Setting the Mechanical Cooling Mode (C mech) 

This setting determines whether to allow the operation 
of mechanical cooling if the free cooling (economizer) 
cannot maintain the cooling setpoint. 

• 

Selecting 

off

 means the mechanical cooling never 

operates at the same time as the free cooling. This 
option typically applies when the mixed air 
temperature sensor is installed after the 
mechanical cooling coils. 

• 

Selecting 

on

 enables mechanical cooling to 

operate when the free cooling (economizer) 
cannot maintain the cooling setpoint. This option 
typically applies when the mixed air temperature 
sensor is installed before the mechanical cooling 
coils. 

To set the mechanical cooling mode while in the 
Installer Configuration Menu: 

1. 

Answer NO to all prompts until the mechanical 
cooling mode prompt appears in the display. 
Press YES to enter the mechanical cooling mode 
menu. 

2. 

Use the UP/DOWN arrow keys to choose 

on

 or 

off

. Press YES to store the selection. 

The display now shows the mixed air setpoint menu. 
See 

Setting the Mixed Air Temperature Setpoint 

(Mix stpt) 

section for instructions. 

Setting the Mixed Air Temperature Setpoint 
(Mix stpt) 

The mixed air temperature setpoint establishes the 
mixed air temperature when operating in the 
economizer mode. The economizer is adjusted 
accordingly to maintain the mixed air temperature 
setpoint. 

The mixed air temperature setpoint is adjustable from 
50 to 90

°

F (10 to 32

°

C). 

To adjust the mixed air temperature setpoint while in 
the Installer Configuration Menu: 

1. 

Answer NO to all prompts until the mixed air 
setpoint prompt appears in the display. Press 
YES to enter the mixed air setpoint menu. 

2. 

Use the UP/DOWN arrow keys to adjust the 
mixed air setpoint. Press YES to store the 
temperature. 

The display mixed air temperature prompt is now 
displayed. See 

Displaying the Mixed Air Temperature 

(Display) 

section for instructions. 

Displaying the Mixed Air Temperature (Display) 
(Only Available if Mixed Air Temperature Sensor is 
Installed) 

The mixed air temperature can be displayed if a mixed 
air temperature sensor is installed. The temperature 
can be used to help service and troubleshoot the 
equipment and economizer operation. The mixed air 
temperature is only accessible through the installer 
configuration menu. 

To access the mixed air temperature while in the 
Installer Configuration Menu: 

1. 

Answer NO to all prompts until the display mixed 
air temperature prompt appears in the display. 
Press YES to display mixed air temperature. 

2. 

The mixed air temperature is displayed. After 
about 45 seconds, the T600MEP-2 returns to the 
Status Display Menu or press YES to advance to 
the exit menu display. The exit menu appears. 

3. 

Press YES to exit the Installer Configuration 
Menu or press NO to return to the beginning of 
the menu (digital input configuration). 

Operation 

Programming/Operating the T600MEP-2 

Once the T600MEP-2 is configured through the 
Installer Configuration Menu, the thermostat’s 
operating parameters can be programmed through the 
Main User Menu (access the Main User Menu by 
pressing the MENU key during normal thermostat 
operation). The Main User Menu contains the basic 
operating features of the T600MEP-2. 

The Main User Menu uses Auto Help. Auto Help is 
displayed automatically in the Main User Menu when 
there is a pause in programming activity. To exit Auto 
Help, continue with the programming selection. 

When the thermostat is in the Main User Menu and is 
left unattended for 45 seconds, it reverts to the Status 
Display Menu. 

Follow the steps in Table 4 to program the 
T600MEP-2. 

12    

T600MEP-2 Programmable Economizer Thermostat Installation Instructions 

Summary of Contents for T600MEP-2

Page 1: ...ver using a Phillips head screwdriver Open the thermostat by pulling on the bottom side of the thermostat cover Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tabs t...

Page 2: ...einsert on to the new thermostat To wire the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram see Figure 5 2 Gently push excess wire...

Page 3: ...common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second stage heating Configurable auxiliary output Configurable digital...

Page 4: ...keys to adjust values activate a Temporary Setpoint Backlit Liquid Crystal Display LCD The T600MEP 2 uses a two line eight character display Low level backlighting is present during normal operation a...

Page 5: ...nputs DI1 and DI2 section Configures Digital Input 2 Default No Function None See the Configuring the Digital Inputs DI1 and DI2 section Sets Keypad Lockout Level Default No Lockout 0 See the Enabling...

Page 6: ...oling Mode C mech section Sets the Mixed Air Temperature Setpoint Default 55 F 13 C See the Setting the Mixed Air Temperature Setpoint Mix stpt section Displays the Mixed Air Temperature Default None...

Page 7: ...ay before any operation is authorized fan cooling and heating The delay time is adjustable between 10 and 120 seconds This parameter can also be used to sequence the start up of multiple units in one...

Page 8: ...uration Menu 1 Answer NO to all prompts until the anti short cycle timer prompt appears in the display Press YES to enter the anti short cycle timer menu 2 Use the UP DOWN arrow keys to adjust the min...

Page 9: ...er NO to all prompts until the fan delay prompt appears in the display Press YES to enter the fan delay menu 2 Using the UP DOWN arrow keys select on or off Press YES to store the selection The displa...

Page 10: ...temperature is above the heating lockout temperature heating operation is disabled The heating lockout temperature parameter is adjustable from 15 to 120 F 26 to 49 C in increments of 5 F C To change...

Page 11: ...to select on or off Press YES to store the selection The display now shows the economizer changeover setpoint menu See Setting the Economizer Changeover Temperature Chngstpt section for instructions S...

Page 12: ...YES to store the temperature The display mixed air temperature prompt is now displayed See Displaying the Mixed Air Temperature Display section for instructions Displaying the Mixed Air Temperature Di...

Page 13: ...User Menu Override schd Y N 1 Answer NO to all prompts until the Override Schedule prompt appears If the Thermostat is in the unoccupied state this is the first prompt 2 Press YES to enable the occupi...

Page 14: ...current mode of operation Temperat set Y N Note Whether the thermostat is heating or cooling the respective setpoint is temporarily adjusted Cooling set Y N Note To toggle between the temporary heatin...

Page 15: ...the time press the UP DOWN arrow keys to change the time in 1 minute increments Hold the keys down to change the time in 30 minute increments Note Programming one of the digital inputs to remote NSB d...

Page 16: ...uling menu Press YES to set the schedule for Monday or NO to advance to Tuesday Press YES to set the occupied start time for Monday or NO to advance to Tuesday selecting NO leaves the thermostat in th...

Page 17: ...the UP DOWN arrow keys to adjust the day When the correct day is displayed press YES to store the day 6 Press YES to choose the time format or NO to access the Main User Menu exit prompt 7 Use the UP...

Page 18: ...t Operating Conditions 32 to 122 F 0 to 50 C 0 to 95 RH noncondensing Ambient Storage Conditions 22 to 122 F 30 to 50 C 0 to 95 RH noncondensing Dimensions H x W x D 4 94 x 3 38 x 1 13 in 125 x 86 x 2...

Reviews: