Installation Instructions
Issue Date
November 23, 2005
© 2005 Johnson Controls, Inc.
1
TEC220x-2 Series Non-Programmable L
ON
W
ORKS
®
Network Configurable
Staged
Thermostats
Application Requirements
The TEC220x-2 Series Non-Programmable
L
ON
W
ORKS
® Network Configurable Staged
Thermostats are specifically designed for single-stage
and multi-stage control of heating/cooling equipment,
such as rooftop and heat pump units.
Code No. LIT-1201911
www.johnsoncontrols.com
Software Release 1.0
Accurate temperature control is achieved with a time
proportional control algorithm, which virtually
eliminates the temperature offset associated with
traditional, differential-based thermostats. For more
advanced applications, an economizer control logic
has been integrated onto the thermostat for use with
proportional damper economizer actuators.
All programmable models contain a Single-Pole
Single-Throw (SPST) auxiliary switch, which can be
used to control lighting or disable the economizer
function.
Mechanical Installation
Location
Install away from any heat source.
Do not install the thermostat:
•
on an outside wall
•
near an air discharge grill
•
in a location affected by direct sun radiation
•
in an area that restrains vertical air circulation to
the thermostat
c
o
v
e
rr
e
m
o
v
a
l
Figure 1: Bottom of Thermostat
Installation
To install the thermostat:
Note:
Wall surface must be flat and clean.
1.
Remove security screw on the bottom of
thermostat cover.
2.
Open up by pulling on the bottom side of
thermostat (Figure 1).
3.
Swing the thermostat circuit board to the left by
pressing the pull tabs (Figure 2).
4.
Pull cables 6” out of the wall.
5.
Insert cable in the central hole of the base.
6.
Align the base and mark the location of the two
mounting holes on the wall. Install proper side of
base up.
m
o
u
n
ti
n
g
b
a
s
e
Figure 2: Pull Tabs
7. Install anchors in the wall.
8. Insert screws in mounting holes on each side of
the base (Figure 2).
9. Gently swing the circuit board back on the base
and push until the tabs lock.
10. Pull out the screw terminal blocks using the pull
tabs on each connector (Figure 3).