background image

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy 
Sensing Capability Installation Instructions

8

Status Display Menu

The Status Display Menu is displayed during normal 
thermostat controller operation. This menu 
continuously scrolls through the following parameters:

Room Temperature (All Models) and Humidity 
(T603DFH-4 and T605DFH-4 Models)

Note:

For models with dehumidification capability, the 

default setting is no humidity reading on the display 
(

%RH disp

 parameter is set to 

off

). The 

%RH disp

 

parameter must be set to 

on

 to display the current 

humidity reading.

System Mode

Schedule Status
(Occupied/Unoccupied/Override/Stand-By 
[PIR Models])

Applicable Alarms – The backlight lights up as an 
alarm condition is displayed.

Note:

An option is available within the Installer 

Configuration Menu to lock out the scrolling display and 
show only the 

Room Temperature

 parameter.

Dehumidification Operation – T603DFH-4 and 
T605DFH-4 Thermostat Controller Models

Dehumidification activates when the room humidity is 
above the adjustable humidity setpoint as sensed by 
the integral humidity sensor.

Note:

Dehumidification operation functions only in the 

Cooling mode; dehumidification operation does not 
function in either the Off or the Heating mode.

The minimum deadband between the Heating and 
Cooling setpoints is adjustable from 2.0F°/1.0C° to 
5.0F°/2.5C°, as defined by the 

Deadband

 parameter in 

Table 4. If the room temperature resides in the 
deadband between the Heating and Cooling setpoints:

the thermostat controller forces the fan to low 
speed

the chilled water valve opens to the specified 
maximum value set by 

CoolMax

the thermostat controller stages Heating to 
maintain the room temperature at the Cooling 
setpoint, as sensed by the thermostat controller

If the room temperature falls below the result of the 
formula 

1 + Cooling Setpoint – Deadband

, then the 

thermostat controller disables dehumidification 
operation.

If the thermostat controller is in Cooling demand:

the chilled water valve opens to 100%

the thermostat controller stages Heating to 
maintain the room temperature at the Cooling 
setpoint, as sensed by the thermostat controller

If the thermostat controller is in Cooling demand and 
the room temperature rises 2F°/1C° above the Cooling 
setpoint, the thermostat controller automatically 
disables dehumidification operation. Likewise, if the 
thermostat controller is in Cooling demand and the 
room temperature falls below the current Heating 
setpoint, the thermostat controller disables 
dehumidification operation.

Occupancy Sensor Operation – 
T60xDFH-4+PIR Thermostat Controllers

A T60xDFH-4+PIR Series Thermostat Controller (or a 
T60xDFH-4 Series Thermostat Controller equipped 
with a PIR accessory cover) provides advanced 
occupancy logic.

Note:

The PIR strategy is an occupied strategy. If the 

thermostat controller is programmed to be Unoccupied, 
the PIR function does not have an effect on the 
occupancy strategy.

The thermostat controller automatically switches 
occupancy levels from Occupied to Stand-By and 
Unoccupied as required, when local movement is 
sensed.

Occupancy sensing is enabled only if a PIR cover is 
installed on the thermostat controller (PIR models) or if 
a remote input is configured as a remote PIR sensor 
(

MotionNO

 or 

MotionNC

).

PIR Warm-Up Period

When a PIR cover is used and a thermostat controller 
is powered up, there is a 1-minute warm-up period 
before any local movement can be detected and 
acknowledged by the PIR sensing device. The local 
status LEDs for the PIR function are not active, and the 
sensor is in Stand-By mode for the 1-minute period. 
The PIR functionality and local movement status LEDs 
are activated after the 1-minute warm-up period has 
elapsed after the initial powering of the thermostat 
controller. If movement is present, the mode changes 
to Occupied.

PIR Diagnostic LEDs

The diagnostic LEDs inside the PIR lens brighten when 
movement is detected within the first 30 minutes after 
powerup. The LEDs do not light up or brighten after the 
initial 30-minute period.

Summary of Contents for T60xDFH 4 PIR Series

Page 1: ...ge grills or stairwells and from behind doors away from steam or water pipes warm air stacks unconditioned areas not heated or cooled or sources of electrical interference For integrated Passive Infra...

Page 2: ...the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the hole in the thermostat controller mounting base 5 Align the thermostat contr...

Page 3: ...mperature readings 3 Reinsert the screw terminal blocks onto the PCB Note If multiple wires are inserted into the terminals be sure to properly twist the wires together prior to inserting them into th...

Page 4: ...Fan H Fan H Fan H Fan On High 2 Fan M Fan M Fan M Fan On Medium 3 Fan L Fan L Fan L Fan On Low 4 24 V Hot 24 V Hot 24 V Hot 24 VAC from Transformer 5 24 V Com 24 V Com 24 V Com 24 VAC Common from Tran...

Page 5: ...Alarm Voltage Free Contact Remote NSB Motion Window OR Same 24 VAC Power Source for Auxiliary Output 24 VAC Maximum Separate 24 VAC Power Source for Auxiliary Output 24 VAC Maximum BO5 Aux BO5 Aux 24...

Page 6: ...Pipe Applications Four Pipe Applications FIG T6023dfh3ooc 24 V Com 24 V Hot or 24 V Com 24 V Hot Cooling Valve or Heating Valve or Figure 8 Wiring T602DFH 4 and T603DFH 4 Thermostat Controllers for F...

Page 7: ...perature scale to either Celsius or Fahrenheit and allow access to the Installer Configuration Menu See the Configuring the T60xDFH 4 and T60xDFH 4 PIR Series Thermostat Controller section Use the UP...

Page 8: ...ehumidification operation If the thermostat controller is in Cooling demand the chilled water valve opens to 100 the thermostat controller stages Heating to maintain the room temperature at the Coolin...

Page 9: ...PIR sensing device used If movements are detected by the PIR sensor and the door is closed the room is considered occupied The thermostat controller switches back to Stand By mode only if the door sw...

Page 10: ...nu begins press and release the center key to scroll through the parameters listed in Table 4 3 When the desired parameter is displayed use the UP DOWN arrow keys to choose the desired selection optio...

Page 11: ...eration in Four Pipe Applications Selection Option Control Curve Terminal Numbers Used See Table 1 and Figure 5 On Off Control Floating Control Proportional 0 to 10 VDC Control 0 Cooling Only See Figu...

Page 12: ...16 Cooling with Reheat Two or Four Pipe Applications Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Cooling Setpoint Device Opened FIG clng_wth_rht Deadband Reheat On Off Fl...

Page 13: ...ng Figure 20 This operation applies to the Occupied mode when the fan is set to Auto Figure 19 Heating Cooling with Reheat Four Pipe Applications Temperature Increase Increments of 1F 0 5C Heating Set...

Page 14: ...at controller remains in the Occupied mode if the contact is open until the TOccTime expires Advanced PIR occupancy functions using a Normally Open N O or Normally Closed N C remote PIR motion sensor...

Page 15: ...an input COC NH Changeover Contact Normally Heat A dry contact input is used to signal seasonal hot cold water changeover The contact closes when cold water is present Valid only for two pipe systems...

Page 16: ...sequence of operation Default 1 Sequence of Operation Default Based on AutoMode Parameter Setting On Off 0 Cooling Only Off Cool Cool Cool 1 Heating Only Off Heat Heat Heat 2 Cooling and Reheat Off Au...

Page 17: ...ive Range 0 5 to 24 0 hrs adjustable in 0 5 hour increments Unocc TM Sets the Unoccupied timer value PIR models Default 0 0 hours Time delay between the moment the thermostat controller toggled to Sta...

Page 18: ...d between the return and supply air feeds that is directly influenced by the supply air stream 3 3 0F 1 7C 4 4 0F 2 2C 5 5 0F 2 8C 6 6 0F 3 3C 7 7 0F 3 9C 8 8 0F 4 4C 9 9 0F 5 0C 10 10 0F 5 6C Set typ...

Page 19: ...s the desired humidity sensor calibration offset The offset can be added to or subtracted from the actual displayed room humidity T603 and T605 models This parameter can be used only if the dehumidifi...

Page 20: ...perature error from the setpoint FL time Sets the maximum actuator stroke timing floating CntrlTyp T602 and T603 models Default 1 5 min Range 0 5 to 9 0 min adjustable in 0 5 minute increments Cph Set...

Page 21: ...at Controllers with Dehumidification and Occupancy Sensing Capability Part 1 of 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals 4 and 5 at 24 VAC Nominal Class 2 or Safety Extra Low Voltage...

Page 22: ...2 2 No 24 Temperature Indicating and Regulating Equipment Industry Canada ICES 003 Europe CE Mark Johnson Controls Inc declares that this product is in compliance with the essential requirements and o...

Reviews: