Setting the EOL switch
Each PC controller has an EOL switch, which when set to ON (up), sets the PC controller as a
terminating device on the bus. See Figure 10 for the EOL switch location on the PC. The default EOL
switch position is OFF (down). The amber EOL LED illuminates to show that the EOL is active.
Figure 10: EOL switch positions
To set the EOL switch on a PC controller:
1. Determine the physical location of the PC controller on the SA or FC Bus.
2. Determine if the PC controller must be set as a terminating device on the bus.
Note:
The EOL termination rules for SA Buses and FC Buses are different.
3. If the PC is a terminating device on the FC Bus, set the EOL switch to ON. If the field controller
is not a terminating device on the bus, set the EOL switch to OFF.
Note:
When the EOL switch is set to ON, the LED light on the face of the controller is
illuminated.
Commissioning
Use the following procedure to commission the PCV1617 or PCV1632 controller:
1. Download the control application to the PCV controller using the Controller Configuration Tool
(CCT). Refer to the
Controller Tool Help (LIT-12011147)
.
2. Commission the VAV Box. Refer to the
Controller Tool Help (LIT-12011147)
.
3. Perform airflow balancing on the VAV box. Refer to the
VAV Balancing Tool and Network Sensors
Technical Bulletin (LIT-12011087)
.
4. Perform commissioning checkout procedures. Refer to the
Controller Tool Help (LIT-12011147)
.
The CCT connects to the PCV through a laptop computer using different connection options: the
Bluetooth
®
Commissioning Converter, or the wired BACnet Ethernet to MS/TP Router can be used
when using the BACnet MS/TP protocol.
Repair information
If the PCV1617 or PCV1632 controller fails to operate within its specifications, replace the unit. For a
replacement unit, contact the nearest Johnson Controls representative.
PCV1617 and PCV1632 VAV Box Controllers Installation instructions
20