T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
20
Accessories
All the accessories in Table 5 include mounting
hardware; contact the nearest Johnson Controls®
representative to order any of these parts.
Note:
Review the technical specifications of the
accessories prior to their use in an application.
Repair Information
If the T60xDFH-4 or T60xDFH-4+PIR Series
Thermostat Controller fails to operate within its
specifications, replace the unit. For a replacement
thermostat controller, contact the nearest
Johnson Controls representative.
Auto Fan
Affects the auto mode of operation
for the following
Fan Menu
parameter selection options only:
•
(2):
Low-Med-High-Auto
•
(3):
Low-High-Auto
Default:
AS
(AS AD):
The fan is on Auto during occupied periods. The Med and
High speeds operate automatically on a temperature error from the
setpoint. The Low speed operates Auto on demand. When there is
no demand, the Low speed shuts down. The Low speed is only re-
activated when there is a heating or cooling demand.
(AS):
The fan is always on during occupied periods. The fan is on
Auto during unoccupied periods. The Low, Med, and High speeds
operate automatically on a temperature error from the setpoint.
FL time
Sets the maximum actuator stroke
timing (floating
CntrlTyp
T602 and
T603 models).
Default:
1.5 min
Range:
0.5
to
9.0 min
adjustable in 0.5-minute increments
Cph
Sets the maximum number of cycles
per hour (T601 and on/off
CntrlTyp
T602 and T603 models).
Default:
4.0
Range:
3.0
to
8.0
cycles per hour
RA/DA
Choice of reverse or direct acting
analog output signal (T604 and
T605 models)
Default:
DA
(RA):
Reverse acting, 0 to 100% = 10 to 0 VDC
(DA):
Direct acting, 0 to 100% = 0 to 10 VDC
Reheat
Sets the duty cycle time for reheat
output (if Option 2, 3, or 5 is chosen
in the
SeqOpera
parameter).
Default:
0
(1):
10 seconds (six cycles per minute), for various equipment with
solid-state relays that withstand short duty cycles such as electric
heat.
(0):
15 minutes (four cycles per hour), for various equipment with
mechanical relays or contactors controlling mechanical reheat
systems.
UI3 dis
Displays the supply or changeover
temperature when UI3 is configured
as an analog input (supply sensor or
changeover sensor).
Default:
-40°F/-40°C
Used as a diagnostic/service help, to troubleshoot and diagnose
sensor operation.
1.
When adjusting the numeric value, press the
UP/DOWN
arrow key to change the value by single increments; press and
hold the
UP/DOWN
arrow key to change the numeric value in increments of ten.
Table 4: Installer Configuration Menu (Part 7 of 7)
Parameter
Appearing
on Display
Description and Default
Selection Options