background image

1031990-UAD-A-0313

14

Johnson Controls Unitary Products

R / W

(2) AV

54

OAT_HEAT_L_O

75

0

100

Outdoor Air Temperature 
HeatingLockout Temperature

R

(2) AI

55

HW_VLV_OUT

n/a

n/a

n/a

Hot Water Valve Output Status (0-
100%)

R

(2) AI

56

CV_VAV_SELEC

n/a

n/a

n/a

CV / VAV Selected (0= Valid CV, 
1=Valid VAV, 2= Invalid Value)

R / W

(2) AV

57

BLDG_SP_STPT

0.15

-0.25

0.25

Building Static Pressure Setpoint

R / W

(2) AV

58

DUCT_SP_STPT

1.5

0

5

Duct Static Pressure Setpoint

R / W

(2) AV

59

DUCT_SD_STPT

4.5

0

5

Duct Static Pressure Shutdown 
Setpoint

R / W

(2) AV

60

VAV_OHEAT_SP

68

40

85

VAV Occupied Heating Setpoint 
(degrees F)

R / W

(2) AV

61

MWU_RAT_STPT

70

50

85

Morning Warm-Up and VAV Heating: 
Return Air Temperature Setpoint 
(degrees F)

R / W

(2) AV

62

HYD_S1_SA_SP

120

80

180

Hydronic Heating Stage #1 Supply Air 
Setpoint (degrees F)

R / W

(2) AV

63

HYD_S2_SA_SP

150

81

180

Hydronic Heating Stage #2 Supply Air 
Setpoint (degrees F)

R / W

(2) AV

64

VAV_CL_HI_SP

60

41

70

VAV Cooling Supply Air Temperature: 
Upper Setpoint (degrees F)

R / W

(2) AV

65

VAV_CL_LO_SP

55

40

69

VAV Cooling Supply Air Temperature: 
Lower Setpoint (degrees F)

R / W

(2) AV

66

VAV_SAT_RSET

72

40

85

VAV Cooling Supply Air Temperature: 
Reset Setpoint (Space 
Temperature)(degrees F)

R

(2) AI

67

REVISION

n/a

n/a

xx

Device Revision

R / W

(2) AV

69

OP_STPT_DIF

1

1

5

Operating Setpoint Differential

R / W

(2) AV

70

SAT_ALM_COOL

0

0

80

Supply Air Temperature Alarm 
Setpoint for Cooling

R / W

(2) AV

71

SPCE_ALM_TMP

0

0

25

Space Sensor Alarm Temperature 
(degrees F, 0 = disabled)

R / W

(2) AV

72

SPCE_ALM_TIM

0

0

120

Space Sensor Alarm Time (minutes F, 
0 = disabled)

R / W

(2) AV

73

SP_OFF_RANGE

3

0

5

Space Temprature Sensor Offset 
Range (0-5 degrees)

R / W

(2) AV

74

OAT_COOL_L_O

45

0

100

Outdoor Air Temperature Cooling 
Lockout Temperature

R / W

(2) AV

75

UNOC_OVR_TP

60

0

240

Unoccupied Override Time Period

R

(2) AI

76

H1_ACCUM_HRS

n/a

n/a

n/a

Heating #1 Accumulated Run Time (in 
hours)

TABLE 3: POINTS LIST IN OBJECT ORDER  (CONTINUED)

Read/ 

Write

BACnet 

Object 

Type

BACnet 

Object 

Inst

Descriptor

Default

Min

Max

Point Description

Summary of Contents for Simplicity LINC

Page 1: ...fort controllers The Simplicity LINC mounts inside the control panel of the UP unit and utilizes 24 VAC power from the unit s control transformer One port is connected to the UP controller The other p...

Page 2: ...and defaulted to 230 The combination of the DE Modifier and the default DIP switch setting creates a default DE of 23001 The default Unit Name is YORK_RTU FIGURE 2 MAC ADDRESS EXAMPLES DIP switches B...

Page 3: ...URCE1 Toll free at 1 800 536 6112 SOFTWARE SETUP The control sequence is managed by the Simplicity controller The data points on these systems are mapped to standard BACnet Objects As a preconfigured...

Page 4: ...ive R 5 BI 87 ALARM_3_ON n a n a n a Alarm Buffer 3 0 Alarm has cleared 1 Alarm is still active R 5 BI 88 ALARM_4_ON n a n a n a Alarm Buffer 4 0 Alarm has cleared 1 Alarm is still active R 5 BI 89 AL...

Page 5: ...BI 31 ECONO_STATUS n a n a n a Economizer Output Status 0 not Free Cooling 1 Free Cooling R W 2 AV 22 ECON_OAEN_SP 27 10 50 Economizer Outside Air Enthalpy Setpoint R W 2 AV 23 ECON_OAT_ENA 55 40 80...

Page 6: ...zed R 5 BI 64 E_GAS_VLVE3 n a n a n a Elite Gas Valve 3 Input Status 1 energized 0 not energized R 5 BI 44 E_HPS1 n a n a n a Elite High Pressure Switch for Compressor 1 Input Status 1 closed 0 open f...

Page 7: ...Present R 5 BI 32 FRECOOL_STAT n a n a n a Free Cooling Mode Status 0 comps not overridden by Econo 1 comps overridden R 5 BI 104 FREEZE_STAT_1 n a n a n a Freeze Stat 1 R 5 BI 105 FREEZE_STAT_2 n a...

Page 8: ...elli Comfort Compressor 2 Accumulated Run Time in hours R 5 BI 76 I_COMP2_STAT n a n a n a Intelli Comfort Compressor 2 Input Status 0 output is OFF 1 output is ON R 5 BI 79 I_CFAN_STAT n a n a n a In...

Page 9: ...0 100 Maximum Demand Ventillation Economizer Position R W 5 BV 110 MIN_AMB_SEN n a n a n a Minimum Outdoor Air Sensor Enabled R W 2 AV 85 MIN_AMB_TEMP_SP 0 0 100 Minimum Outdoor Air Temperature Setpo...

Page 10: ...1 REM_CONT_BAS_ECON n a n a n a Remote Control Third Party BAS Economizer Enable R 2 AI 13 RET_AIR_ENTH n a n a n a Return Air Enthalpy R W 2 AV 12 RET_AIR_HUM n a n a n a Return Air Humidity R 2 AI 5...

Page 11: ...OFF Continuous Fan when Starting Heat Enabled 0 Continuous Fan ON R W 2 AV 2 UNOC_COOL_SP 85 46 99 Un Occupied Cooling Setpoint R W 2 AV 51 UNOC_HEAT_SP 60 45 98 Un Occupied Heating Setpoint R W 2 AV...

Page 12: ...umidity R 2 AI 13 RET_AIR_ENTH n a n a n a Return Air Enthalpy R W 2 AV 14 ACC_OVER_TME n a n a n a Accumulated Unoccupied Override Time in hours R 2 AI 15 ACTIVE_ALARM n a n a n a Active Alarm R 2 AI...

Page 13: ...te Compressor 2 Accumulated Run Time in hours R 2 AI 43 E_C3_ACM_HRS n a n a n a Elite Compressor 3 Accumulated Run Time in hours R 2 AI 44 E_C4_ACM_HRS n a n a n a Elite Compressor 4 Accumulated Run...

Page 14: ...VAV_CL_HI_SP 60 41 70 VAV Cooling Supply Air Temperature Upper Setpoint degrees F R W 2 AV 65 VAV_CL_LO_SP 55 40 69 VAV Cooling Supply Air Temperature Lower Setpoint degrees F R W 2 AV 66 VAV_SAT_RSET...

Page 15: ...V 90 FAN_SPD_NO_HEAT_C OOL 50 0 100 Fan Speed No Heating No Cooling R W 2 AV 91 FAN_SPD_1ST_COOL 70 0 100 Fan Speed 1st Stage Cooling R W 2 AV 92 FAN_SPD_1ST_HEAT 100 0 100 Fan Speed 1st Stage Heating...

Page 16: ...Space Sensor Present Option Enabled R W 5 BV 22 SAT_COOLING n a n a n a Supply Air Temperature Limit for Cooling Enabled R W 5 BV 23 COOLING_ENA n a n a n a Cooling Mode Enabled R W 5 BV 24 SAT_HEATIN...

Page 17: ...ut Status 1 closed 0 open fault R 5 BI 44 E_HPS1 n a n a n a Elite High Pressure Switch for Compressor 1 Input Status 1 closed 0 open fault R 5 BI 45 E_C1_OVRLOAD n a n a n a Elite Compressor 1 Overlo...

Page 18: ...energized R 5 BI 61 E_LIMIT_ 1 n a n a n a Elite Limit Switch 1 Input Status 1 closed 0 open fault R 5 BI 62 E_GAS_VLVE2 n a n a n a Elite Gas Valve 2 Input Status 1 energized 0 not energized R 5 BI...

Page 19: ...li Comfort High Pressure Switch for Compressor 2 Input Status 1 closed 0 open fault R 5 BI 79 I_CFAN_STAT n a n a n a Intelli Comfort Condenser Fan 1 Input Status 0 output is OFF 1 output is ON R 5 BI...

Page 20: ...n a n a Accept Comm Value for OAT R 5 BI 102 4_STG_EXP_PRES n a n a n a Four Stage Expansion board Present R 5 BI 103 VAV_INTELLI_2_PRES n a n a n a VAV Intelli Comfort 2 Expansion Board Present R 5...

Page 21: ...l turn off after 5 seconds If the Node Offline LED stays on solid a node offline condition has occurred Unused 15 seconds after powering up the 4 unused LEDs will turn on solid for 5 seconds then turn...

Page 22: ...ls Inc All rights reserved Supersedes Nothing Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 FIGURE 3 SIMPLICITY LINC BOARD AND LED LAYOUT PWR RS485 PWR BACnet EOL Switch So Reset S...

Reviews: