TM-21x1 Series Room Temperature Module Installation Instructions 

3

TM-2191 Modules

  

Installing the TM-21x1

To install the TM-21x1 Series Room Temperature 
Module:

1.

Use the Allen-head tool to loosen the security 
screw located at the top center of the housing.

2.

Insert a screwdriver blade or coin into the slot on 
the top of the housing.

3.

Press down gently, and pry the housing away from 
the base. As the two parts separate, remove the 
blade or coin and continue to pull the housing away 
from the base until the housing is free.

4.

Pull the wires through the base. Locate the green 

terminal blocks in the upper right of the base and 

position the module on the wallbox with the 

terminal numbers right-side up.

5.

Mount the base to the wallbox using the two #6-32 
mounting screws (included).

6.

Wire the controller to the module. See the 

Wiring

 

section for correct wiring.

7.

Attach the housing to the base and tighten the 
security screw with the allen-head tool.

Mounting

Location Considerations

Mount the TM-21x1 Series Room Temperature Module 
on a wall in the room to be controlled where the 
occupant can easily read and adjust the setpoint dial or 
fan speed override adjustment dial. Consider these 
additional guidelines in determining the best mounting 
location:

Avoid areas subject to excessive vibration, 
electrical noise, direct sunlight, or the effects of 
radiant heat.

Keep electrical wiring as short as possible to 
minimize temperature error.

Install modules in areas where the temperature is 
representative of the general room conditions.

Wiring

To wire a controller to the TM-21x1 Series Room 
Temperature Module, see the appropriate wiring 
diagram (Figure 6 to Figure 10).

Note:

Use 22 AWG (0.65 mm diameter) wire 

minimum. Do not exceed 164 ft (50 m) between the 
controller and the temperature module. 

Figure 5: TM-2191 Dimensions, in. (mm)

F

IG

:2

1

9

1

_

d

im

3.15 (80)

1.38 (35)

4.72

(120)

Setpoint

Adjustment

Dial

Table 1:  Nominal Values for 10k ohm Sensors

Temperature

Resistance

F

C

ohm

20

-7

48,525

30

-1

34,919

40

4

27,550

50

10

19,898

60

16

12,246

70

21

11,993

80

27

9,222

90

32

7,510

100

38

5,874

110

43

4,871

120

49

3,956

130

54

3,277

Summary of Contents for TM-2161

Page 1: ...iode LED that indicates the current operating mode Installation Parts Included Two 6 32 x 7 8 in 22 mm wallbox mounting screws are included with the TM 21x1 Module Special Tools Needed For tightening and loosening the TM 11x1 Series Room Temperature Module security screw order the optional Allen head tool T 4000 119 from the nearest Johnson Controls representative IMPORTANT The TM 21x1 Series Room...

Page 2: ...re 2 TM 2151 Dimensions in mm FIG 2151_dim Mode LED Occupancy Button 3 15 80 1 26 32 4 72 120 Figure 3 TM 2161 0002 and TM 2161 0007 Dimensions in mm FIG 2161_dim 1 38 35 4 72 120 3 15 80 Mode LED Occupancy Button Fan Speed Dial Setpoint Adjustment Dial FIG 2161_0005_dim 1 38 35 4 72 120 3 15 80 Mode LED Occupancy Button Setpoint Adjustment Dial Figure 4 TM 2161 0000 and TM 2161 0005 Dimensions in...

Page 3: ...ing Location Considerations Mount the TM 21x1 Series Room Temperature Module on a wall in the room to be controlled where the occupant can easily read and adjust the setpoint dial or fan speed override adjustment dial Consider these additional guidelines in determining the best mounting location Avoid areas subject to excessive vibration electrical noise direct sunlight or the effects of radiant h...

Page 4: ...turing an NTC Sensor with Temperature Setpoint Adjustment and Occupancy Override FIG 2161_0005_WIR 15 14 21 20 NTC Sensor Common Mode LED Occupancy Button 23 22 Room Temperature Module DC 5 V Temperature Setpoint Figure 9 Wiring to a Room Temperature Module Featuring an NTC Sensor with Temperature Setpoint Adjustment Occupancy Override and Three Speed Fan Override FIG 2161_0207_WIR 15 14 21 20 NTC...

Page 5: ...Running low and high voltage wires in the same conduit or wiring troughs may damage the equipment or cause system malfunction MISE EN GARDE Risque de dégâts matériels Ne pas faire courir un câble basse tension dans les mêmes gaines ou goulottes électriques que des câbles haute tension L installation de fils basse tension et haute tension dans les mêmes gaines ou goulottes électriques risque d endo...

Page 6: ...perature Output with Setpoint Adjustment Power Requirements 5 VDC Power Consumption N A Refer to individual component specification Inputs None Adjustments Temperature Setpoint Fan Speed Optional by Model Mode Indicator Green LED 5 V 4 mA Occupancy Button Momentary Contact Switch 5 V at 1 mA Output Temperature Sensing Element Resistance Temperature Device RTD Thermistor Negative Temperature Coeffi...

Page 7: ...d III TM 21x1 0005 10k ohm potentiometer marked for 5F TM 21x1 0007 10k ohm potentiometer marked for 5F Fan Speed Adjustment Auto Off I II and III Accuracy 0 9 F 0 5 C Field Connection 18 to 22 AWG 1 00 to 0 65 mm diameter recommended Mounting Wallbox Mount Housing Material ABS PC Self Extinguishing HB UL94 Protection IP30 EN 60529 Ambient Operating Conditions 32 to 122 F 0 to 50 C 10 to 90 RH non...

Reviews: