Johnson Controls WT-BAC-IP Installation Instructions Manual Download Page 6

WT-BAC-IP Gateway Installation Instructions

6

Restarting the BACnet Application

The BACnet application that sources data for the BACnet objects does not run while the WT-BAC-IP Configuration 
Tool configures the WT-BAC-IP. The WT-BAC-IP is not discoverable while the tool is in use.

Perform the following steps to restart the BACnet application and enable discovery of the device.

1.

Ensure that all configuration tasks are complete (including changing wireless network addresses, modifying IP 
connection parameters, and creating the point map).

2.

Click 

Disconnect

 in the upper right-hand corner of the tool. Restarting the WT-BAC-IP takes up to 30 seconds. 

The following image appears.

3.

The WT-BAC-IP is now running and discoverable from the BAS.

Figure 8: Point Map Representation

Figure 9: WT-BAC-IP Running Notification

Summary of Contents for WT-BAC-IP

Page 1: ...ormal operating conditions Where failure or malfunction of the gateway could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be des...

Page 2: ...an IP Connection to the WT BAC IP Use the following steps to establish an IP connection to the WT BAC IP 1 Configure a temporary static IP address on your computer Windows 7 by going to Start Control...

Page 3: ...DHCP 5 Connect an Ethernet cable from your computer to the WT BAC IP Gateway 6 Plug the 12 VDC adapter into the WT BAC IP 7 Open the WT BAC IP Configuration Tool program 8 In the By MAC Address tab t...

Page 4: ...es the use of a default gateway 4 Click Save 5 If the intended application calls for a DHCP connection simply select the DHCP option and click Save Changing the Wireless Network Information All WT Ser...

Page 5: ...All DIDs in the grid are currently connected to the gateway Note WT 4000 Series thermostats take up to 5 minutes to appear in the grid 2 Ensure that the DIDs of all the physically installed devices ar...

Page 6: ...eps to restart the BACnet application and enable discovery of the device 1 Ensure that all configuration tasks are complete including changing wireless network addresses modifying IP connection parame...

Page 7: ...m temperature allowed in the zone default 50 F AV 14 Override_Period Override duration with one minute increments default 120 minutes maximum 240 minutes AV 15 Override_Up_D Comfort zone upper delta d...

Page 8: ...s in PSI AV 73 Low_PSI_Value In the case where Error Reporting Register indicates insufficient pressure this register holds the maximum branch line pressure of the system at that time in PSI AI 79 Tem...

Page 9: ...connected devices Update refreshes the count to check for newly connected devices Wireless Network Info Shows information about the WT BAC IP s GID DID and Channel all three fields are editable Conne...

Page 10: ...NA SA Single Point of Contact APAC Single Point of Contact JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS C O CONTROLS PRO...

Reviews: