background image

1031990-UAD-A-0313

Johnson Controls Unitary Products

21

TROUBLESHOOTING

TABLE 4:

SIMPLICITY

®

LINC GATEWAY LED TROUBLESHOOTING

Light

Description

PWR

This is the power light and should show steady green at all times when the Simplicity Linc is powered.

SYS ERROR

The SYS ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red light will 
indicate there is a system error on the Simplicity Linc. If this occurs, contact UP Tech Services at 1-877-874-7378

COMM 

ERROR

COMM ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red light will 
indicate the communications problem if there is a configured node connected to the Simplicity Linc that is offline. 

Config 

ERROR

Config ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady amber light will 
indicate a configuration error exists in the active configuration.  If this occurs, contact UP Tech Services at 1-877-
874-7378

Node Offline

Node Offline LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. If the Node Offline LED 
stays on solid, a node offline condition has occurred.

Unused

15 seconds after powering up the 4 unused LEDs will turn on solid for 5 seconds, then turn off.

RX

On normal operation of Simplicity Linc, the RX LED will flash when a message is received on the field port.

TX

On normal operation of Simplicity Linc, the TX LED will flash when a message is sent on the field port.

RUN

RUN LED will flash 20 seconds after power up, signifying normal operation. During the first 20 seconds, the LED 
should be off.

General

Power Source

24 ± 15% VAC (Obtained from the Roof Top Unit)

Frequency

45 to 65 HZ

Power Consumption

Nominal >2 VA

Operating Environment

-40 to 160° F (-40 to 70° C) 10 to 95% non-condensing

Size (H x W x D)

5.0 x 2.4 x 1.8 in. (128 x 61 x 45.75 cm)

Weight

0.2 lb. (0.09 kg)

Processor

Type

Microchip

SDRAM Memory

2048 bytes

FLASH Memory

1024 bytes w/1,000,000 write cycle capability

Interface

Port 1 Type

BACnet MS/TP

Port 1 Speeds

9.6, 19.2, 38.4, 76.8 kbaud

Port 1 Connector

3-pin screw terminals

Port 2 Type

Modbus RTU (RS485)

Port 2 Speeds

9.6, 19,2 kbaud

Port 2 Connector

6-pin screw terminals

LAN Cable

Screened Twisted-Pair (Belden 9272 or 89272)

LEDs

Controller Status; BACnet; Modbus

Switch Selections

MAC Address (1-99), Baud Rate

Summary of Contents for Simplicity LINC

Page 1: ...fort controllers The Simplicity LINC mounts inside the control panel of the UP unit and utilizes 24 VAC power from the unit s control transformer One port is connected to the UP controller The other p...

Page 2: ...and defaulted to 230 The combination of the DE Modifier and the default DIP switch setting creates a default DE of 23001 The default Unit Name is YORK_RTU FIGURE 2 MAC ADDRESS EXAMPLES DIP switches B...

Page 3: ...URCE1 Toll free at 1 800 536 6112 SOFTWARE SETUP The control sequence is managed by the Simplicity controller The data points on these systems are mapped to standard BACnet Objects As a preconfigured...

Page 4: ...ive R 5 BI 87 ALARM_3_ON n a n a n a Alarm Buffer 3 0 Alarm has cleared 1 Alarm is still active R 5 BI 88 ALARM_4_ON n a n a n a Alarm Buffer 4 0 Alarm has cleared 1 Alarm is still active R 5 BI 89 AL...

Page 5: ...BI 31 ECONO_STATUS n a n a n a Economizer Output Status 0 not Free Cooling 1 Free Cooling R W 2 AV 22 ECON_OAEN_SP 27 10 50 Economizer Outside Air Enthalpy Setpoint R W 2 AV 23 ECON_OAT_ENA 55 40 80...

Page 6: ...zed R 5 BI 64 E_GAS_VLVE3 n a n a n a Elite Gas Valve 3 Input Status 1 energized 0 not energized R 5 BI 44 E_HPS1 n a n a n a Elite High Pressure Switch for Compressor 1 Input Status 1 closed 0 open f...

Page 7: ...Present R 5 BI 32 FRECOOL_STAT n a n a n a Free Cooling Mode Status 0 comps not overridden by Econo 1 comps overridden R 5 BI 104 FREEZE_STAT_1 n a n a n a Freeze Stat 1 R 5 BI 105 FREEZE_STAT_2 n a...

Page 8: ...elli Comfort Compressor 2 Accumulated Run Time in hours R 5 BI 76 I_COMP2_STAT n a n a n a Intelli Comfort Compressor 2 Input Status 0 output is OFF 1 output is ON R 5 BI 79 I_CFAN_STAT n a n a n a In...

Page 9: ...0 100 Maximum Demand Ventillation Economizer Position R W 5 BV 110 MIN_AMB_SEN n a n a n a Minimum Outdoor Air Sensor Enabled R W 2 AV 85 MIN_AMB_TEMP_SP 0 0 100 Minimum Outdoor Air Temperature Setpo...

Page 10: ...1 REM_CONT_BAS_ECON n a n a n a Remote Control Third Party BAS Economizer Enable R 2 AI 13 RET_AIR_ENTH n a n a n a Return Air Enthalpy R W 2 AV 12 RET_AIR_HUM n a n a n a Return Air Humidity R 2 AI 5...

Page 11: ...OFF Continuous Fan when Starting Heat Enabled 0 Continuous Fan ON R W 2 AV 2 UNOC_COOL_SP 85 46 99 Un Occupied Cooling Setpoint R W 2 AV 51 UNOC_HEAT_SP 60 45 98 Un Occupied Heating Setpoint R W 2 AV...

Page 12: ...umidity R 2 AI 13 RET_AIR_ENTH n a n a n a Return Air Enthalpy R W 2 AV 14 ACC_OVER_TME n a n a n a Accumulated Unoccupied Override Time in hours R 2 AI 15 ACTIVE_ALARM n a n a n a Active Alarm R 2 AI...

Page 13: ...te Compressor 2 Accumulated Run Time in hours R 2 AI 43 E_C3_ACM_HRS n a n a n a Elite Compressor 3 Accumulated Run Time in hours R 2 AI 44 E_C4_ACM_HRS n a n a n a Elite Compressor 4 Accumulated Run...

Page 14: ...VAV_CL_HI_SP 60 41 70 VAV Cooling Supply Air Temperature Upper Setpoint degrees F R W 2 AV 65 VAV_CL_LO_SP 55 40 69 VAV Cooling Supply Air Temperature Lower Setpoint degrees F R W 2 AV 66 VAV_SAT_RSET...

Page 15: ...V 90 FAN_SPD_NO_HEAT_C OOL 50 0 100 Fan Speed No Heating No Cooling R W 2 AV 91 FAN_SPD_1ST_COOL 70 0 100 Fan Speed 1st Stage Cooling R W 2 AV 92 FAN_SPD_1ST_HEAT 100 0 100 Fan Speed 1st Stage Heating...

Page 16: ...Space Sensor Present Option Enabled R W 5 BV 22 SAT_COOLING n a n a n a Supply Air Temperature Limit for Cooling Enabled R W 5 BV 23 COOLING_ENA n a n a n a Cooling Mode Enabled R W 5 BV 24 SAT_HEATIN...

Page 17: ...ut Status 1 closed 0 open fault R 5 BI 44 E_HPS1 n a n a n a Elite High Pressure Switch for Compressor 1 Input Status 1 closed 0 open fault R 5 BI 45 E_C1_OVRLOAD n a n a n a Elite Compressor 1 Overlo...

Page 18: ...energized R 5 BI 61 E_LIMIT_ 1 n a n a n a Elite Limit Switch 1 Input Status 1 closed 0 open fault R 5 BI 62 E_GAS_VLVE2 n a n a n a Elite Gas Valve 2 Input Status 1 energized 0 not energized R 5 BI...

Page 19: ...li Comfort High Pressure Switch for Compressor 2 Input Status 1 closed 0 open fault R 5 BI 79 I_CFAN_STAT n a n a n a Intelli Comfort Condenser Fan 1 Input Status 0 output is OFF 1 output is ON R 5 BI...

Page 20: ...n a n a Accept Comm Value for OAT R 5 BI 102 4_STG_EXP_PRES n a n a n a Four Stage Expansion board Present R 5 BI 103 VAV_INTELLI_2_PRES n a n a n a VAV Intelli Comfort 2 Expansion Board Present R 5...

Page 21: ...l turn off after 5 seconds If the Node Offline LED stays on solid a node offline condition has occurred Unused 15 seconds after powering up the 4 unused LEDs will turn on solid for 5 seconds then turn...

Page 22: ...ls Inc All rights reserved Supersedes Nothing Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 FIGURE 3 SIMPLICITY LINC BOARD AND LED LAYOUT PWR RS485 PWR BACnet EOL Switch So Reset S...

Reviews: