Installation
The TYCO 16.8 K-factor, Ultra K17,
Standard Response, Upright Control
Mode Specific Application Sprinkler
must be installed in accordance with
this section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontal, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm).
A leak-tight 3/4 in. NPT sprinkler joint
should be obtained by applying a min-
imum-to-maximum torque of 7 to 14
lb-ft (9,5 to 19,0 N
∙
m). Higher levels of
torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Step 1.
With pipe thread sealant
applied to the pipe threads, hand
tighten the Ultra K17 Sprinkler into the
sprinkler fitting.
Step 2.
Using the W-Type 8 Sprinkler
Wrench (Ref. Figure 2) applied to the
sprinkler Wrench Flats (Ref. Figure 1),
tighten the Ultra K17 Sprinkler into the
sprinkler fitting.
Care and
Maintenance
The TYCO 16.8 K-factor, Ultra K17,
Standard Response, Upright Control
Mode Specific Application Sprinkler
must be maintained and serviced in
accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection systems must
be obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. Refer to Installation
section for additional information.
The owner is responsible for the inspec-
tion, testing, and maintenance of their
fire protection system and devices in
compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associ-
ation, such as NFPA 25, in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Ultra K17 (TY7153), K = 16.8,
Upright Control Mode Specific Appli-
cation Sprinkler, Standard Response,
(specify) temperature rating, P/N
(specify):
155°F (68°C). . . . . . . . . . . . . . . . . . 51-887-1-155
200°F (93°C) . . . . . . . . . . . . . . . . . 51-887-1-200
Sprinkler Wrench
Specify: W-Type 8 Sprinkler Wrench,
P/N 56-892-1-001
WRENCH
RECESS
FIGURE 2
W-TYPE 8
SPRINKLER WRENCH