TFP485

Page 10 of 14

•  SYSTEM TROUBLE

When a trouble occurs, the SYS-

TEM TROUBLE LED flashes until 

accepted. When accepted, it 

changes from flashing to steady.

•  AC POWER

When lit steady, the green AC 

POWER LED indicates the elec-

tronic control is receiving AC power 

that is within the specified range. 

If the LED is not lit and the panel is 

still functioning, electronic control is 

using battery power to operate. The 

cause for loss of AC Power should 

be determined and corrected. The 

system is in a normal standby con-

dition when only the Green AC 

POWER LED is ON.

•  TROUBLE LEDs

A flashing yellow TROUBLE LED 

for one of the IDCs, NACs, or RACs 

indicates the presence of a circuit 

break or ground within a system 

point, or somewhere in the wiring 

between the control panel and one 

of its points.

•  SUPERVISORY

A flashing yellow SUPERVISORY 

LED indicates a problem with the 

condition of the sprinkler system 

controls or normal status (for exam-

ple, closed valve position for main 

control valve, closed valve position 

for system control valve, or high air 

condition).

Operator 

Interface

The Model RCP-1 Panel uses LEDs and 

keys as its primary means of display-

ing status information and controlling 

the system. It allows the occupants to 

monitor the status of the Model RCP-1 

Panel and its circuits.
The Operator Interface is organized 

with the LEDs located along the left and 

right sides and keys along the lower 

edge (see Figure 5).

LEDs

•  ALARM LEDs

A flashing red LED adjacent to the 

Sprinkler (IDC1) indicates an alarm.

Maximum 

Coverage Area

(a)

Width x Length

(b)

 

ft x ft 

(m x m)

Maximum 

Spacing 

ft 

(m)

DRY PIPE 

Minimum Flow

(c) 

and Residual Pressure

Top-of-Deflector to Ceiling: 

4 to 6 in. (100 to 150 mm)

Top-of-Deflector to Ceiling: 

6 to 12 in. (100 to 150 mm)

155°F 

(68°C)

175°F 

(79°C)

155°F 

(68°C)

175°F 

(79°C)

12 x 12

(3,7 x 3,7)

12

(3,7)

12 GPM (45,4 LPM)

8.2 psi (0,57 bar)

12 GPM (45,4 LPM)

8.2 psi (0,57 bar)

13 GPM (49,2 LPM)

9.6 psi (0,48 bar)

13 GPM (49,2 LPM)

9.6 psi (0,48 bar)

14 x 14

(4,3 x 4,3)

14

(4,3)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

16 x 16

(4,9 x 4,9)

16

(4,9)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

21 GPM (79,5 LPM)

25.0 psi (1,72 bar)

16 x 18

(4,9 x 5,5)

16

(4,9)

19 GPM (71,9 LPM)

20.5 psi (1,41 bar)

Not 

Applicable

21 GPM (79,5 LPM)

25.0 psi (1,72 bar)

21 GPM (79,5 LPM)

25.0 psi (1,72 bar)

16 x 20

(4,9 x 6,1)

16

(4,9)

23 GPM (87,1 LPM)

30.0 psi (2,07 bar)

Not 

Applicable

Not 

Applicable

Not 

Applicable

Sidewall sprinklers, where installed under a ceiling with a slope greater than 0 in. rise for a 12 in. run to a slope up to a 2 in. rise for a 12 in. run, must be located per 
one of the following:
•  At the high point of the slope and positioned to discharge down the slope.
•  Along the slope and positioned to discharge across the slope.

Notes:

a.  For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic 

design criteria are stated.

b.  The Width x Length dimension refers to Width (backwall where sprinkler is located) times Length (horizontal throw of sprinkler).
c.  The Minimum Flow Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the 

nominal K-factor. Refer to Hydraulic Design under the Design Criteria section of TFP410.

*  For detailed information about the Series LFII Residential Horizontal Sidewall Sprinklers, refer to Technical Data Sheet TFP410.

ELEVATION

TABLE D 

RAPID RESPONSE SERIES LFII (TY1334) 

4.2K RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL 

 SPRINKLERS DRY PIPE SYSTEM NFPA 13D HYDRAULIC DESIGN CRITERIA FOR HORIZONTAL CEILINGS 

(MAXIMUM 2 INCH RISE FOR 12 INCH RUN)

Summary of Contents for tyco RAPID RESPONSE RCP-1

Page 1: ... Residential Sprinklers have undergone rigorous testing to meet UL1626 fire test criteria includ ing a 15 second delay for water deliv ery as required for residential sprinklers intended for use in dry pipe systems NOTICE The RAPID RESPONSE Residential Dry Pipe System described herein must be installed and maintained by qualified personnel in compliance with this docu ment and with the applicable ...

Page 2: ...These wet and dry type residential sprinklers have undergone rigorous testing to meet UL1626 fire test criteria including a 15 second delay for water delivery as required for residential sprinklers intended for use in dry pipe systems TYCO CPVC Pipe and Fittings Another component of the Resi dential Dry Pipe System is TYCO BLAZEMASTER CPVC Pipe and Fit tings TYCO CPVC products provide the only com...

Page 3: ...ments for Dry System Water Delivery per Section 8 3 4 3 of the 2010 edition of NFPA 13D applies Water deliv ery to the most remote single sprin kler for a residential hazard shall not exceed 15 seconds The use of the TYCO SprinkFDT Fluid Delivery cal culation program is recommended to assure a properly operating system can be achieved prior to constructing the actual installation Figures 1 and 2 p...

Page 4: ...sed for this example 2 Horizontal Sidewall Sprinklers are used to allow the system to com pletely drain 3 The Model RCP 1 Panel outlet flow is based on the least available water flow to hydraulically support the two most remote sprinklers at 16 GPM each 4 Water delivery to the most remote sprinkler is calculated assuming the highest possible initial air pressure based on a 10 to 14 psi automatic a...

Page 5: ...rature of 0 F was used for this example 2 Dry Type Residential Pendent Sprinklers 3 The Model RCP 1 Panel outlet flow is based on the least available water flow to hydraulically support the two most remote sprinklers at 15 GPM each 4 Water delivery to the most remote sprinkler is calculated assuming the highest possible initial air pressure based on a 10 to 14 psi automatic air supply 5 This examp...

Page 6: ...MBLY AIR PRESSURE CONTROL Always consult local jurisdictions for water supply criteria and requirements Nominal Weight 95 LBS 43 kg MOUNTING BRACKETS 2 7 8 73 mm ELECTRONIC CONTROL 1 3 4 45 mm 5 127 mm OPERATOR INTERFACE WINDOW OPERATOR INTERFACE SYSTEM AIR SUPPLY PRESSURE GAUGE SYSTEM WATER SUPPLY PRESSURE GAUGE OUTLET CONNECTION TO DRY PIPE FIRE PROTECTION SYSTEM FRONT LEFT SIDE FIGURE 3 MODEL R...

Page 7: ...mple 3 Example 3 Sidewall b Example 3 Example 3 Dry Type c Pendent Example 4 Example 4 Dry Type c Pendent a Recessed Pendent TY2234 Data Sheet TFP400 Domed Concealed Pendent TY2234 Data Sheet TFP450 Flat Plate Concealed Pendent TY3596 Data Sheet TFP442 b Recessed Horizontal Sidewall TY1334 Data Sheet TFP410 c Dry Type Recessed Pendent TY2235 Data Sheet TFP460 CPVC DRY TYPE SPRINKLER TEE P N 80259 ...

Page 8: ... for Horizontal Ceiling Maximum 2 in Rise for 12 in Run 155 F 68 C 175 F 79 C 12 x 12 3 7 x 3 7 12 3 7 13 GPM 49 2 LPM 7 0 psi 0 48 bar 13 GPM 49 2 LPM 7 0 psi 0 48 bar 14 x 14 4 3 x 4 3 14 4 3 14 GPM 53 0 LPM 8 2 psi 0 57 bar 14 GPM 53 0 LPM 8 2 psi 0 57 bar 16 x 16 4 9 x 4 9 16 4 9 15 GPM 56 8 LPM 9 4 psi 0 65 bar 15 GPM 56 8 LPM 9 4 psi 0 65 bar 18 x 18 5 5 x 5 5 18 5 5 18 GPM 68 1 LPM 13 5 psi...

Page 9: ...when connecting a Dry Type Residential Pendent Sprinkler to CPVC piping in areas subject to freezing Notes a For coverage area dimensions less than or between those indicated use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated b The requirement is based on minimum flow in GPM LPM from each sprinkler The associated residual pressures are c...

Page 10: ...x 12 3 7 x 3 7 12 3 7 12 GPM 45 4 LPM 8 2 psi 0 57 bar 12 GPM 45 4 LPM 8 2 psi 0 57 bar 13 GPM 49 2 LPM 9 6 psi 0 48 bar 13 GPM 49 2 LPM 9 6 psi 0 48 bar 14 x 14 4 3 x 4 3 14 4 3 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 GPM 60 6 LPM 14 5 psi 1 00 bar 18 GPM 68 1 LPM 18 4 psi 1 27 bar 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 16 4 9 x 4 9 16 4 9 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 GPM 60 6 LPM 14 5 psi 1...

Page 11: ... a normal system air pressure of 10 to 14 psi 0 7 to 1 0 bar via the Air Compressor In the standby condition water is prevented from entering the system piping until the Solenoid Valve in the Manifold Assembly is opened in response to the electronic control Operation sequence The normal standby condition is AC green light ON Closure of Main Control Valve closure of System Control Valve or a high s...

Page 12: ...pressure of 10 to 14 psi Step 9 Reset the Electronic Control by pressing the SYSTEM RESET key Wait approximately fifteen seconds for the Electronic Control to clear A supervisory signal will remain because the Main Control Valve is still closed Press the ACCEPT SIGNAL key to accept the supervisory signal and silence the tone alert Step 10 Open the Main Control Valve The supervisory signal should c...

Page 13: ... to 10 Verify that POSITIONs 1 to 10 light up as follows MODE 1 POSITION 6 for Dry Pipe MODE 2 POSITION 1 for Class B Initiating Circuit Style MODE 3 POSITION 1 for 0 Second Automatic Time Release Delay MODE 4 POSITION 1 for No RAC Cutout Timer MODE 5 POSITION 1 for 0 Second Manual Release Time Delay Step 2 Verify the Operator Interface Panel of the Electronic Control only indicates a green light ...

Page 14: ...ial Dry Pipe System P N specify 1 in 52 310 2 601 1 1 2 in 52 310 2 602 Separately Ordered Parts Specify Bezel for use with the Model RCP 1 Residential Control Panel P N 52 310 2 603 Panel Replacement Parts Specify 8 0 Amp Battery for use with the Model RCP 1 Residential Control Panel quantity of 2 P N 2656 Sprinklers Refer to the specific technical data sheets describing Residential Sprin klers f...