background image

TFP485

Page 2 of 14

This equipment generates, uses, and 

can radiate radio frequency energy, 

and if not installed and used in accor-

dance with this technical data sheet, 

may cause interference to radio com-

munications. This equipment has been 

tested and found to comply with the 

limits for a Class A computing device 

pursuant to Subpart J of Part 15 of FCC 

Rules, that are designed to provide rea-

sonable protection against such inter-

ference when operated in a commercial 

environment. However, operation of 

this equipment in a residential area 

may cause interference, in which case 

the user, at their own expense, will be 

required to take whatever measure may 

be required to correct the interference. 
To ensure proper operation, this 

product must be retested by qualified 

personnel in accordance with the Care 

and Maintenance section after any 

modification, repair, or adjustment. 

Retesting is required to assure that the 

system is operating as intended.

Model RCP-1 

Residential Control Panel

A key component of the Residential 

Dry Pipe System is The Model RCP-1 

Panel.
The Model RCP-1 Residential Control 

Panel is an integrated valve manifold, 

air pressure, and electronic control 

package for controlling the release of 

water into residential dry pipe sprinkler 

systems.
The Model RCP-1 Panel is intended 

for use in one-and two-family dwell-

ings and mobile homes per NFPA 13D 

when used with residential sprinklers 

that have been Listed for use in dry 

pipe residential sprinkler systems.
The Model RCP-1 Panel incorporates 

the Listed Model 4004R Household Fire 

Warning Unit Subassembly installed 

within the Model RCP-1 Panel cabinet.

The Model RCP-1 Panel includes the 

following features:
•  Pre-wired assembly containing pre-

programmed control panel, sys-

tem performance gauges, and an 

enclosed compressor

•  Pre-engineered riser design
•  Supervised valve system
•  High pressure supervision for indi-

cation of a false trip or failure of the 

automatic air supply cut-out switch

•  Dry contacts for remote connection 

(dial-up systems or additional moni-

toring, for example)

•  48-hour battery backup
For detailed information about the 

Model RCP-1 Panel, refer to Technical 

Data Sheet TFP480.

RAPID RESPONSE Residential 

Sprinklers

The Residential Dry Pipe System oper-

ates with RAPID RESPONSE Residen-

tial Sprinklers. These wet and dry-type 

residential sprinklers have undergone 

rigorous testing to meet UL1626 fire 

test criteria, including a 15-second 

delay for water delivery as required for 

residential sprinklers intended for use 

in dry pipe systems.

TYCO CPVC Pipe and Fittings

Another component of the Resi-

dential Dry Pipe System is TYCO 

BLAZEMASTER CPVC Pipe and Fit-

tings. TYCO CPVC products provide the 

only complete line of BLAZEMASTER 

pipe and fittings in the fire protection 

industry and are also UL Listed for use 

in dry pipe systems.

• 

WARNINGS

Never remove any piping component or 

correct or modify any piping deficien-

cies without first de-pressurizing and 

draining the system. Failure to do so 

may result in equipment damage and/

or personal injury.

SprinkFDT Fluid Delivery 

Calculation Software

Water delivery times can be conve-

niently determined prior to actual field 

installations using the industry’s only 

fluid delivery calculation software, the 

TYCO SprinkFDT program.
For more information on this fluid 

delivery calculation program, visit 

www.sprinkcad.com.

Technical 

Data

Approvals

The Model RCP-1 Residential Control 

Panel is UL Listed for use in residen-

tial dry pipe systems installed in one- 

and two- family dwellings and mobile 

homes per NPFA 13D when installed in 

accordance with this document.
The Model 4004R Household Fire 

Warning Unit Subassembly (Electronic 

Control) installed with the Model RCP-1 

cabinet is UL and C-UL Listed.
The following sprinklers are UL Listed 

for use in residential dry pipe sprinkler 

systems:

•  TY1334: 4.2K Sidewall/Recessed 

Sidewall

•  TY2234: 4.9K Pendent/Recessed 

Pendent

•  TY2234: 

4.9

K Domed Concealed 

Pendent

•  TY2235: 4.9K

 Dry-Type Recessed 

Pendent

TYCO CPVC Pipe and Fittings are UL 

Listed for use in residential dry pipe 

systems.

Sprinkler Selection and Piping

To prevent potential freezing of water 

in most applications, and in order 

to ensure complete draining of the 

system after a hydrostatic test, trip 

test, or system operation, see Figure 4 

for appropriate sprinkler selection and 

piping arrangements.

NOTICE

The referenced data sheets provide 

complete descriptions of these sprin-

klers, including installation criteria for 

wet pipe systems. As a function of their 

UL Listing for use in residential dry pipe 

systems, the following criteria provides 

Water Delivery and Hydraulic Design 

criteria as it relates to the sprinkler’s 

use in dry pipe systems:

•  TY1334: Data Sheet TFP410
•  TY2234: Data Sheet TFP400
•  TY2234: Data Sheet TFP450
•  TY2235: Data Sheet TFP460

Summary of Contents for tyco RAPID RESPONSE RCP-1

Page 1: ... Residential Sprinklers have undergone rigorous testing to meet UL1626 fire test criteria includ ing a 15 second delay for water deliv ery as required for residential sprinklers intended for use in dry pipe systems NOTICE The RAPID RESPONSE Residential Dry Pipe System described herein must be installed and maintained by qualified personnel in compliance with this docu ment and with the applicable ...

Page 2: ...These wet and dry type residential sprinklers have undergone rigorous testing to meet UL1626 fire test criteria including a 15 second delay for water delivery as required for residential sprinklers intended for use in dry pipe systems TYCO CPVC Pipe and Fittings Another component of the Resi dential Dry Pipe System is TYCO BLAZEMASTER CPVC Pipe and Fit tings TYCO CPVC products provide the only com...

Page 3: ...ments for Dry System Water Delivery per Section 8 3 4 3 of the 2010 edition of NFPA 13D applies Water deliv ery to the most remote single sprin kler for a residential hazard shall not exceed 15 seconds The use of the TYCO SprinkFDT Fluid Delivery cal culation program is recommended to assure a properly operating system can be achieved prior to constructing the actual installation Figures 1 and 2 p...

Page 4: ...sed for this example 2 Horizontal Sidewall Sprinklers are used to allow the system to com pletely drain 3 The Model RCP 1 Panel outlet flow is based on the least available water flow to hydraulically support the two most remote sprinklers at 16 GPM each 4 Water delivery to the most remote sprinkler is calculated assuming the highest possible initial air pressure based on a 10 to 14 psi automatic a...

Page 5: ...rature of 0 F was used for this example 2 Dry Type Residential Pendent Sprinklers 3 The Model RCP 1 Panel outlet flow is based on the least available water flow to hydraulically support the two most remote sprinklers at 15 GPM each 4 Water delivery to the most remote sprinkler is calculated assuming the highest possible initial air pressure based on a 10 to 14 psi automatic air supply 5 This examp...

Page 6: ...MBLY AIR PRESSURE CONTROL Always consult local jurisdictions for water supply criteria and requirements Nominal Weight 95 LBS 43 kg MOUNTING BRACKETS 2 7 8 73 mm ELECTRONIC CONTROL 1 3 4 45 mm 5 127 mm OPERATOR INTERFACE WINDOW OPERATOR INTERFACE SYSTEM AIR SUPPLY PRESSURE GAUGE SYSTEM WATER SUPPLY PRESSURE GAUGE OUTLET CONNECTION TO DRY PIPE FIRE PROTECTION SYSTEM FRONT LEFT SIDE FIGURE 3 MODEL R...

Page 7: ...mple 3 Example 3 Sidewall b Example 3 Example 3 Dry Type c Pendent Example 4 Example 4 Dry Type c Pendent a Recessed Pendent TY2234 Data Sheet TFP400 Domed Concealed Pendent TY2234 Data Sheet TFP450 Flat Plate Concealed Pendent TY3596 Data Sheet TFP442 b Recessed Horizontal Sidewall TY1334 Data Sheet TFP410 c Dry Type Recessed Pendent TY2235 Data Sheet TFP460 CPVC DRY TYPE SPRINKLER TEE P N 80259 ...

Page 8: ... for Horizontal Ceiling Maximum 2 in Rise for 12 in Run 155 F 68 C 175 F 79 C 12 x 12 3 7 x 3 7 12 3 7 13 GPM 49 2 LPM 7 0 psi 0 48 bar 13 GPM 49 2 LPM 7 0 psi 0 48 bar 14 x 14 4 3 x 4 3 14 4 3 14 GPM 53 0 LPM 8 2 psi 0 57 bar 14 GPM 53 0 LPM 8 2 psi 0 57 bar 16 x 16 4 9 x 4 9 16 4 9 15 GPM 56 8 LPM 9 4 psi 0 65 bar 15 GPM 56 8 LPM 9 4 psi 0 65 bar 18 x 18 5 5 x 5 5 18 5 5 18 GPM 68 1 LPM 13 5 psi...

Page 9: ...when connecting a Dry Type Residential Pendent Sprinkler to CPVC piping in areas subject to freezing Notes a For coverage area dimensions less than or between those indicated use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated b The requirement is based on minimum flow in GPM LPM from each sprinkler The associated residual pressures are c...

Page 10: ...x 12 3 7 x 3 7 12 3 7 12 GPM 45 4 LPM 8 2 psi 0 57 bar 12 GPM 45 4 LPM 8 2 psi 0 57 bar 13 GPM 49 2 LPM 9 6 psi 0 48 bar 13 GPM 49 2 LPM 9 6 psi 0 48 bar 14 x 14 4 3 x 4 3 14 4 3 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 GPM 60 6 LPM 14 5 psi 1 00 bar 18 GPM 68 1 LPM 18 4 psi 1 27 bar 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 16 4 9 x 4 9 16 4 9 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 GPM 60 6 LPM 14 5 psi 1...

Page 11: ... a normal system air pressure of 10 to 14 psi 0 7 to 1 0 bar via the Air Compressor In the standby condition water is prevented from entering the system piping until the Solenoid Valve in the Manifold Assembly is opened in response to the electronic control Operation sequence The normal standby condition is AC green light ON Closure of Main Control Valve closure of System Control Valve or a high s...

Page 12: ...pressure of 10 to 14 psi Step 9 Reset the Electronic Control by pressing the SYSTEM RESET key Wait approximately fifteen seconds for the Electronic Control to clear A supervisory signal will remain because the Main Control Valve is still closed Press the ACCEPT SIGNAL key to accept the supervisory signal and silence the tone alert Step 10 Open the Main Control Valve The supervisory signal should c...

Page 13: ... to 10 Verify that POSITIONs 1 to 10 light up as follows MODE 1 POSITION 6 for Dry Pipe MODE 2 POSITION 1 for Class B Initiating Circuit Style MODE 3 POSITION 1 for 0 Second Automatic Time Release Delay MODE 4 POSITION 1 for No RAC Cutout Timer MODE 5 POSITION 1 for 0 Second Manual Release Time Delay Step 2 Verify the Operator Interface Panel of the Electronic Control only indicates a green light ...

Page 14: ...ial Dry Pipe System P N specify 1 in 52 310 2 601 1 1 2 in 52 310 2 602 Separately Ordered Parts Specify Bezel for use with the Model RCP 1 Residential Control Panel P N 52 310 2 603 Panel Replacement Parts Specify 8 0 Amp Battery for use with the Model RCP 1 Residential Control Panel quantity of 2 P N 2656 Sprinklers Refer to the specific technical data sheets describing Residential Sprin klers f...

Reviews: