background image

To mount the VMA18 Series controller, complete the

following steps:

1.  Place the VMA18 Series controller in the proper

mounting position on the damper shaft so that

the wiring connections are easily accessible.

Note: 

The line from the captive spacer and

screw through the center of the damper

shaft must be either horizontal or vertical,

and the wall plate must be wall-mounted

to comply with UL requirements. See the

following figure for possible mounting

positions.

Figure 2: Possible VMA18 Series Controller

Mounting Positions

Make sure the VMA controller base is parallel

to the VAV box (perpendicular to the damper

shaft). If needed, use a spacer to offset tipping

of the VMA controller caused by the shaft

bushings.

Note: 

Using the alignment marks to center

the captive spacer ensures sufficient

VMA18 controller movement in either

direction.

2.  Secure the self-drilling No. 10 screw through

the shoulder washer (Figure 1) with a power

screwdriver and 100 mm (4 in.) extension

socket. Otherwise, use a punch to mark the

position of the shoulder washer, and then drill a

hole into the VAV box using a 3.5 mm (9/64 in.)

drill bit. Insert the mounting screw and tighten

against the washer.

Note: 

The mounting screw for the VMA

controller does not use the same hole

as the screw for the VMA1410, VMA1415,

VMA1420, and the VMA1440 controller.

We recommend plugging the unused

open hole with the screw from the original

VMA14 mounting when using the VMA18

to replace a VMA14 Series controller.

Important: 

Do not overtighten the screws,

or the threads may strip. If mounting to

the VAV box, make sure the screws do not

interfere with damper blade movement.

3.  Locate the damper position using the typical

marking on the end of the damper shaft. See

the following figure.

Figure 3: Typical damper end shaft icons

4.  Note the direction, clockwise (CW) or

counterclockwise (CCW), required to close the

damper. Grasp the damper shaft firmly with

pliers, and either manually close the damper

(for 90° boxes) or manually open the damper

(for 45° or 60° boxes).

5.  Push down and hold the Manual Override

button (Figure 1) and turn the VMA controller

coupler until it contacts the mechanical end-

stop at either the fully closed (90° boxes) or

fully open (45° and 60° boxes) position.

6.  If the damper for a 90° box closes CCW, rotate

the coupler to the CCW mechanical limit. If the

damper for a 90° box closes CW, rotate the

coupler to the CW mechanical limit. The open

end-stop is automatically set for 90° boxes. For

45° and 60° boxes, hard stops must be provided

at both fully closed and fully open damper

positions. By installing the VMA controller at the

fully open position, the VMA controller provides

the open stop for 45° and 60° boxes. The closed

damper seal provides the fully closed stop.

Important: 

The integrated actuator has

a stroke time of 60 seconds for 90° of

travel. The stroke time is the amount of

time (in seconds) that it takes the actuator

to move from the fully closed to fully

opened position or from fully open to fully

closed position. For proper operation, the

actuator stroke time must be configured

in the CCT application based on the actual

time it takes the actuator to drive the

damper. The default setting is 60 seconds

VMA1826/1832 VAV Controller Installation Guide

4

Summary of Contents for VMA18 Series

Page 1: ...cting an IOM to the VMA via the SA Bus connection is not supported For information about sensor compatibility and replacement see Sensor replacement and reuse scenarios North American emissions compli...

Page 2: ...river for securing wires in the terminal blocks 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point socket to tighten the square coupler bolt Several shims or washers to mount the VMA Power screwdriver 100 m...

Page 3: ...t condensation to fall away from the VMA Additional measures may be required in some installations Ensure the mounting surface can support the VMA and any user supplied enclosure Mount the VMA on a ha...

Page 4: ...r the threads may strip If mounting to the VAV box make sure the screws do not interfere with damper blade movement 3 Locate the damper position using the typical marking on the end of the damper shaf...

Page 5: ...e the damper to the full open position before starting the air handler Failure to rotate the damper to the full open position may result in damage to the VAV box or ductwork when the air handler is st...

Page 6: ...n Figure 4 See Table 5 and Table 6 for more information Figure 4 N2 FC bus terminal block wiring Note The Shield terminal SHLD on the N2 FC Bus terminal block is isolated and can be used to connect th...

Page 7: ...ss the network devices Powering network devices with uniform 24 VAC supply power phasing reduces noise interference and ground loop problems The VMA does not require an earth ground connection However...

Page 8: ...to the wire size and the load current in mA when wiring inputs and outputs N2 FC and SA bus and supply power wiring guidelines Table 6 provides information about terminal block functions ratings and r...

Page 9: ...ut Termination diagrams Voltage Input Internal Source UI Voltage Input Self Powered UI Temperature Sensor UI Dry Contact UI 0 10 VDC Output to Actuator Internal Source CO 0 10 VDC Output to Actuator E...

Page 10: ...plies to CO4 and CO5 Analog Output Voltage CO 24 VAC Binary Output Switch Low Internally Sourced BO Note Applies to BO1 BO2 and BO3 Incremental Control to Actuator Switch Low Internally Sourced BO Not...

Page 11: ...ontroller The VMA142x controller has five binary outputs BOs and internally supplies 24 VAC The VMA18 controller has three binary outputs BOs and supplies 24 VAC to these BOs The VMA18 controller has...

Page 12: ...A18 controllers See Table 3 for a description of the most popular sensor models used with the VMA1410 VMA1415 VMA1420 and the VMA controllers the sensor replacement and reuse scenarios for that sensor...

Page 13: ...ally equivalent NS Series Network Sensor follow the instructions in the Replacing a TE 6xxx series sensor section To reuse a TE 6xxx Series Sensor connected to a VMA controller follow the instructions...

Page 14: ...apter assembly in the existing wall opening behind the sensor Refer to the installation instructions for the applicable NS Series Sensor model 5 Plug the BTCVT into the 6 pin socket on the NS Series N...

Page 15: ...0 Series Wireless Transmitter and TE 7720 0 Wireless Receiver connected to a VMA Controller To replace a TE 7710 0 Series Wireless Transmitter and TE 7720 0 Wireless Receiver connected to a VMA contro...

Page 16: ...a TE 700 Series sensor See the instructions in this section to reuse a TE 700 Series Sensor when connected to a VMA18 controller 1 Disconnect the 8 pin male jack plugged into the VMA controller 2 Plu...

Page 17: ...ensor Negative Temperature Coefficient NTC Sensor 10K Type L 10K JCI Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 5 INn Binary Input Dry Contact Maintained Mode 1 second...

Page 18: ...or recommended wire sizes Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975...

Page 19: ...Supply Common The 0 models isolate this terminal from all other commons The 1 models only isolate this terminal from the FC bus common 0 8 mm to 1 0 mm 20 to 18 AWG 2 wire 1 To determine wire size and...

Page 20: ...e sum of the switch numbers set to ON equals the intended device address Set the highest number switch that is less than or equal to the intended device address to ON Then continue setting lower numbe...

Page 21: ...procedures Refer to the Controller Tool Help LIT 12011147 CCT connects to the VMA through a laptop computer using any one of the following connection options the MAP Gateway BTCVT the Wireless ZigBee...

Page 22: ...OUT3 terminals of binary outputs are not connected to 24 VAC COM verify that OCOM1 OCOM3 are not connected to 24 VAC HOT these terminals are internally sourced 3 Verify the short circuit has been reso...

Page 23: ...24 VAC Secondary 92 VA Foot Mount 30 in Primary Leads and 30 in Secondary Leads Class 2 Y65A13 0 Transformer 120 VAC Primary to 24 VAC Secondary 40 VA Foot Mount Y65AS 8 in Primary Leads and 30 in Se...

Page 24: ...es 4 127 Device addresses 0 3 and 128 255 are reserved and not valid field controller addresses Communications Bus N2 Open Protocol N2 FC Bus 1 5 mm 18 AWG standard 3 wire twisted shielded cable recom...

Page 25: ...oduct is in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004 108 EC Compliance Australia and New Zealand RCM Mark Australia NZ Emissions Compliant Pro...

Page 26: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Reviews: