background image

TFP485

Page 3 of 14

Design 

Criteria

The following design criteria is provided 

with respect to residential sprinklers, 

sprinkler pipe and fittings, water deliv-

ery, and notification appliances.

Residential Sprinklers

NOTICE

The use of an automatic sprinkler 

system does not allow for omission of a 

Household Fire Alarm System installed 

per NFPA 72.

Sprinklers are to be located and 

hydraulically designed per their Listing 

for use in dry pipe systems.
See Tables A through D for required 

flows and pressures for residential dry 

pipe listings. In accordance with NFPA 

13D, sprinkler types and/or piping 

configurations supplying these sprin-

klers vary depending on factors such 

as temperature, type of piping, and 

water supply. See Figure 4 for appro-

priate sprinkler selection and piping 

arrangements.

CPVC Pipe and Fittings

Corrosion-resistant or internally gal-

vanized pipe must be utilized with the 

sprinklers described in this data sheet. 
TYCO BLAZEMASTER CPVC Pipe and 

Fittings have been specifically listed 

for use in dry systems. Users must be 

familiar with and follow listing parame-

ters, such as, maximum 15 psi (1,0 bar) 

air pressure when utilizing CPVC prod-

ucts in a dry-type system.

To facilitate draining, piping in areas 

subject to freezing shall be pitched in 

accordance with NFPA 13D for dry pipe 

systems.
The TYCO CPVC Sprinkler Head 

Adapter Tee (P/N 80259) is to be 

used with the dry-type residential 

pendent sprinklers in dry pipe system 

installations.
Refer to the TYCO technical manual 

CPVC Fire Sprinkler Products Installa-

tion Instructions & Technical Handbook 

(IH-1900). 

Water Delivery

For dry pipe systems, the require-

ments for Dry System Water Delivery 

per Section 8.3.4.3 of the 2010 edition 

of NFPA 13D applies. Water deliv-

ery to the most remote single sprin-

kler for a residential hazard shall not 

exceed 15 seconds. The use of the 

TYCO SprinkFDT Fluid Delivery cal-

culation program is recommended to 

assure a properly operating system can 

be achieved prior to constructing the 

actual installation.
Figures 1 and 2 provide a sample sprin-

kler layout and water delivery times that 

can be expected for a dry pipe sprin-

kler system.
As an alternative to using a Listed 

water delivery calculation program and 

method as referenced in NFPA 13D, an 

inspector’s test connection providing a 

flow equivalent to the smallest orifice 

sprinkler may be utilized, wherein the 

test orifice is located on the end of 

the pipe supplying the most remote 

sprinkler.

NOTICE

In no case shall the time of water deliv-

ery exceed 15 seconds for the most 

remote operating sprinkler.

Hydraulic Design (NFPA 13D)

The minimum required sprinkler flow 

rates for systems designed to NFPA 

13D (dry systems) are given in Tables 

A through F as a function of temper-

ature rating and the maximum allow-

able coverage areas. The sprinkler flow 

rate is the minimum required discharge 

from each of the total number of design 

sprinklers (the two most hydraulically 

demanding sprinklers) as specified in 

NFPA 13D.

Notification Appliances

NOTICE

NFPA 13D does not require the instal-

lation of a waterflow alarm (notification 

appliance device).

Notification appliances can be installed 

to indicate release of the Model RCP-1 

Panel.
When installed, notification appli-

ances must be installed in accordance 

with the applicable requirements of 

NFPA 72. Per the requirements of 

NFPA 72, fire warning equipment for 

dwelling units shall provide a sound 

that is audible in all occupiable dwell-

ing areas.

Summary of Contents for tyco RAPID RESPONSE RCP-1

Page 1: ... Residential Sprinklers have undergone rigorous testing to meet UL1626 fire test criteria includ ing a 15 second delay for water deliv ery as required for residential sprinklers intended for use in dry pipe systems NOTICE The RAPID RESPONSE Residential Dry Pipe System described herein must be installed and maintained by qualified personnel in compliance with this docu ment and with the applicable ...

Page 2: ...These wet and dry type residential sprinklers have undergone rigorous testing to meet UL1626 fire test criteria including a 15 second delay for water delivery as required for residential sprinklers intended for use in dry pipe systems TYCO CPVC Pipe and Fittings Another component of the Resi dential Dry Pipe System is TYCO BLAZEMASTER CPVC Pipe and Fit tings TYCO CPVC products provide the only com...

Page 3: ...ments for Dry System Water Delivery per Section 8 3 4 3 of the 2010 edition of NFPA 13D applies Water deliv ery to the most remote single sprin kler for a residential hazard shall not exceed 15 seconds The use of the TYCO SprinkFDT Fluid Delivery cal culation program is recommended to assure a properly operating system can be achieved prior to constructing the actual installation Figures 1 and 2 p...

Page 4: ...sed for this example 2 Horizontal Sidewall Sprinklers are used to allow the system to com pletely drain 3 The Model RCP 1 Panel outlet flow is based on the least available water flow to hydraulically support the two most remote sprinklers at 16 GPM each 4 Water delivery to the most remote sprinkler is calculated assuming the highest possible initial air pressure based on a 10 to 14 psi automatic a...

Page 5: ...rature of 0 F was used for this example 2 Dry Type Residential Pendent Sprinklers 3 The Model RCP 1 Panel outlet flow is based on the least available water flow to hydraulically support the two most remote sprinklers at 15 GPM each 4 Water delivery to the most remote sprinkler is calculated assuming the highest possible initial air pressure based on a 10 to 14 psi automatic air supply 5 This examp...

Page 6: ...MBLY AIR PRESSURE CONTROL Always consult local jurisdictions for water supply criteria and requirements Nominal Weight 95 LBS 43 kg MOUNTING BRACKETS 2 7 8 73 mm ELECTRONIC CONTROL 1 3 4 45 mm 5 127 mm OPERATOR INTERFACE WINDOW OPERATOR INTERFACE SYSTEM AIR SUPPLY PRESSURE GAUGE SYSTEM WATER SUPPLY PRESSURE GAUGE OUTLET CONNECTION TO DRY PIPE FIRE PROTECTION SYSTEM FRONT LEFT SIDE FIGURE 3 MODEL R...

Page 7: ...mple 3 Example 3 Sidewall b Example 3 Example 3 Dry Type c Pendent Example 4 Example 4 Dry Type c Pendent a Recessed Pendent TY2234 Data Sheet TFP400 Domed Concealed Pendent TY2234 Data Sheet TFP450 Flat Plate Concealed Pendent TY3596 Data Sheet TFP442 b Recessed Horizontal Sidewall TY1334 Data Sheet TFP410 c Dry Type Recessed Pendent TY2235 Data Sheet TFP460 CPVC DRY TYPE SPRINKLER TEE P N 80259 ...

Page 8: ... for Horizontal Ceiling Maximum 2 in Rise for 12 in Run 155 F 68 C 175 F 79 C 12 x 12 3 7 x 3 7 12 3 7 13 GPM 49 2 LPM 7 0 psi 0 48 bar 13 GPM 49 2 LPM 7 0 psi 0 48 bar 14 x 14 4 3 x 4 3 14 4 3 14 GPM 53 0 LPM 8 2 psi 0 57 bar 14 GPM 53 0 LPM 8 2 psi 0 57 bar 16 x 16 4 9 x 4 9 16 4 9 15 GPM 56 8 LPM 9 4 psi 0 65 bar 15 GPM 56 8 LPM 9 4 psi 0 65 bar 18 x 18 5 5 x 5 5 18 5 5 18 GPM 68 1 LPM 13 5 psi...

Page 9: ...when connecting a Dry Type Residential Pendent Sprinkler to CPVC piping in areas subject to freezing Notes a For coverage area dimensions less than or between those indicated use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated b The requirement is based on minimum flow in GPM LPM from each sprinkler The associated residual pressures are c...

Page 10: ...x 12 3 7 x 3 7 12 3 7 12 GPM 45 4 LPM 8 2 psi 0 57 bar 12 GPM 45 4 LPM 8 2 psi 0 57 bar 13 GPM 49 2 LPM 9 6 psi 0 48 bar 13 GPM 49 2 LPM 9 6 psi 0 48 bar 14 x 14 4 3 x 4 3 14 4 3 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 GPM 60 6 LPM 14 5 psi 1 00 bar 18 GPM 68 1 LPM 18 4 psi 1 27 bar 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 16 4 9 x 4 9 16 4 9 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 GPM 60 6 LPM 14 5 psi 1...

Page 11: ... a normal system air pressure of 10 to 14 psi 0 7 to 1 0 bar via the Air Compressor In the standby condition water is prevented from entering the system piping until the Solenoid Valve in the Manifold Assembly is opened in response to the electronic control Operation sequence The normal standby condition is AC green light ON Closure of Main Control Valve closure of System Control Valve or a high s...

Page 12: ...pressure of 10 to 14 psi Step 9 Reset the Electronic Control by pressing the SYSTEM RESET key Wait approximately fifteen seconds for the Electronic Control to clear A supervisory signal will remain because the Main Control Valve is still closed Press the ACCEPT SIGNAL key to accept the supervisory signal and silence the tone alert Step 10 Open the Main Control Valve The supervisory signal should c...

Page 13: ... to 10 Verify that POSITIONs 1 to 10 light up as follows MODE 1 POSITION 6 for Dry Pipe MODE 2 POSITION 1 for Class B Initiating Circuit Style MODE 3 POSITION 1 for 0 Second Automatic Time Release Delay MODE 4 POSITION 1 for No RAC Cutout Timer MODE 5 POSITION 1 for 0 Second Manual Release Time Delay Step 2 Verify the Operator Interface Panel of the Electronic Control only indicates a green light ...

Page 14: ...ial Dry Pipe System P N specify 1 in 52 310 2 601 1 1 2 in 52 310 2 602 Separately Ordered Parts Specify Bezel for use with the Model RCP 1 Residential Control Panel P N 52 310 2 603 Panel Replacement Parts Specify 8 0 Amp Battery for use with the Model RCP 1 Residential Control Panel quantity of 2 P N 2656 Sprinklers Refer to the specific technical data sheets describing Residential Sprin klers f...

Reviews: