(for 90° VAV boxes). For 45° and 60° VAV

boxes, the actuator stroke time must be

adjusted. Refer to the 

Controller Tool Help

(LIT-12011147)

 for instructions on setting

the actuator stroke time in the application.

7.  Tighten the square coupler bolt to the shaft

using an 8 mm (5/16 in.) wrench or 10 mm (3/8

in.) 12-point socket. Tighten to 10.5 to 11.5 N·m

(95 to 105 lb·in).

8.  Loop the pneumatic tubing to include a trap for

condensation. If needed, use the included brass

fittings and attach the included pieces of tubing

to the tubing of the VMA controller. Attach the

tubing from the VMA controller to the dual port

fitting on the VMA controller and the other ends

of the tubing to the pressure transducer in the

VAV box application (Figure 1). The VMA1826

does not come with the tubing pieces.

Note: 

The VMA uses a digital non-flow

pressure sensor with bidirectional flow

operation, which allows the high- and

low-pressure DP tube connections to

be made to either barbed fitting on the

VMA controller. You do not need to make

a specific high- or low-side connection

when you attach the tubing to the barbed

fittings on the VMA.

9.  Push the manual release button, and turn the

actuator coupling manually to ensure that the

actuator can rotate from full-closed to full-open

positions without binding.

10.  Complete the mounting by rotating the damper

to the full-open position.

 CAUTION

Risk of Property Damage

Rotate the damper to the full-open position before

starting the air handler. Failure to rotate the damper to

the full-open position may result in damage to the VAV

box or ductwork when the air handler is started.

 ATTENTION

Mise En Garde: Risque de dégâts matériels

Faire pivoter le registre pour le placer en position

d'ouverture complète avant de démarrer l'unité de

traitement d'air. Le non-respect de cette directive

risque d'endommager le caisson de l'unité à volume

d'air variable (VAV) ou le réseau de conduites au dé-

marrage de l'unité de traitement d'air.

Wiring

 WARNING

Risk of Electric Shock

Disconnect the power supply before making electrical

connections to avoid electric shock.

 AVERTISSEMENT

Mise En Garde: Risque de décharge électrique:

Débrancher l'alimentation avant de réaliser tout rac-

cordement électrique afin d'éviter tout risque de

décharge

Important: 

Do not connect supply power

to the controller before finishing wiring and

checking all wiring connections. Short circuits

or improperly connected wires can result

in damage to the controller and void any

warranty.

Important: 

Do not exceed the controller

electrical ratings. Exceeding controller electrical

ratings can result in permanent damage to the

controller and void any warranty.

Important: 

Use copper conductors only. Make

all wiring in accordance with local, national, and

regional regulations.

Important: 

Electrostatic discharge can

damage controller components. Use proper

electrostatic discharge precautions during

installation, setup, and servicing to avoid

damaging the controller.

VMA1826/1832 VAV Controller Installation Guide

5

Summary of Contents for VMA18 Series

Page 1: ...cting an IOM to the VMA via the SA Bus connection is not supported For information about sensor compatibility and replacement see Sensor replacement and reuse scenarios North American emissions compli...

Page 2: ...river for securing wires in the terminal blocks 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point socket to tighten the square coupler bolt Several shims or washers to mount the VMA Power screwdriver 100 m...

Page 3: ...t condensation to fall away from the VMA Additional measures may be required in some installations Ensure the mounting surface can support the VMA and any user supplied enclosure Mount the VMA on a ha...

Page 4: ...r the threads may strip If mounting to the VAV box make sure the screws do not interfere with damper blade movement 3 Locate the damper position using the typical marking on the end of the damper shaf...

Page 5: ...e the damper to the full open position before starting the air handler Failure to rotate the damper to the full open position may result in damage to the VAV box or ductwork when the air handler is st...

Page 6: ...n Figure 4 See Table 5 and Table 6 for more information Figure 4 N2 FC bus terminal block wiring Note The Shield terminal SHLD on the N2 FC Bus terminal block is isolated and can be used to connect th...

Page 7: ...ss the network devices Powering network devices with uniform 24 VAC supply power phasing reduces noise interference and ground loop problems The VMA does not require an earth ground connection However...

Page 8: ...to the wire size and the load current in mA when wiring inputs and outputs N2 FC and SA bus and supply power wiring guidelines Table 6 provides information about terminal block functions ratings and r...

Page 9: ...ut Termination diagrams Voltage Input Internal Source UI Voltage Input Self Powered UI Temperature Sensor UI Dry Contact UI 0 10 VDC Output to Actuator Internal Source CO 0 10 VDC Output to Actuator E...

Page 10: ...plies to CO4 and CO5 Analog Output Voltage CO 24 VAC Binary Output Switch Low Internally Sourced BO Note Applies to BO1 BO2 and BO3 Incremental Control to Actuator Switch Low Internally Sourced BO Not...

Page 11: ...ontroller The VMA142x controller has five binary outputs BOs and internally supplies 24 VAC The VMA18 controller has three binary outputs BOs and supplies 24 VAC to these BOs The VMA18 controller has...

Page 12: ...A18 controllers See Table 3 for a description of the most popular sensor models used with the VMA1410 VMA1415 VMA1420 and the VMA controllers the sensor replacement and reuse scenarios for that sensor...

Page 13: ...ally equivalent NS Series Network Sensor follow the instructions in the Replacing a TE 6xxx series sensor section To reuse a TE 6xxx Series Sensor connected to a VMA controller follow the instructions...

Page 14: ...apter assembly in the existing wall opening behind the sensor Refer to the installation instructions for the applicable NS Series Sensor model 5 Plug the BTCVT into the 6 pin socket on the NS Series N...

Page 15: ...0 Series Wireless Transmitter and TE 7720 0 Wireless Receiver connected to a VMA Controller To replace a TE 7710 0 Series Wireless Transmitter and TE 7720 0 Wireless Receiver connected to a VMA contro...

Page 16: ...a TE 700 Series sensor See the instructions in this section to reuse a TE 700 Series Sensor when connected to a VMA18 controller 1 Disconnect the 8 pin male jack plugged into the VMA controller 2 Plu...

Page 17: ...ensor Negative Temperature Coefficient NTC Sensor 10K Type L 10K JCI Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 5 INn Binary Input Dry Contact Maintained Mode 1 second...

Page 18: ...or recommended wire sizes Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975...

Page 19: ...Supply Common The 0 models isolate this terminal from all other commons The 1 models only isolate this terminal from the FC bus common 0 8 mm to 1 0 mm 20 to 18 AWG 2 wire 1 To determine wire size and...

Page 20: ...e sum of the switch numbers set to ON equals the intended device address Set the highest number switch that is less than or equal to the intended device address to ON Then continue setting lower numbe...

Page 21: ...procedures Refer to the Controller Tool Help LIT 12011147 CCT connects to the VMA through a laptop computer using any one of the following connection options the MAP Gateway BTCVT the Wireless ZigBee...

Page 22: ...OUT3 terminals of binary outputs are not connected to 24 VAC COM verify that OCOM1 OCOM3 are not connected to 24 VAC HOT these terminals are internally sourced 3 Verify the short circuit has been reso...

Page 23: ...24 VAC Secondary 92 VA Foot Mount 30 in Primary Leads and 30 in Secondary Leads Class 2 Y65A13 0 Transformer 120 VAC Primary to 24 VAC Secondary 40 VA Foot Mount Y65AS 8 in Primary Leads and 30 in Se...

Page 24: ...es 4 127 Device addresses 0 3 and 128 255 are reserved and not valid field controller addresses Communications Bus N2 Open Protocol N2 FC Bus 1 5 mm 18 AWG standard 3 wire twisted shielded cable recom...

Page 25: ...oduct is in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004 108 EC Compliance Australia and New Zealand RCM Mark Australia NZ Emissions Compliant Pro...

Page 26: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Reviews: