8 RLD-H10G Product/Technical Bulletin
S
pecifications
Product
RLD-H10G Refrigerant Leak Detector
Power Requirements
120 VAC at 60 Hz
Sensing Element Type
Positive Ion Emission Heated Diode
Approximate Sensitivity
Switch Position
Alarm Sensitivity (moving probe)
Small
>0.05 oz per year CFC or HCFC
>0.5 oz per year HFC
Medium
>0.5 oz per year CFC or HCFC
>1.0 oz per year HFC
Large
>3.0 oz per year CFC or HCFC
>5.0 oz per year HFC
Leak Alarm
Audible alarm, visible neon lamp
Response Time
Approximately 1 second
Warmup Time
Approximately 2 minutes
Accuracy
Meets SAE J1627 test requirements
Probe Length
Approximately 4.5 ft (1.4 m)
Ambient Operating
Conditions
32 to 113
°
F (0 to 45
°
C); 5-90% RH, non-condensing
Ambient Storage
Conditions
14 to 140
°
F (-10 to 60
°
C); 5-90% RH, non-condensing
Case
Vinyl
Dimensions (H x W x D)
2.8 x 8.8 x 5.0 in. (71 x 224 x 127 mm)
Shipping Weight
3.2 lb (1.4 kg)
Agency Listings
UL Listed, File SA9717
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications,
consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
Controls Group
507 E. Michigan Street
P.O. Box 423
Milwaukee, WI 53201
Printed in U.S.A.