T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy 
Sensing Capability Installation Instructions 

11

Table 2:  Selection Options for Sequence of Operation in Two-Pipe Applications

Selection
Option

Control 
Curve

Terminal Numbers Used (See Table 1 and Figure 5.)

On/Off Control

Floating Control

Proportional 
0 to 10 VDC  Control

(0): Cooling Only

See Figure 14.

10:

 Normally Open 

(N.O.) Cooling 

11:

Normally Closed 

(N.C.) Cooling

10:

 Open Cooling 

11:

Closed Cooling

10:

 Proportional Cooling

(1): Heating Only

See Figure 15.

10:

 N.O. Heating 

11:

N.C. Heating

10:

 Open Heating 

11:

Closed Heating

10:

 Proportional Heating

(2): Cooling and Reheat

See Figure 16.

6 and 7:

 Reheat 

10:

N.O. Cooling 

11:

N.C. Cooling

6 and 7:

 Reheat 

10:

Open Cooling 

11:

Closed Cooling

6 and 7:

 Reheat 

10:

Proportional Cooling

(3): Heating and Reheat

See Figure 17.

6 and 7:

 Reheat 

10:

N.O. Heating 

11:

N.C. Heating

6 and 7:

 Reheat 

10:

Open Heating 

11:

Closed Heating

6 and 7:

 Reheat 

10:

Proportional Heating

Table 3:  Selection Options for Sequence of Operation in Four-Pipe Applications

Selection
Option

Control 
Curve

Terminal Numbers Used (See Table 1 and Figure 5.)

On/Off Control

Floating Control

Proportional 
0 to 10 VDC  Control

(0): Cooling Only

See Figure 14.

10:

 N.O. Cooling 

11:

N.C. Cooling

10:

 Open Cooling 

11:

Closed Cooling

10:

 Proportional Cooling

(1): Heating Only

See Figure 15.

8:

 N.O. Heating 

9:

N.C. Heating

8:

 Open Heating 

9:

Closed Heating

9:

 Proportional Heating

(2): Cooling and Reheat

See Figure 16.

6 and 7:

 Reheat 

10:

N.O. Cooling 

11:

N.C. Cooling

6 and 7:

 Reheat 

10:

Open Cooling 

11:

Closed Cooling

6 and 7:

 Reheat 

10:

Proportional Cooling

(3): Heating and Reheat

See Figure 17.

6 and 7:

 Reheat 

8:

N.O. Heating 

9:

N.C. Heating

6 and 7:

 Reheat 

8:

Open Heating 

9:

Closed Heating

6 and 7:

 Reheat 

9:

Proportional Heating

(4): Cool/Heat Four-Pipe

See Figure 18.

8:

 N.O. Heating

 

9:

N.C. Heating 

10:

N.O. Cooling 

11:

N.C. Cooling

8:

 Open Heating

 

9:

Closed Heating 

10:

Open Cooling 

11:

Closed Cooling

9:

 Proportional Heating

 

10:

Proportional Cooling

(5): Cool/Heat Four-Pipe 
and Reheat

See Figure 19.

6 and 7:

 Reheat 

8:

N.O. Heating

 

9:

N.C. Heating 

10:

N.O. Cooling 

11:

N.C. Cooling

6 and 7:

 Reheat 

8:

Open Heating

 

9:

Closed Heating 

10:

Open Cooling 

11:

Closed Cooling

6 and 7:

 Reheat

 

9:

Proportional Heating

 

10:

Proportional Cooling

Summary of Contents for T60xDFH 4 PIR Series

Page 1: ...ge grills or stairwells and from behind doors away from steam or water pipes warm air stacks unconditioned areas not heated or cooled or sources of electrical interference For integrated Passive Infra...

Page 2: ...the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the hole in the thermostat controller mounting base 5 Align the thermostat contr...

Page 3: ...mperature readings 3 Reinsert the screw terminal blocks onto the PCB Note If multiple wires are inserted into the terminals be sure to properly twist the wires together prior to inserting them into th...

Page 4: ...Fan H Fan H Fan H Fan On High 2 Fan M Fan M Fan M Fan On Medium 3 Fan L Fan L Fan L Fan On Low 4 24 V Hot 24 V Hot 24 V Hot 24 VAC from Transformer 5 24 V Com 24 V Com 24 V Com 24 VAC Common from Tran...

Page 5: ...Alarm Voltage Free Contact Remote NSB Motion Window OR Same 24 VAC Power Source for Auxiliary Output 24 VAC Maximum Separate 24 VAC Power Source for Auxiliary Output 24 VAC Maximum BO5 Aux BO5 Aux 24...

Page 6: ...Pipe Applications Four Pipe Applications FIG T6023dfh3ooc 24 V Com 24 V Hot or 24 V Com 24 V Hot Cooling Valve or Heating Valve or Figure 8 Wiring T602DFH 4 and T603DFH 4 Thermostat Controllers for F...

Page 7: ...perature scale to either Celsius or Fahrenheit and allow access to the Installer Configuration Menu See the Configuring the T60xDFH 4 and T60xDFH 4 PIR Series Thermostat Controller section Use the UP...

Page 8: ...ehumidification operation If the thermostat controller is in Cooling demand the chilled water valve opens to 100 the thermostat controller stages Heating to maintain the room temperature at the Coolin...

Page 9: ...PIR sensing device used If movements are detected by the PIR sensor and the door is closed the room is considered occupied The thermostat controller switches back to Stand By mode only if the door sw...

Page 10: ...nu begins press and release the center key to scroll through the parameters listed in Table 4 3 When the desired parameter is displayed use the UP DOWN arrow keys to choose the desired selection optio...

Page 11: ...eration in Four Pipe Applications Selection Option Control Curve Terminal Numbers Used See Table 1 and Figure 5 On Off Control Floating Control Proportional 0 to 10 VDC Control 0 Cooling Only See Figu...

Page 12: ...16 Cooling with Reheat Two or Four Pipe Applications Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Cooling Setpoint Device Opened FIG clng_wth_rht Deadband Reheat On Off Fl...

Page 13: ...ng Figure 20 This operation applies to the Occupied mode when the fan is set to Auto Figure 19 Heating Cooling with Reheat Four Pipe Applications Temperature Increase Increments of 1F 0 5C Heating Set...

Page 14: ...at controller remains in the Occupied mode if the contact is open until the TOccTime expires Advanced PIR occupancy functions using a Normally Open N O or Normally Closed N C remote PIR motion sensor...

Page 15: ...an input COC NH Changeover Contact Normally Heat A dry contact input is used to signal seasonal hot cold water changeover The contact closes when cold water is present Valid only for two pipe systems...

Page 16: ...sequence of operation Default 1 Sequence of Operation Default Based on AutoMode Parameter Setting On Off 0 Cooling Only Off Cool Cool Cool 1 Heating Only Off Heat Heat Heat 2 Cooling and Reheat Off Au...

Page 17: ...ive Range 0 5 to 24 0 hrs adjustable in 0 5 hour increments Unocc TM Sets the Unoccupied timer value PIR models Default 0 0 hours Time delay between the moment the thermostat controller toggled to Sta...

Page 18: ...d between the return and supply air feeds that is directly influenced by the supply air stream 3 3 0F 1 7C 4 4 0F 2 2C 5 5 0F 2 8C 6 6 0F 3 3C 7 7 0F 3 9C 8 8 0F 4 4C 9 9 0F 5 0C 10 10 0F 5 6C Set typ...

Page 19: ...s the desired humidity sensor calibration offset The offset can be added to or subtracted from the actual displayed room humidity T603 and T605 models This parameter can be used only if the dehumidifi...

Page 20: ...perature error from the setpoint FL time Sets the maximum actuator stroke timing floating CntrlTyp T602 and T603 models Default 1 5 min Range 0 5 to 9 0 min adjustable in 0 5 minute increments Cph Set...

Page 21: ...at Controllers with Dehumidification and Occupancy Sensing Capability Part 1 of 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals 4 and 5 at 24 VAC Nominal Class 2 or Safety Extra Low Voltage...

Page 22: ...2 2 No 24 Temperature Indicating and Regulating Equipment Industry Canada ICES 003 Europe CE Mark Johnson Controls Inc declares that this product is in compliance with the essential requirements and o...

Reviews: