Installation

The TYCO 16.8 K-factor, Ultra K17, 

Standard Response, Upright Control 

Mode Specific Application Sprinkler 

must be installed in accordance with 

this section.

General Instructions

Do not install any bulb type sprinkler 

if the bulb is cracked or there is a loss 

of liquid from the bulb. With the sprin-

kler held horizontal, a small air bubble 

should be present. The diameter of the 

air bubble is approximately 1/16 in.  

(1,6 mm).
A leak-tight 3/4 in. NPT sprinkler joint 

should be obtained by applying a min-

imum-to-maximum torque of 7 to 14 

lb-ft (9,5 to 19,0 N

m). Higher levels of 

torque can distort the sprinkler Inlet 

with consequent leakage or impairment 

of the sprinkler.

Step 1. 

With pipe thread sealant 

applied to the pipe threads, hand 

tighten the Ultra K17 Sprinkler into the 

sprinkler fitting.

Step 2. 

Using the W-Type 8 Sprinkler 

Wrench (Ref. Figure 2) applied to the 

sprinkler Wrench Flats (Ref. Figure 1), 

tighten the Ultra K17 Sprinkler into the 

sprinkler fitting.

Care and 

Maintenance

The TYCO 16.8 K-factor, Ultra K17, 

Standard Response, Upright Control 

Mode Specific Application Sprinkler 

must be maintained and serviced in 

accordance with this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system that 

it controls, permission to shut down the 

affected fire protection systems must 

be obtained from the proper authorities 

and all personnel who may be affected 

by this action must be notified.
Sprinklers that are found to be leaking 

or exhibiting visible signs of corrosion 

must be replaced.
Automatic sprinklers must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush.
Care must be exercised to avoid 

damage to the sprinklers before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be replaced. Also, replace any sprinkler 

that has a cracked bulb or that has lost 

liquid from its bulb. Refer to Installation 

section for additional information.
The owner is responsible for the inspec-

tion, testing, and maintenance of their 

fire protection system and devices in 

compliance with this document, as 

well as with the applicable standards 

of the National Fire Protection Associ-

ation, such as NFPA 25, in addition to 

the standards of any other authorities 

having jurisdiction. Contact the install-

ing contractor or product manufacturer 

with any questions.
Automatic sprinkler systems are rec-

ommended to be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

Ordering 

Procedure

Contact your local distributor for avail-

ability. When placing an order, indicate 

the full product name and Part Number 

(P/N).

Sprinkler Assemblies with NPT 

Thread Connections

Specify: Ultra K17 (TY7153), K = 16.8, 

Upright Control Mode Specific Appli-

cation Sprinkler, Standard Response, 

(specify) temperature rating, P/N 

(specify):

155°F (68°C). . . . . . . . . . . . . . . . . . 51-887-1-155

200°F (93°C)  . . . . . . . . . . . . . . . . . 51-887-1-200 

Sprinkler Wrench

Specify: W-Type 8 Sprinkler Wrench,  

P/N 56-892-1-001

WRENCH

RECESS

FIGURE 2  

W-TYPE 8 

SPRINKLER WRENCH

Summary of Contents for tyco ULTRA K17

Page 1: ...7 Upright Control Mode Specific Application Sprinkler are expanding beyond the current specific application listings approvals For information regard ing research fire tests which may be acceptable to an authority having juris diction please contact the Technical Services Department NOTICE The Ultra K17 Standard Response Upright Control Mode Specific Applica tion Sprinkler described herein must be...

Page 2: ...lled with the applicable storage sprinkler guide lines provided by Factory Mutual FM guidelines may differ from UL and C UL Listing criteria Item Description Sprinkler Identification Number SIN TY7153 TY7153 is a redesignation for C7153 G1887 and S8042 K factor gpm psi lpm bar 16 8 gpm psi 241 9 lpm bar Temperature Rating ºF ºC 1 155ºF 68ºC 1 200ºF 93ºC Thread Size 3 4 in NPT Sprinkler Orientation...

Page 3: ...IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Solid Pile or Palletized Storage of Class I IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Idle Pallet Storage Refer to NFPA 13 Refer to FM 2 0 8 9 and 8 24 Rubber Tire Storage Refer to NFPA 13 Refer to FM 2 0 and 8 3 Roll Paper Storage Refer to the Standard Refer to NFPA 13 Refer to FM 8 21 Flammable Igni...

Page 4: ...onnel who may be affected by this action must be notified Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced Automatic sprinklers must never be painted plated coated or other wise altered after leaving the factory Modified sprinklers must be replaced Sprinklers that have been exposed to corrosive products of combustion but have not operated should be ...

Reviews: