background image

TFP330

Page 3 of 4

SPRINKLER FINISH

TYPE

TEMPERATURE

BULB 

LIQUID

NATURAL BRASS WITH 

CHROME DEFLECTOR

UPRIGHT K16.8 (TY7153)

155ºF (68ºC)

Red

3, 4

200ºF (93ºC)

Green

1, 2, 3, 4

NOTES:

1.  Listed by Underwriters Laboratories, Inc. (UL Listed)
2.  Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL Listed)
3.  Approved by Factory Mutual Research Corporation (FM Approved)
4.  Approved by the City of New York under MEA 177-03-E

Storage Type

NFPA

FM Global

Sprinkler Type

CMSA

Storage

Response Type

SR

SR

System Type

Wet and Dry

Wet and Dry

Temperature Rating ºF (ºC)

1

155ºF (68ºC)

1

 

200ºF (93ºC)

155ºF (68ºC)

1

 

200ºF (93ºC)

Open Frame (i.e., no solid shelves)

Single, Double, Multiple-Row, or Portable Rack Storage of 

Class I-IV and Group A or B Plastics

Refer to NFPA 13

Refer to FM 2-0 and 8-9

Solid Pile or Palletized Storage of 

Class I-IV and Group A or B Plastics

Refer to NFPA 13

Refer to FM 2-0 and 8-9

Idle Pallet Storage

Refer to NFPA 13

Refer to FM 2-0, 8-9, and 8-24

Rubber Tire Storage

Refer to NFPA 13

Refer to FM 2-0 and 8-3

Roll Paper Storage (Refer to the Standard)

Refer to NFPA 13

Refer to FM  8-21

Flammable/Ignitable Liquid Storage (Refer to the Standard)

Refer to NFPA 30

Refer to FM  7-29

Aerosol Storage (Refer to the Standard)

Refer to NFPA 30B

Refer to FM  7-31

Automotive Components in Portable Racks  

(Control mode only; refer to the Standard)

Refer to NFPA 13

N/A

Notes:

1.  Refer to Table C for laboratory listings and approvals.
N/A – Not Applicable

TABLE C 

LABORATORY LISTINGS AND APPROVALS

(Refer to the Design Criteria section)

TABLE B 

ULTRA K17 UPRIGHT SPRINKLER 

COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

Summary of Contents for tyco ULTRA K17

Page 1: ...7 Upright Control Mode Specific Application Sprinkler are expanding beyond the current specific application listings approvals For information regard ing research fire tests which may be acceptable to an authority having juris diction please contact the Technical Services Department NOTICE The Ultra K17 Standard Response Upright Control Mode Specific Applica tion Sprinkler described herein must be...

Page 2: ...lled with the applicable storage sprinkler guide lines provided by Factory Mutual FM guidelines may differ from UL and C UL Listing criteria Item Description Sprinkler Identification Number SIN TY7153 TY7153 is a redesignation for C7153 G1887 and S8042 K factor gpm psi lpm bar 16 8 gpm psi 241 9 lpm bar Temperature Rating ºF ºC 1 155ºF 68ºC 1 200ºF 93ºC Thread Size 3 4 in NPT Sprinkler Orientation...

Page 3: ...IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Solid Pile or Palletized Storage of Class I IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Idle Pallet Storage Refer to NFPA 13 Refer to FM 2 0 8 9 and 8 24 Rubber Tire Storage Refer to NFPA 13 Refer to FM 2 0 and 8 3 Roll Paper Storage Refer to the Standard Refer to NFPA 13 Refer to FM 8 21 Flammable Igni...

Page 4: ...onnel who may be affected by this action must be notified Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced Automatic sprinklers must never be painted plated coated or other wise altered after leaving the factory Modified sprinklers must be replaced Sprinklers that have been exposed to corrosive products of combustion but have not operated should be ...

Reviews: