TFP330

Page 2 of 4

Design 

Criteria

UL and C-UL Listing Requirements

The TYCO 16.8 K-factor, Ultra K17, 

Standard Response, Upright Control 

Mode Specific Application Sprin-

kler may be installed in accordance 

with NFPA 13 “Control Mode Specific 

Application Sprinkler (for Storage Use)” 

requirements to provide ceiling only 

protection (that is, no in-rack sprin-

klers) for high piled storage occupan-

cies (Solid-piled, palletized and rack 

storage including but not limited to 

Class I-IV and Group A plastics) using 

the criteria from NFPA 13. Refer to 

Table B for additional information.

FM Approval Requirements

The TYCO 16.8 K-factor, Ultra K17  

Sprinklers may be installed with the 

applicable storage sprinkler guide-

lines provided by Factory Mutual. (FM 

guidelines may differ from UL and C-UL 

Listing criteria.)

Item

Description

Sprinkler Identification Number (SIN)

TY7153

TY7153 is a redesignation for C7153,  

G1887, and S8042.

K-factor, gpm/psi

½

 (lpm/bar

½

)

16.8 gpm/psi

½

 (241,9 lpm/bar

½

)

Temperature Rating ºF (ºC)

1

155ºF (68ºC)

1

 

200ºF (93ºC)

Thread Size

3/4 in. NPT

Sprinkler Orientation

Upright

Maximum Working Pressure, psi (bar)

175 psi (12 bar)

Note:

1.  Refer to Table C for laboratory listings and approvals.

*

*

*

UPRIGHT

CROSS SECTION

1

2

3

4

5

6

-

2

Button

Compression

Screw

Bulb

Sealing Assembly

-

6

-

4

5 -

3 -

Frame

1 -

Deflector

2-3/8"

(60,3 mm)

WRENCH

FLAT

Temperature rating is

indicated on deflector.

1/2"

(12,7 mm)

NOMINAL

MAKE-IN

3/4"

NPT

FIGURE 1 

ULTRA K17, 155°F (68°C) & 200°F (93°C), 

UPRIGHT SPRINKLER (TY7153)

TABLE A 

ULTRA K17 UPRIGHT SPRINKLER 

TECHNICAL DATA

Summary of Contents for tyco ULTRA K17

Page 1: ...7 Upright Control Mode Specific Application Sprinkler are expanding beyond the current specific application listings approvals For information regard ing research fire tests which may be acceptable to an authority having juris diction please contact the Technical Services Department NOTICE The Ultra K17 Standard Response Upright Control Mode Specific Applica tion Sprinkler described herein must be...

Page 2: ...lled with the applicable storage sprinkler guide lines provided by Factory Mutual FM guidelines may differ from UL and C UL Listing criteria Item Description Sprinkler Identification Number SIN TY7153 TY7153 is a redesignation for C7153 G1887 and S8042 K factor gpm psi lpm bar 16 8 gpm psi 241 9 lpm bar Temperature Rating ºF ºC 1 155ºF 68ºC 1 200ºF 93ºC Thread Size 3 4 in NPT Sprinkler Orientation...

Page 3: ...IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Solid Pile or Palletized Storage of Class I IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Idle Pallet Storage Refer to NFPA 13 Refer to FM 2 0 8 9 and 8 24 Rubber Tire Storage Refer to NFPA 13 Refer to FM 2 0 and 8 3 Roll Paper Storage Refer to the Standard Refer to NFPA 13 Refer to FM 8 21 Flammable Igni...

Page 4: ...onnel who may be affected by this action must be notified Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced Automatic sprinklers must never be painted plated coated or other wise altered after leaving the factory Modified sprinklers must be replaced Sprinklers that have been exposed to corrosive products of combustion but have not operated should be ...

Reviews: