background image

DIP switch block at the top of the controller (Figure

1). Device addresses 1 through 253 are the valid N2

addresses for these N2 controllers.
Valid MS/TP addresses for wired controllers are

4 through 127. For wireless controllers, valid

addresses are 132 through 254 (132 [132-128=4]

through 254 [254-128=126]).
For wireless controllers, the address 120 through

127 are used by the ZigBee

®

 Coordinator. This may

cause a smaller field device range.
If the VMA18 Series controller may eventually be

converted to MS/TP, use addresses 4 through

127 for a wired VMA controller or addresses 132

through 253 for a future wireless VMA controller, if

possible. Using these addresses simplifies the MS/

TP conversion process.

Note: 

Metasys

 field controllers ship with

Switch 128 ON and the remaining address

switches OFF rendering the controllers wired

subordinate devices, which do not operate

on MS/TP buses, but do not interfere with

bus operation. Set a valid and unique device

address on the field controller before applying

power to the controller on the bus.

The DIP switch block (Figure 14) has eight switches

numbered 128, 64, 32, 16, 8, 4, 2, and 1. Switches 128

through 1 are device address switches.

Figure 14: Device address switches set to 21

To set the device addresses on a 

Metasys

 field

controller:

1.  Set all of the switches on the field controller’s

device address DIP switch block (128 through 1)

to OFF.

2.  Set one or more of the eight address switches

(128 through 1) to ON, so that the sum of the

switch numbers set to ON equals the intended

device address. Set the highest number switch

that is less than or equal to the intended device

address to ON. Then continue setting lower

numbered switches until the total equals the

intended address. For example, if the intended

device address is 21, set Switch 16 to ON first,

then set Switch 4 to ON, followed by Switch 1

(16+4+1=21). See Figure 14.

3.  Set a unique and sequential device address

for each of the field controllers connected on

the N2 bus, starting with device address 1.

To ensure the best bus performance (if the

protocol is changed to BACnet MS/TP), set

sequential device addresses with no gaps in

the device address range (4, 5, 6, 7, 8, 9, and

so on). The field controllers do not need to

be physically connected on the bus in their

numerical device address order.

4.  Write each field controller’s device address on

the white label below the DIP switch block on

the controller’s cover.

Refer to the 

N2 Communications Bus Technical Bulletin

(LIT-636018)

 for more information on field controller

device addresses and how to set them on N2 buses.

Setting the EOL switch

Each field controller has an EOL (End of Line) switch,

which, when set to ON (up), sets the field controller

as a terminating device on the bus. See Figure 1 for

the EOL switch location on the field controller. The

default EOL switch position is OFF (down).

Figure 15: EOL switch positions

To set the EOL switch on a field controller:

1.  Determine the physical location of the field

controller on the N2 or FC Bus.

2.  Determine if the field controller must be set as

a terminating device on the bus.

VMA1826/1832 VAV Controller Installation Guide

20

Summary of Contents for VMA18 Series

Page 1: ...cting an IOM to the VMA via the SA Bus connection is not supported For information about sensor compatibility and replacement see Sensor replacement and reuse scenarios North American emissions compli...

Page 2: ...river for securing wires in the terminal blocks 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point socket to tighten the square coupler bolt Several shims or washers to mount the VMA Power screwdriver 100 m...

Page 3: ...t condensation to fall away from the VMA Additional measures may be required in some installations Ensure the mounting surface can support the VMA and any user supplied enclosure Mount the VMA on a ha...

Page 4: ...r the threads may strip If mounting to the VAV box make sure the screws do not interfere with damper blade movement 3 Locate the damper position using the typical marking on the end of the damper shaf...

Page 5: ...e the damper to the full open position before starting the air handler Failure to rotate the damper to the full open position may result in damage to the VAV box or ductwork when the air handler is st...

Page 6: ...n Figure 4 See Table 5 and Table 6 for more information Figure 4 N2 FC bus terminal block wiring Note The Shield terminal SHLD on the N2 FC Bus terminal block is isolated and can be used to connect th...

Page 7: ...ss the network devices Powering network devices with uniform 24 VAC supply power phasing reduces noise interference and ground loop problems The VMA does not require an earth ground connection However...

Page 8: ...to the wire size and the load current in mA when wiring inputs and outputs N2 FC and SA bus and supply power wiring guidelines Table 6 provides information about terminal block functions ratings and r...

Page 9: ...ut Termination diagrams Voltage Input Internal Source UI Voltage Input Self Powered UI Temperature Sensor UI Dry Contact UI 0 10 VDC Output to Actuator Internal Source CO 0 10 VDC Output to Actuator E...

Page 10: ...plies to CO4 and CO5 Analog Output Voltage CO 24 VAC Binary Output Switch Low Internally Sourced BO Note Applies to BO1 BO2 and BO3 Incremental Control to Actuator Switch Low Internally Sourced BO Not...

Page 11: ...ontroller The VMA142x controller has five binary outputs BOs and internally supplies 24 VAC The VMA18 controller has three binary outputs BOs and supplies 24 VAC to these BOs The VMA18 controller has...

Page 12: ...A18 controllers See Table 3 for a description of the most popular sensor models used with the VMA1410 VMA1415 VMA1420 and the VMA controllers the sensor replacement and reuse scenarios for that sensor...

Page 13: ...ally equivalent NS Series Network Sensor follow the instructions in the Replacing a TE 6xxx series sensor section To reuse a TE 6xxx Series Sensor connected to a VMA controller follow the instructions...

Page 14: ...apter assembly in the existing wall opening behind the sensor Refer to the installation instructions for the applicable NS Series Sensor model 5 Plug the BTCVT into the 6 pin socket on the NS Series N...

Page 15: ...0 Series Wireless Transmitter and TE 7720 0 Wireless Receiver connected to a VMA Controller To replace a TE 7710 0 Series Wireless Transmitter and TE 7720 0 Wireless Receiver connected to a VMA contro...

Page 16: ...a TE 700 Series sensor See the instructions in this section to reuse a TE 700 Series Sensor when connected to a VMA18 controller 1 Disconnect the 8 pin male jack plugged into the VMA controller 2 Plu...

Page 17: ...ensor Negative Temperature Coefficient NTC Sensor 10K Type L 10K JCI Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 5 INn Binary Input Dry Contact Maintained Mode 1 second...

Page 18: ...or recommended wire sizes Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975...

Page 19: ...Supply Common The 0 models isolate this terminal from all other commons The 1 models only isolate this terminal from the FC bus common 0 8 mm to 1 0 mm 20 to 18 AWG 2 wire 1 To determine wire size and...

Page 20: ...e sum of the switch numbers set to ON equals the intended device address Set the highest number switch that is less than or equal to the intended device address to ON Then continue setting lower numbe...

Page 21: ...procedures Refer to the Controller Tool Help LIT 12011147 CCT connects to the VMA through a laptop computer using any one of the following connection options the MAP Gateway BTCVT the Wireless ZigBee...

Page 22: ...OUT3 terminals of binary outputs are not connected to 24 VAC COM verify that OCOM1 OCOM3 are not connected to 24 VAC HOT these terminals are internally sourced 3 Verify the short circuit has been reso...

Page 23: ...24 VAC Secondary 92 VA Foot Mount 30 in Primary Leads and 30 in Secondary Leads Class 2 Y65A13 0 Transformer 120 VAC Primary to 24 VAC Secondary 40 VA Foot Mount Y65AS 8 in Primary Leads and 30 in Se...

Page 24: ...es 4 127 Device addresses 0 3 and 128 255 are reserved and not valid field controller addresses Communications Bus N2 Open Protocol N2 FC Bus 1 5 mm 18 AWG standard 3 wire twisted shielded cable recom...

Page 25: ...oduct is in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004 108 EC Compliance Australia and New Zealand RCM Mark Australia NZ Emissions Compliant Pro...

Page 26: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Reviews: