TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
22
4.
Press
Set Schedule.
5.
Select the days to which the schedule should apply. Note that if events are already set for the selected days,
they appear in the corresponding event box. If any events conflict between selected days, an asterisk appears
in the event box.
6.
Select the event to be set.
7.
Set the Occupancy to Not Set, Occupied, Unoccupied, or Standby and press
Save
.
Figure 12: Selecting the Days (Left) and Selecting the Event (Right)
Figure 13: Setting the Room Occupancy (Left) and Setting the Occupancy Mode (Right)
IMPORTANT:
Internally, the TEC 3000 uses a BACnet schedule where daily schedules are independent of the
previous and next days. The default occupancy of the TEC3000 from the factory is set to Occupied. As a result,
a daily event at 12:00 AM must be scheduled if you do not want the controller to transition to Occupied Mode at
midnight.