Table 2: Termination details
Type of field
device
Type of
Input/
Output
Termination diagrams
Network
Stat with
Terminals
Addressable
SA Bus
Network
Stat with
Terminals
(Fixed
Address =
199)
SA Bus
Terminal wiring guidelines, functions, ratings, and
requirements
Input and Output wiring guidelines
Table 3 provides information and guidelines about the functions, ratings, and requirements for the
controller input and output terminals. The table also references guidelines for determining proper
wire sizes and cable lengths.
In addition to the wiring guidelines in Table 3, observe these guidelines when you wire controller
inputs and outputs:
• Run all low-voltage wiring and cables separate from high-voltage wiring.
• All input and output cables, regardless of wire size or number of wires, should consist of
stranded, insulated, and twisted copper wires.
• Shielded cable is not required for input or output cables.
• Shielded cable is recommended for input and output cables that are exposed to high
electromagnetic or radio frequency noise.
15
PCA3613 Advanced Application Programmable Controller Installation Instructions