Outdoor Temperature (providing sensor is 
connected and functional) 

• 

Applicable Alarms (The backlight lights up and an 
alarm condition is displayed.) 

To temporarily stop the scrolling, press the 
YES/SCROLL key. 

The 

Main User Menu

 is used to access and change 

the thermostat’s basic operating parameters. Access 
the menu by pressing the MENU key during normal 
thermostat operation. 

The 

Installer Configuration Menu 

is used to set up 

the thermostat for application specific operation. 
Access the menu by removing the front cover and 
pressing the configuration key, labeled CONFIG 
(Figure 7). 

Configuring the T600MEP-2 

The T600MEP-2 ships from the factory with default 
settings for all configurable parameters. The default 
settings are shown in Table 1. To reconfigure the 
parameters, follow the steps in this section for the 
corresponding parameters. The parameters must be 
set up by accessing the Installer Configuration Menu. 
Access the Installer Configuration Menu by removing 
the front cover and pressing the configuration key 
(Figure 7). 

Exit the Installer Configuration Menu any time by 
pressing the MENU key and, at the exit prompt, 
pressing the YES key. To pass over a parameter 
without changing it, press the NO key. 

When the thermostat is in the Installer Configuration 
Menu and left unattended for 45 seconds, it reverts to 
the Status Display Menu. 

Table 1: Installer Configuration Menu 

 

Remove the cover and press the 

CONFIG key from the Status Display 

Menu to enter the Installer 
Configuration Menu. 

 

Configures Digital Input 1 
Default: No Function 

(None) 

See the 

Configuring the Digital Inputs 

(DI1 and DI2) 

section. 

 

Configures Digital Input 2 
Default: No Function 

(None) 

See the 

Configuring the Digital Inputs 

(DI1 and DI2) 

section. 

 

Sets Keypad Lockout Level 
Default: No Lockout 

(0) 

See the 

Enabling Keypad Lockout 

(Lockout) 

section. 

 

Sets Power-up Delay 
Default: Ten Seconds 

(10.0 sec) 

See the 

Setting the Power-up Delay 

(Pwr del) 

section. 

 

Enables/Disables Frost Protection 
Default: Disabled 

(Off) 

See the 

Enabling Frost Protection 

(Frost pr) 

section. 

 

Sets the Maximum Heating Setpoint 
Default: 

90.0

°

F (32.0

°

C)

 

See the 

Setting the Maximum Heating 

Setpoint (Heat max) 

section. 

 

Sets the Minimum Cooling Setpoint 
Default: 

54.0

°

F (12.0

°

C)

 

See the 

Setting the Minimum Cooling 

Setpoint (Cool min) 

section. 

 

Sets the Anti-short Cycle Timer 
Default: Two Minutes 

(2.0 min)

 

See the 

Setting the Anti-Short Cycle 

Timer (Anticycl) 

section. 

 

Sets the Maximum Heating Cycles per 
Hour 
Default: Four 

(4.0) 

See the 

Setting the Maximum Heating 

Cycles per Hour (Heat cph) 

section. 

 

Sets the Maximum Cooling Cycles per 
Hour 
Default: Four 

(4.0) 

See the 

Setting the Maximum Cooling 

Cycles per Hour (Cool cph) 

section. 

 

Sets the Minimum Heating/Cooling 
Deadband 
Default: 

2.0

°

F (1.1

°

C) 

See the 

Setting the Heating/Cooling 

Deadband (Deadband) 

section. 

 

Determines how the Fan Activates in 
Response to a call for Heat 
Default: Thermostat Controls Fan 

(On)

See the 

Setting the Fan Control (Fan 

cont) 

section. 

 

Delays Fan Termination at Cycle’s End 
for 60 Seconds 
Default: No Delay 

(Off) 

See the 

Setting the Fan Delay (Fan 

del) 

section. 

Continued on the next page . . . 

Lockout
set? Y/N 

Pwr del
set? Y/N 

Frost pr
set? Y/N 

Heat max
set? Y/N 

Cool min
set? Y/N 

Anticycl
set? Y/N 

Heat cph
set? Y/N 

Cool cph
set? Y/N 

Deadband
set? Y/N 

RoomTemp 
75.0 

°

F

 

Fan cont
set? Y/N 

DI1 
set? Y/N

 

Fan del

set? Y/N

DI2 
set? Y/N 

T600MEP-2 Programmable Economizer Thermostat Installation Instructions    

5

 

Summary of Contents for T600MEP-2

Page 1: ...ver using a Phillips head screwdriver Open the thermostat by pulling on the bottom side of the thermostat cover Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tabs t...

Page 2: ...einsert on to the new thermostat To wire the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram see Figure 5 2 Gently push excess wire...

Page 3: ...common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second stage heating Configurable auxiliary output Configurable digital...

Page 4: ...keys to adjust values activate a Temporary Setpoint Backlit Liquid Crystal Display LCD The T600MEP 2 uses a two line eight character display Low level backlighting is present during normal operation a...

Page 5: ...nputs DI1 and DI2 section Configures Digital Input 2 Default No Function None See the Configuring the Digital Inputs DI1 and DI2 section Sets Keypad Lockout Level Default No Lockout 0 See the Enabling...

Page 6: ...oling Mode C mech section Sets the Mixed Air Temperature Setpoint Default 55 F 13 C See the Setting the Mixed Air Temperature Setpoint Mix stpt section Displays the Mixed Air Temperature Default None...

Page 7: ...ay before any operation is authorized fan cooling and heating The delay time is adjustable between 10 and 120 seconds This parameter can also be used to sequence the start up of multiple units in one...

Page 8: ...uration Menu 1 Answer NO to all prompts until the anti short cycle timer prompt appears in the display Press YES to enter the anti short cycle timer menu 2 Use the UP DOWN arrow keys to adjust the min...

Page 9: ...er NO to all prompts until the fan delay prompt appears in the display Press YES to enter the fan delay menu 2 Using the UP DOWN arrow keys select on or off Press YES to store the selection The displa...

Page 10: ...temperature is above the heating lockout temperature heating operation is disabled The heating lockout temperature parameter is adjustable from 15 to 120 F 26 to 49 C in increments of 5 F C To change...

Page 11: ...to select on or off Press YES to store the selection The display now shows the economizer changeover setpoint menu See Setting the Economizer Changeover Temperature Chngstpt section for instructions S...

Page 12: ...YES to store the temperature The display mixed air temperature prompt is now displayed See Displaying the Mixed Air Temperature Display section for instructions Displaying the Mixed Air Temperature Di...

Page 13: ...User Menu Override schd Y N 1 Answer NO to all prompts until the Override Schedule prompt appears If the Thermostat is in the unoccupied state this is the first prompt 2 Press YES to enable the occupi...

Page 14: ...current mode of operation Temperat set Y N Note Whether the thermostat is heating or cooling the respective setpoint is temporarily adjusted Cooling set Y N Note To toggle between the temporary heatin...

Page 15: ...the time press the UP DOWN arrow keys to change the time in 1 minute increments Hold the keys down to change the time in 30 minute increments Note Programming one of the digital inputs to remote NSB d...

Page 16: ...uling menu Press YES to set the schedule for Monday or NO to advance to Tuesday Press YES to set the occupied start time for Monday or NO to advance to Tuesday selecting NO leaves the thermostat in th...

Page 17: ...the UP DOWN arrow keys to adjust the day When the correct day is displayed press YES to store the day 6 Press YES to choose the time format or NO to access the Main User Menu exit prompt 7 Use the UP...

Page 18: ...t Operating Conditions 32 to 122 F 0 to 50 C 0 to 95 RH noncondensing Ambient Storage Conditions 22 to 122 F 30 to 50 C 0 to 95 RH noncondensing Dimensions H x W x D 4 94 x 3 38 x 1 13 in 125 x 86 x 2...

Reviews: