TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
28
Menus and Submenus
In the following table, the * indicates that the menus depend on your configuration.
Table 10: Menus and Submenus (Part 1 of 9)
Level 1
Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values
1
Setpoints
Occ Cooling Setpoint
72°F (22°C)
55 to 85°F (13 to 30°C)
Occ Heating Setpoint
68°F (20°C)
55 to 85°F (13 to 30°C)
Unocc Cooling Setpoint
80ºF (27°C)
55 to 85°F (13 to 30°C)
Unocc Heating Setpoint
60°F (15°C)
55 to 85°F (13 to 30°C)
Stby Cooling Setpoint
74°F (23°C)
55 to 85°F (13 to 30°C)
Stby Heating Setpoint
66°F (19°C)
55 to 85°F (13 to 30°C)
Occ Setpoint Select
Setpoint Offset
Min and Max Setpoint or Setpoint Offset
Heat Cool Setpoint Mode
Individual
Setpoints
Common Setpoint or Individual Setpoint
Max Heating Setpoint*
68°F (20°C)
The range (in degrees) from the Min
Heating Setpoint temperature to the Min
Cooling Setpoint temperature minus 1°F
(0.55°C). (The cooling temperature
always needs to be 1°F [0.55°C] above
the heating temperature.)
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select ==
Min and Max Setpoint.
Min Heating Setpoint*
60°F (15°C)
45°F (7.22°C) to Max Heating Setpoint
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select ==
Min and Max Setpoint.
Max Cooling Setpoint*
80ºF (27°C)
Min Cooling Setpoint to 100°F (37.77°C)
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select ==
Min and Max Setpoint.
Min Cooling Setpoint*
72°F (22°C)
The range (in degrees) from the Max
Heating Setpoint temperature plus
1°F (0.55°C) to the Max Cooling Setpoint
temperature.
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select ==
Min and Max Setpoint.
Max Setpoint*
80ºF (27°C)
Min Setpoint to 100°F (37.77°C)
*These values only appear when Heat
Cool Setpoint Mode == Common
Setpoint and Occ Setpoint Select == Min
and Max Setpoint.
Min Setpoint*
60°F (15°C)
45°F (7.22°C) to Max Setpoint
*These values only appear when Heat
Cool Setpoint Mode == Common
Setpoint and Occ Setpoint Select == Min
and Max Setpoint.