressing

WT-BAC-IP Gateway

 (Part 1 of 2

)

Power Requirements

12 VDC external supply

Communications

Interface: Ethernet 10Base-T/100Base-TX with RJ-45 Connector

Protocol: BACnet IP

Wireless Band

Direct-Sequence, Spread-Spectrum, 2.4 GHz ISM Band

Operating Frequency 
Range

2,405 to 2,480 MHz

Channels

Quantity: 15

Spacing: 5 MHz

Transmissions

Power: 18 dBm maximum

Rate: 250 Kbits for each second

Ambient Conditions

Operating: 50 to 104°F (10 to 40°C), 5 to 95% RH, noncondensing

Storage: -4 to 158°F (-20 to 70°C), 5 to 95% RH, noncondensing

Materials

Gray ABS plastic housing

Figure 10: WT-BAC-IP LED Functions

Summary of Contents for WT-BAC-IP

Page 1: ...ormal operating conditions Where failure or malfunction of the gateway could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be des...

Page 2: ...an IP Connection to the WT BAC IP Use the following steps to establish an IP connection to the WT BAC IP 1 Configure a temporary static IP address on your computer Windows 7 by going to Start Control...

Page 3: ...DHCP 5 Connect an Ethernet cable from your computer to the WT BAC IP Gateway 6 Plug the 12 VDC adapter into the WT BAC IP 7 Open the WT BAC IP Configuration Tool program 8 In the By MAC Address tab t...

Page 4: ...es the use of a default gateway 4 Click Save 5 If the intended application calls for a DHCP connection simply select the DHCP option and click Save Changing the Wireless Network Information All WT Ser...

Page 5: ...All DIDs in the grid are currently connected to the gateway Note WT 4000 Series thermostats take up to 5 minutes to appear in the grid 2 Ensure that the DIDs of all the physically installed devices ar...

Page 6: ...eps to restart the BACnet application and enable discovery of the device 1 Ensure that all configuration tasks are complete including changing wireless network addresses modifying IP connection parame...

Page 7: ...m temperature allowed in the zone default 50 F AV 14 Override_Period Override duration with one minute increments default 120 minutes maximum 240 minutes AV 15 Override_Up_D Comfort zone upper delta d...

Page 8: ...s in PSI AV 73 Low_PSI_Value In the case where Error Reporting Register indicates insufficient pressure this register holds the maximum branch line pressure of the system at that time in PSI AI 79 Tem...

Page 9: ...connected devices Update refreshes the count to check for newly connected devices Wireless Network Info Shows information about the WT BAC IP s GID DID and Channel all three fields are editable Conne...

Page 10: ...NA SA Single Point of Contact APAC Single Point of Contact JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS C O CONTROLS PRO...

Reviews: