PCA3613 physical features
Figure 3: PCA3613 physical features
Table 1: Physical features
Callout
Physical feature: description and references
1
Analog Output (AO) Terminal Block: Can be defined as Voltage Analog Output (0–10
VDC) or Current Analog Output (4–20 mA) (see Table 3)
2
Device Address DIP Switch Block (see
)
3
Mounting clip
4
Binary Outputs (BO) Terminal Block: 24 VAC Triac (see Table 3)
5
24 VAC, Class 2/SELV Supply Power Terminal Block (see
6
Cover Lift Tab (One of Two)
7
FC Bus Terminal Block (see
)
8
)
9
Sensor Port: (SA Bus) RJ-12 6-Pin Modular Jack (see
)
10
Binary Input (BI) Terminal Block: Dry Contact Maintained or Pulse Counter/Accumulator
Terminal wiring guidelines, functions, ratings, and requirements
11
Universal Inputs (UI) Terminal Block: Can be defined as Voltage Analog Input (0–10
VDC), Current Analog Input (4–20 mA), Resistive Analog Inputs (0–600k ohms), or Dry
Contact Binary Input (see
Input and Output wiring guidelines
5
PCA3613 Advanced Application Programmable Controller Installation Instructions