WT-BAC-IP Gateway Installation Instructions

7

WT-BAC-IP Gateway Point Mapping

The following table lists the BACnet objects associated with the WT-BAC-IP Gateway. The WT-BAC-IP also 
sources BACnet objects for all its connected devices. Refer to the respective documentation for more information 
about the BACnet objects.  

Table 1:  BACnet Objects of the WT-BAC-IP Gateway (Part 1 of 2)

Register 
Number

Point Name

Description

BACnet 
Object 
Type

5

Occupancy_Mode

Occupancy mode requested by the BAS:
1 – occupied; 2 – constrained float (unoccupied); 3 to 6 – reserved; 7 – 
shoulder mode (shallow setback, also used in demand response events)

AV

7

Comfort_Up_D

Comfort zone upper range relative to system master setpoint; default 3°F; 
maximum comfort zone 14° F

AV

8

Comfort_Lo_D

Comfort zone lower range relative to system master setpoint; default 3°F; 
maximum comfort zone 14° F

AV

10

Setback_Up_L

Upper temperature limit in unoccupied setback mode; default 85°F; maximum 
value restricted by Protect_Up_L temperature (register 12)

AV

11

Setback_Lo_L

Lower temperature limit in unoccupied setback mode; default 55°F; minimum 
value restricted by Protect_Lo_L temperature (register 13)

AV

12

Protect_Up_L

Maximum temperature allowed in the zone; default 90°F

AV

13

Protect_Lo_L

Minimum temperature allowed in the zone; default 50° F

AV

14

Override_Period

Override duration with one-minute increments; default 120 minutes; maximum 
240 minutes

AV

15

Override_Up_D

Comfort zone upper delta during override mode; default 5° F; maximum 14° F

AV

16

Override_Lo_D

Comfort zone lower delta during override mode; default 5° F; maximum 14° F

AV

18

Dead_Band

Temperature control deadband; default 1° F; maximum 14° F

AV

31

Shoulder_Up_D

Upper delta; default 5°F.
In shoulder mode, the device does not call for cool if space temperature is 
below setpoint plus upper delta.

AV

Shoulder_Lo_D

Lower delta; default 5°F.
In shoulder mode, device does not call for heat if space temperature is above 
setpoint minus lower delta.

AV

33

Display_Mode

Display mode setting:
0 – normal LCD and button functionality; 1 – temperature is not displayed and 
buttons are disabled; 2 – normal LCD functionality but buttons are disabled
If set to any other value, everything is displayed as normal and buttons are 
enabled; this feature is not supported in stand-alone mode.

AV

54

UTC_High

High indicates 16 bits of 32 bit time stamp in UTC format (UNIX epoch time).

AI

55

UTC_Low

Low indicates 16 bits of 32 bit time stamp in UTC format (UNIX epoch time).

AI

57

Space_Temp

Space temperature value in °F

AI

58

BL_PSI_Rqstd

The branch line pressure requested by the unit based on temperature 
measurement, in PSI.

AI

BL_PSI_Msrd

The actual branch line pressure measured by the pressure sensor, in PSI.

AI

Summary of Contents for WT-BAC-IP

Page 1: ...ormal operating conditions Where failure or malfunction of the gateway could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be des...

Page 2: ...an IP Connection to the WT BAC IP Use the following steps to establish an IP connection to the WT BAC IP 1 Configure a temporary static IP address on your computer Windows 7 by going to Start Control...

Page 3: ...DHCP 5 Connect an Ethernet cable from your computer to the WT BAC IP Gateway 6 Plug the 12 VDC adapter into the WT BAC IP 7 Open the WT BAC IP Configuration Tool program 8 In the By MAC Address tab t...

Page 4: ...es the use of a default gateway 4 Click Save 5 If the intended application calls for a DHCP connection simply select the DHCP option and click Save Changing the Wireless Network Information All WT Ser...

Page 5: ...All DIDs in the grid are currently connected to the gateway Note WT 4000 Series thermostats take up to 5 minutes to appear in the grid 2 Ensure that the DIDs of all the physically installed devices ar...

Page 6: ...eps to restart the BACnet application and enable discovery of the device 1 Ensure that all configuration tasks are complete including changing wireless network addresses modifying IP connection parame...

Page 7: ...m temperature allowed in the zone default 50 F AV 14 Override_Period Override duration with one minute increments default 120 minutes maximum 240 minutes AV 15 Override_Up_D Comfort zone upper delta d...

Page 8: ...s in PSI AV 73 Low_PSI_Value In the case where Error Reporting Register indicates insufficient pressure this register holds the maximum branch line pressure of the system at that time in PSI AI 79 Tem...

Page 9: ...connected devices Update refreshes the count to check for newly connected devices Wireless Network Info Shows information about the WT BAC IP s GID DID and Channel all three fields are editable Conne...

Page 10: ...NA SA Single Point of Contact APAC Single Point of Contact JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS C O CONTROLS PRO...

Reviews: