background image

RAPID RESPONSE

Residential Dry Pipe System

Page 1 of 14 

FEBRUARY 2019 

TFP485

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO RAPID RESPONSE Resi-

dential Dry Pipe System provides a 

normally dry system for areas subject 

to freezing or areas that may be inad-

vertently subject to freezing.
The key components of the RAPID 

RESPONSE Residential Dry Pipe 

System are:
•  Model RCP-1 Residential Control 

Panel

•  RAPID RESPONSE Residential 

Sprinklers specifically Listed for use 

in residential dry pipe systems (ver-

sus being limited to wet pipe sys-

tems only)

•  TYCO CPVC Pipe and Fittings made 

with BLAZEMASTER Compound

•  SprinkFDT Fluid Delivery Calculation 

Software

Typically, residential sprinklers based 

on their Listing are limited to wet pipe 

sprinkler systems to assure speed of 

water delivery for a prescribed design 

area (the number of design sprinklers). 

The Model RCP-1 Residential Control 

Panel, in combination with specific 

Rapid Response Residential Sprin-

klers listed for use in dry pipe systems, 

provides options for areas sensitive to 

freezing.

To achieve UL Listing, the RAPID 

RESPONSE Residential Sprinklers 

have undergone rigorous testing to 

meet UL1626 fire test criteria, includ-

ing a 15-second delay for water deliv-

ery as required for residential sprinklers 

intended for use in dry pipe systems.

NOTICE

The RAPID RESPONSE Residential Dry 

Pipe System described herein must be 

installed and maintained by qualified 

personnel in compliance with this docu-

ment, and with the applicable standards 

of the NATIONAL FIRE PROTECTION 

ASSOCIATION (NFPA), in addition to 

the requirements of any other authori-

ties having jurisdiction. Failure to do 

so may impair the performance of this 

device.
The owner is responsible for maintain-

ing their fire protection system and 

devices in proper operating condition 

and in compliance with all applicable 

standards and requirements. Contact 

the installing contractor or product 

manufacturer with any questions.
Do not disconnect batteries or turn off 

AC power to quiet unwanted alarms.
The Model RCP-1 Panel will not operate 

(that is, release water or energize 

alarms) if AC power is not connected, 

has failed, or has been interrupted 

for any reason and the battery is dis-

connected, drained, or improperly 

connected.
The use of an automatic sprinkler 

system does not allow for omission of a 

Household Fire Alarm System installed 

per NFPA 72. The Model RCP-1 Panel 

is not intended to be used as part of a 

Household Fire Alarm System.
Disconnect electrical field power when 

making any internal adjustments or 

repairs. Failure to do so may result in 

personal injury. Servicing should be 

performed by qualified personnel.
Static electricity can damage com-

ponents. Therefore, qualified person-

nel must be grounded before opening 

components, installing components, 

and prior to installation. Keep compo-

nents wrapped in anti-static material at 

all times.

Summary of Contents for tyco RAPID RESPONSE RCP-1

Page 1: ... Residential Sprinklers have undergone rigorous testing to meet UL1626 fire test criteria includ ing a 15 second delay for water deliv ery as required for residential sprinklers intended for use in dry pipe systems NOTICE The RAPID RESPONSE Residential Dry Pipe System described herein must be installed and maintained by qualified personnel in compliance with this docu ment and with the applicable ...

Page 2: ...These wet and dry type residential sprinklers have undergone rigorous testing to meet UL1626 fire test criteria including a 15 second delay for water delivery as required for residential sprinklers intended for use in dry pipe systems TYCO CPVC Pipe and Fittings Another component of the Resi dential Dry Pipe System is TYCO BLAZEMASTER CPVC Pipe and Fit tings TYCO CPVC products provide the only com...

Page 3: ...ments for Dry System Water Delivery per Section 8 3 4 3 of the 2010 edition of NFPA 13D applies Water deliv ery to the most remote single sprin kler for a residential hazard shall not exceed 15 seconds The use of the TYCO SprinkFDT Fluid Delivery cal culation program is recommended to assure a properly operating system can be achieved prior to constructing the actual installation Figures 1 and 2 p...

Page 4: ...sed for this example 2 Horizontal Sidewall Sprinklers are used to allow the system to com pletely drain 3 The Model RCP 1 Panel outlet flow is based on the least available water flow to hydraulically support the two most remote sprinklers at 16 GPM each 4 Water delivery to the most remote sprinkler is calculated assuming the highest possible initial air pressure based on a 10 to 14 psi automatic a...

Page 5: ...rature of 0 F was used for this example 2 Dry Type Residential Pendent Sprinklers 3 The Model RCP 1 Panel outlet flow is based on the least available water flow to hydraulically support the two most remote sprinklers at 15 GPM each 4 Water delivery to the most remote sprinkler is calculated assuming the highest possible initial air pressure based on a 10 to 14 psi automatic air supply 5 This examp...

Page 6: ...MBLY AIR PRESSURE CONTROL Always consult local jurisdictions for water supply criteria and requirements Nominal Weight 95 LBS 43 kg MOUNTING BRACKETS 2 7 8 73 mm ELECTRONIC CONTROL 1 3 4 45 mm 5 127 mm OPERATOR INTERFACE WINDOW OPERATOR INTERFACE SYSTEM AIR SUPPLY PRESSURE GAUGE SYSTEM WATER SUPPLY PRESSURE GAUGE OUTLET CONNECTION TO DRY PIPE FIRE PROTECTION SYSTEM FRONT LEFT SIDE FIGURE 3 MODEL R...

Page 7: ...mple 3 Example 3 Sidewall b Example 3 Example 3 Dry Type c Pendent Example 4 Example 4 Dry Type c Pendent a Recessed Pendent TY2234 Data Sheet TFP400 Domed Concealed Pendent TY2234 Data Sheet TFP450 Flat Plate Concealed Pendent TY3596 Data Sheet TFP442 b Recessed Horizontal Sidewall TY1334 Data Sheet TFP410 c Dry Type Recessed Pendent TY2235 Data Sheet TFP460 CPVC DRY TYPE SPRINKLER TEE P N 80259 ...

Page 8: ... for Horizontal Ceiling Maximum 2 in Rise for 12 in Run 155 F 68 C 175 F 79 C 12 x 12 3 7 x 3 7 12 3 7 13 GPM 49 2 LPM 7 0 psi 0 48 bar 13 GPM 49 2 LPM 7 0 psi 0 48 bar 14 x 14 4 3 x 4 3 14 4 3 14 GPM 53 0 LPM 8 2 psi 0 57 bar 14 GPM 53 0 LPM 8 2 psi 0 57 bar 16 x 16 4 9 x 4 9 16 4 9 15 GPM 56 8 LPM 9 4 psi 0 65 bar 15 GPM 56 8 LPM 9 4 psi 0 65 bar 18 x 18 5 5 x 5 5 18 5 5 18 GPM 68 1 LPM 13 5 psi...

Page 9: ...when connecting a Dry Type Residential Pendent Sprinkler to CPVC piping in areas subject to freezing Notes a For coverage area dimensions less than or between those indicated use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated b The requirement is based on minimum flow in GPM LPM from each sprinkler The associated residual pressures are c...

Page 10: ...x 12 3 7 x 3 7 12 3 7 12 GPM 45 4 LPM 8 2 psi 0 57 bar 12 GPM 45 4 LPM 8 2 psi 0 57 bar 13 GPM 49 2 LPM 9 6 psi 0 48 bar 13 GPM 49 2 LPM 9 6 psi 0 48 bar 14 x 14 4 3 x 4 3 14 4 3 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 GPM 60 6 LPM 14 5 psi 1 00 bar 18 GPM 68 1 LPM 18 4 psi 1 27 bar 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 16 4 9 x 4 9 16 4 9 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 GPM 60 6 LPM 14 5 psi 1...

Page 11: ... a normal system air pressure of 10 to 14 psi 0 7 to 1 0 bar via the Air Compressor In the standby condition water is prevented from entering the system piping until the Solenoid Valve in the Manifold Assembly is opened in response to the electronic control Operation sequence The normal standby condition is AC green light ON Closure of Main Control Valve closure of System Control Valve or a high s...

Page 12: ...pressure of 10 to 14 psi Step 9 Reset the Electronic Control by pressing the SYSTEM RESET key Wait approximately fifteen seconds for the Electronic Control to clear A supervisory signal will remain because the Main Control Valve is still closed Press the ACCEPT SIGNAL key to accept the supervisory signal and silence the tone alert Step 10 Open the Main Control Valve The supervisory signal should c...

Page 13: ... to 10 Verify that POSITIONs 1 to 10 light up as follows MODE 1 POSITION 6 for Dry Pipe MODE 2 POSITION 1 for Class B Initiating Circuit Style MODE 3 POSITION 1 for 0 Second Automatic Time Release Delay MODE 4 POSITION 1 for No RAC Cutout Timer MODE 5 POSITION 1 for 0 Second Manual Release Time Delay Step 2 Verify the Operator Interface Panel of the Electronic Control only indicates a green light ...

Page 14: ...ial Dry Pipe System P N specify 1 in 52 310 2 601 1 1 2 in 52 310 2 602 Separately Ordered Parts Specify Bezel for use with the Model RCP 1 Residential Control Panel P N 52 310 2 603 Panel Replacement Parts Specify 8 0 Amp Battery for use with the Model RCP 1 Residential Control Panel quantity of 2 P N 2656 Sprinklers Refer to the specific technical data sheets describing Residential Sprin klers f...

Reviews: