Johnson Controls WT-BAC-IP Installation Instructions Manual Download Page 1

WT-BAC-IP Gateway Installation Instructions

1

 Refer to the 

QuickLIT website

 for the most up-to-date version of this document.

Application

The WT-BAC-IP Gateway is a multi-function device that performs wireless mesh network management tasks and 
provides bidirectional communication between the wireless devices of the Johnson Controls® WT-4000 Series 
Pneumatic-to-Direct Digital Control (DDC) Room Thermostat System and the BACnet® IP Client. The gateway 
communicates wirelessly with its associated devices and performs all the high-level system functions, such as 
BACnet object creation and object sourcing. This robust mesh network supports up to 100 wireless devices per 
WT-BAC-IP Gateway.

The WT-BAC-IP Gateway is designed for indoor, intra-building applications only. The gateway uses 
direct-sequence, spread-spectrum RF technology, and operates on the 2.4 GHz Industrial, Scientific, and Medical 
(ISM) band. The gateway meets the IEEE 802.15.4 standard for low power, low duty cycle RF transmitting 
systems. 

  

North American Emissions Compliance

United States 

Canada 

IMPORTANT:

Use the WT-BAC-IP Gateway only to provide an input to equipment under normal operating 

conditions. Where failure or malfunction of the gateway could lead to personal injury or property damage to the 
controlled equipment or other property, additional precautions must be designed into the control system. 
Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, 
intended to warn of or protect against failure or malfunction of the gateway.

Compliance Statement (Part 15.19)

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:

1.

This device may not cause harmful interference, and

2.

This device must accept any interference received, including interference that may cause undesired 
operation.

Warning (Part 15.21)

Changes or modifications not expressly approved by the party responsible for compliance could void the user’s 
authority to operate the equipment.

Industry Canada Statement

The term 

IC

 before the certification/registration number only signifies that the Industry Canada technical 

specifications were met.

Le terme « IC » précédant le numéro d'accréditation/inscription signifie simplement que le produit est conforme 
aux spécifications techniques d'Industry Canada.

WT-BAC-IP Gateway

Installation Instructions

WT-BAC-IP

Part No. 24-10732-21, Rev. B

Issued June 2017

24- 10732- 21,  Rev .  B

(barcode for factory use only)

Summary of Contents for WT-BAC-IP

Page 1: ...ormal operating conditions Where failure or malfunction of the gateway could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be des...

Page 2: ...an IP Connection to the WT BAC IP Use the following steps to establish an IP connection to the WT BAC IP 1 Configure a temporary static IP address on your computer Windows 7 by going to Start Control...

Page 3: ...DHCP 5 Connect an Ethernet cable from your computer to the WT BAC IP Gateway 6 Plug the 12 VDC adapter into the WT BAC IP 7 Open the WT BAC IP Configuration Tool program 8 In the By MAC Address tab t...

Page 4: ...es the use of a default gateway 4 Click Save 5 If the intended application calls for a DHCP connection simply select the DHCP option and click Save Changing the Wireless Network Information All WT Ser...

Page 5: ...All DIDs in the grid are currently connected to the gateway Note WT 4000 Series thermostats take up to 5 minutes to appear in the grid 2 Ensure that the DIDs of all the physically installed devices ar...

Page 6: ...eps to restart the BACnet application and enable discovery of the device 1 Ensure that all configuration tasks are complete including changing wireless network addresses modifying IP connection parame...

Page 7: ...m temperature allowed in the zone default 50 F AV 14 Override_Period Override duration with one minute increments default 120 minutes maximum 240 minutes AV 15 Override_Up_D Comfort zone upper delta d...

Page 8: ...s in PSI AV 73 Low_PSI_Value In the case where Error Reporting Register indicates insufficient pressure this register holds the maximum branch line pressure of the system at that time in PSI AI 79 Tem...

Page 9: ...connected devices Update refreshes the count to check for newly connected devices Wireless Network Info Shows information about the WT BAC IP s GID DID and Channel all three fields are editable Conne...

Page 10: ...NA SA Single Point of Contact APAC Single Point of Contact JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS C O CONTROLS PRO...

Reviews: