Table 1: PCV1617/PCV1632 features callout numbers and descriptions
Callout
Physical features: description and references
9
Universal Input: Voltage Analog Input (0–10 VDC)
Resistive Analog Inputs (0–600k ohm) (see Table 2):
0–2k Potentiometer
RTD: 1k Nickel, 1k Platinum, or A99B SI
NTC: 10K Type L (10K JCI Type II is equivalent to Type L) or 2.252K Type II
Dry Contact Binary Input
10
FC Bus Pluggable Screw Terminal Block (see
11
12
13
TSTAT Modular Port: RJ-45 8-Pin Modular Jack (see
)
14
Captive Spacer and Screw (see Figure 2)
15
LED Status Indicators (see Table 8)
Wiring
Warning
Risk of Electric Shock:
Disconnect or isolate all power supplies before making electrical connections. More than one
disconnection or isolation may be required to completely de-energize equipment. Contact with
components carrying hazardous voltage can cause electric shock and may result in severe personal
injury or death.
Important:
Do not connect supply power to the controller before finishing wiring and
checking all wiring connections. Short circuits or improperly connected wires can result in
damage to the controller and void any warranty.
Important:
Do not exceed the controller electrical ratings. Exceeding controller electrical
ratings can result in permanent damage to the controller and void any warranty.
Important:
Use copper conductors only. Make all wiring in accordance with local, national,
and regional regulations.
Important:
Electrostatic Discharge can damage controller components. Use proper
Electrostatic Discharge precautions during installation, setup, and servicing to avoid damaging
the controller.
PCV terminals and bus ports
See Figure 2 for input and output terminal and bus port locations on the PCV1617 and PCV1632
controllers. Observe the following guidelines when wiring a PCV controller.
PCV1617 and PCV1632 VAV Box Controllers Installation instructions
6