1031990-UAD-A-0313
Johnson Controls Unitary Products
11
R / W
(5) BV
24
SAT_HEATING
n/a
n/a
n/a
Supply Air Temperature Limit for
Heating Enabled
R / W
(2) AV
52
SAT_HEAT_SP
135
100
180
Supply Air Temperature Limit for
Heating Setpoint (degrees F)
R
(2) AI
34
SFAN_VFD_OUT
n/a
n/a
n/a
Supply Fan VFD Output Status (0-
100%)
R
(2) AI
36
ALARM_1
n/a
n/a
n/a
System Alarm #1
R
(2) AI
37
ALARM_2
n/a
n/a
n/a
System Alarm #2
R
(2) AI
38
ALARM_3
n/a
n/a
n/a
System Alarm #3
R
(2) AI
39
ALARM_4
n/a
n/a
n/a
System Alarm #4
R
(2) AI
40
ALARM_5
n/a
n/a
n/a
System Alarm #5
R / W
(2) AV
29
TH_OFFSET
5
1
10
Temperature / Humidity % Humidity that
= 1°F of Offset
R / W
(2) AV
26
TEM_HUM_STPT
50
20
80
Temperature / Humidity Setpoint
(percent Humidity)
R / W
(5) BV
97
THERMO_CONTROL
n/a
n/a
n/a
Thermostat Only Control Enable
R / W
(5) BV
67
FAN_HEAT
n/a
n/a
n/a
Turn OFF Continuous Fan when
Starting Heat Enabled (0=Continuous
Fan ON)
R / W
(2) AV
2
UNOC_COOL_SP
85
46
99
Un-Occupied Cooling Setpoint
R / W
(2) AV
51
UNOC_HEAT_SP
60
45
98
Un-Occupied Heating Setpoint
R / W
(2) AV
75
UNOC_OVR_TP
60
0
240
Unoccupied Override Time Period
R
(5) BI
103
VAV_INTELLI_2_PRES
n/a
n/a
n/a
VAV / Intelli-Comfort 2 Expansion Board
Present
R / W
(2) AV
65
VAV_CL_LO_SP
55
40
69
VAV Cooling Supply Air Temperature:
Lower Setpoint (degrees F)
R / W
(2) AV
66
VAV_SAT_RSET
72
40
85
VAV Cooling Supply Air Temperature:
Reset Setpoint (Space
Temperature)(degrees F)
R / W
(2) AV
64
VAV_CL_HI_SP
60
41
70
VAV Cooling Supply Air Temperature:
Upper Setpoint (degrees F)
R / W
(5) BV
5
VAV_OCC_HEAT
n/a
n/a
n/a
VAV Occupied Heating Enabled
R / W
(2) AV
60
VAV_OHEAT_SP
68
40
85
VAV Occupied Heating Setpoint
(degrees F)
R / W
(5) BV
96
VAV_UNOCC_HEAT
n/a
n/a
n/a
VAV Unoccupied Heating Enabled
TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor
Default Min
Max Point Description