Installation Instructions   

 

Issue Date  January 19, 2005 

 

©  2005 Johnson Controls, Inc.

 

1

 

 

T600MEP-2 Programmable Economizer Thermostat 

 

Application 

The T600MEP-2 is a programmable thermostat for 
control of single- or two-stage unitary rooftop units with 
economizers. The T600MEP-2 thermostat provides 
exceptional accuracy through the use of a unique 
Proportional-Integral (PI) time proportioning algorithm. 
The algorithm virtually eliminates temperature offset 
associated with traditional, differential-based on/off 
thermostats. The T600MEP-2 also uses an adaptive 
control logic algorithm to control the space 
temperature during recovery to minimize overshoot 
while providing maximum comfort. Economizer 
functions include a 0 to 10 VDC control signal, dry bulb 
changeover strategy, adjustable minimum position, 
and mixed air setpoint control. Additionally, the menu 
driven backlit display, plain text menus, and five keys 
on the T600MEP-2 make programming the thermostat 
easy and intuitive. 

Installation 

Location Considerations 

Locate the T600MEP-2 thermostat: 

• 

on a partitioning interior wall, and approximately 
5 ft. (1.5 m) above the floor in a location of 
average temperature 

• 

away from direct sunlight, radiant heat, outside 
walls, behind doors, air discharge grills, stairwells, 
or outside doors 

• 

away from steam or water pipes, warm air stacks, 
unheated/uncooled areas, or sources of electrical 
interference 

To install the thermostat: 

1. 

Remove the security screw on the bottom of the 
thermostat cover using a Phillips-head 
screwdriver. Open the thermostat by pulling on 
the bottom side of the thermostat cover 
(Figure 1). 

2. 

Unlock the Printed Circuit Board (PCB) by 
carefully pressing the locking tabs to the right 
(Figure 2). Open the thermostat’s PCB to the left. 

3. 

Pull out approximately 6 in. (152 mm) of wires 
from the wall and insert the cable through the 
hole in the base. 

4. 

Align the base on the wall, and using the base as 
a template, mark the location of the two mounting 
holes on the wall. Confirm the thermostat base is 
installed with the proper side up. 

5. 

Use the supplied anchors and screws for 
mounting on drywall or plaster. Drill two 3/16 in. 
(4.7 mm) holes at the marked locations and tap 
nylon anchors flush to wall surface (Figure 3). 

6. 

Position base on the wall, insert screws through 
mounting base, and fasten into wall anchors. Do 
not overtighten screws. 

7. 

Swing the thermostat PCB back to the right to 
close. Gently press on the PCB to secure each of 
the locking tabs. 

8. 

Pull out the screw terminal blocks using the 
pull-tabs on each connector (Figure 4). 

Note: 

The number of terminals on the terminal 

blocks varies depending on the T600 model. 

IMPORTANT: 

Use this T600MEP-2 

programmable economizer thermostat only as an 
operating control. Where failure or malfunction of the 
thermostat could lead to personal injury or property 
damage to the controlled equipment or other 
property, additional precautions must be designed 
into the system. Incorporate and maintain other 
devices such as supervisory or alarm systems or 
safety or limit controls intended to warn of, or protect 
against, failure or malfunction of the thermostat. 

  Part No. 24-9889-150, Rev. A 

www.johnsoncontrols.com 

Summary of Contents for T600MEP-2

Page 1: ...ver using a Phillips head screwdriver Open the thermostat by pulling on the bottom side of the thermostat cover Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tabs t...

Page 2: ...einsert on to the new thermostat To wire the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram see Figure 5 2 Gently push excess wire...

Page 3: ...common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second stage heating Configurable auxiliary output Configurable digital...

Page 4: ...keys to adjust values activate a Temporary Setpoint Backlit Liquid Crystal Display LCD The T600MEP 2 uses a two line eight character display Low level backlighting is present during normal operation a...

Page 5: ...nputs DI1 and DI2 section Configures Digital Input 2 Default No Function None See the Configuring the Digital Inputs DI1 and DI2 section Sets Keypad Lockout Level Default No Lockout 0 See the Enabling...

Page 6: ...oling Mode C mech section Sets the Mixed Air Temperature Setpoint Default 55 F 13 C See the Setting the Mixed Air Temperature Setpoint Mix stpt section Displays the Mixed Air Temperature Default None...

Page 7: ...ay before any operation is authorized fan cooling and heating The delay time is adjustable between 10 and 120 seconds This parameter can also be used to sequence the start up of multiple units in one...

Page 8: ...uration Menu 1 Answer NO to all prompts until the anti short cycle timer prompt appears in the display Press YES to enter the anti short cycle timer menu 2 Use the UP DOWN arrow keys to adjust the min...

Page 9: ...er NO to all prompts until the fan delay prompt appears in the display Press YES to enter the fan delay menu 2 Using the UP DOWN arrow keys select on or off Press YES to store the selection The displa...

Page 10: ...temperature is above the heating lockout temperature heating operation is disabled The heating lockout temperature parameter is adjustable from 15 to 120 F 26 to 49 C in increments of 5 F C To change...

Page 11: ...to select on or off Press YES to store the selection The display now shows the economizer changeover setpoint menu See Setting the Economizer Changeover Temperature Chngstpt section for instructions S...

Page 12: ...YES to store the temperature The display mixed air temperature prompt is now displayed See Displaying the Mixed Air Temperature Display section for instructions Displaying the Mixed Air Temperature Di...

Page 13: ...User Menu Override schd Y N 1 Answer NO to all prompts until the Override Schedule prompt appears If the Thermostat is in the unoccupied state this is the first prompt 2 Press YES to enable the occupi...

Page 14: ...current mode of operation Temperat set Y N Note Whether the thermostat is heating or cooling the respective setpoint is temporarily adjusted Cooling set Y N Note To toggle between the temporary heatin...

Page 15: ...the time press the UP DOWN arrow keys to change the time in 1 minute increments Hold the keys down to change the time in 30 minute increments Note Programming one of the digital inputs to remote NSB d...

Page 16: ...uling menu Press YES to set the schedule for Monday or NO to advance to Tuesday Press YES to set the occupied start time for Monday or NO to advance to Tuesday selecting NO leaves the thermostat in th...

Page 17: ...the UP DOWN arrow keys to adjust the day When the correct day is displayed press YES to store the day 6 Press YES to choose the time format or NO to access the Main User Menu exit prompt 7 Use the UP...

Page 18: ...t Operating Conditions 32 to 122 F 0 to 50 C 0 to 95 RH noncondensing Ambient Storage Conditions 22 to 122 F 30 to 50 C 0 to 95 RH noncondensing Dimensions H x W x D 4 94 x 3 38 x 1 13 in 125 x 86 x 2...