Note:

The wall mount feet are designed to make
mounting easier. When the NAE55 is wall
mounted in the BEST (horizontal) orientation,
you can hang the NAE55 on the screws with
the upper two mount feet.

5. Insert the screws into the lower two wall mount feet

and holes and carefully tighten all of the screws.

Important:

Do not overtighten the mounting screws.
Overtightening the screws can crack the
NAE55 wall mount feet or housing.

DIN Rail Mount Applications

To mount the NAE55 on DIN rails:

1. Mount two DIN rails horizontally, so they are 125 mm

(4.9 in.) apart on centers (

Figure 2

).

2. Snap the DIN clips on the bottom of the NAE55 to the

outward position.

3. Hang the NAE55 on the DIN rail hooks on the back

of the NAE55.

Press the DIN clips back into position to secure the unit
on the DIN rails.

Figure 4: Required Orientations for NAE55 Wall Mount

Applications

To remove the NAE55 from the DIN rails:
1. Snap the DIN clips on the bottom of the NAE55 to the

outward position.

2. Lift the NAE55 off the DIN rails.

Enclosure Mount

To mount the NAE55 in an enclosure:

1. Mount the enclosure per the manufacturer’s

instructions.

2. Mount the NAE55 in the enclosure following the

guidelines in the

Location Considerations

and

Mounting the NAE55

sections of this document.

Wiring

Power Supply, Network, and
Communication Connections

See

Figure 1

for the location of the power supply terminal,

network communication terminals, Ethernet jack, and
modem jack.

Power Supply

Important:

Install the data protection battery before
applying 24 VAC power to the NAE55. See
the

Installing the Data Protection Battery

section.

In North America, use a Class 2, 24 VAC power supply
with a 50 VA minimum output. Outside North America,
use a 24 VAC Safety Extra-Low Voltage (SELV)
transformer at the appropriate rating. The minimum input
voltage for the NAE55 to operate properly is 20 VAC.
See the

Technical Specifications

section.

Use a dedicated power supply to the NAE55 only. Do not
connect any other loads to the power supply. Additional
loads may cause noise interference.

FC Bus Terminal Block

The two Field Controllers (FCs) Bus connections on the
MS-NAE55xx-x models are 4-pin removable, keyed
terminal blocks labeled

FC A

and

FC B

.

Note:

MS-NIE55xx-x models (NIE55s) do not have FC
Bus terminal blocks or L

ON

W

ORKS

®

network

terminal blocks.

The FC bus connections are optically isolated RS-485
ports with keyed 4-position terminal blocks that
communicate at 9.6k, 19.2k, 38.4k, or 76.8k baud. Use
an FC Bus port to integrate an N2 network or a BACnet

®

Master-Slave/Token-Passing (MS/TP) FC Bus trunk into
the Metasys system.

Note:

N2 and BACnet MS/TP Buses have different
protocols and network requirements. Do not
connect N2 and MS/TP devices to the same FC
Bus port.

The Shield (SHD) connections on the FC terminal blocks
are not connected to any earth ground connection. The
FC A and FC B terminal blocks are not interchangeable.

L

ON

W

ORKS

Network Terminal Block

The L

ON

W

ORKS

TP/FT-10 network connection on the

MS-NAE552x-2 models (only) is a 3-wire removable,
keyed terminal block. The SHD connection on the
L

ON

W

ORKS

network terminal block is an isolated terminal

and is not connected in the NAE552x. Use the L

ON

W

ORKS

terminal block to connect L

ON

W

ORKS

networks to the

NAE552x.

4

NAE55/NIE55 Installation Instructions

Summary of Contents for NAE55 Series

Page 1: ...stalled and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in which case the users will be required to correct the interference at their own expense Canada This Class A digital apparatus meets all the requirements of the Canadian Interference Causing Equipment Reg...

Page 2: ...cal Features and Mounting Orientation Note The features shown in Figure 1 may or may not be present depending on the NAE55 NIE55 model See Ordering Information for a list of features available on the NAE55 NIE55 models 2 NAE55 NIE55 Installation Instructions ...

Page 3: ...m in Each NAE55 application is different and no general guidelines can be given about the heat dissipating devices that may be mounted in an enclosure with the NAE55 Monitor the NAE55 processor temperature for each application to determine the acceptable combinations of devices and proper mounting location for your specific application Important Do not add any devices to an enclosure with an NAE55...

Page 4: ...E55 See the Installing the Data Protection Battery section In North America use a Class 2 24 VAC power supply with a 50 VA minimum output Outside North America use a 24 VAC Safety Extra Low Voltage SELV transformer at the appropriate rating The minimum input voltage for the NAE55 to operate properly is 20 VAC See the Technical Specifications section Use a dedicated power supply to the NAE55 only D...

Page 5: ... guidelines when wiring the NAE55 Important Do not apply 24 VAC power to the NAE before completing and checking connections Short circuits or improperly connected wires may result in permanent damage to the equipment Important Do not apply 24 VAC power to the NAE55 before installing the data protection battery See the Installing the Data Protection Battery section in this document Important Use co...

Page 6: ...the transformer to the removable power terminal block plug Figure 7 Power supply wire colors may be different on transformers not manufactured by Johnson Controls Follow the transformer manufacturer s instructions and the project installation drawings The 24 VAC power should be connected to all network devices so transformer phasing is uniform across the devices Powering network devices with unifo...

Page 7: ...ble is recommended Stranded 0 6 mm 22 AWG shielded 4 wire two twisted pairs shielded cable is acceptable Note The and bus leads should be a twisted pair On applications using 4 wire two twisted pairs cable isolate and insulate unused conductor Refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for more information Cable Type 1 Two FC devices with End of Line EOL switches in the ...

Page 8: ...bus topology the maximum length stub cable is 3 m 10 ft and the stub lengths must be calculated into the overall segment length Table 5 Guidelines for LONWorks Network Free Topology Maximum Segment Length with FTT10 and or LPT10 11 Devices Maximum Node to Node Distance Cable Type 500 m 1 640 ft 500 m 1 640 ft Belden 85102 Cable 500 m 1 640 ft 500 m 1 640 ft Belden 8471 Cable 500 m 1 640 ft 400 m 1...

Page 9: ...le you to set the NAE55 as a network terminated device on the bus To set an NAE55 as an FC Bus terminated device position the switch on the EOL switch block to the ON position Figure 8 Figure 8 FC Bus EOL Switch in the Factory Default ON Up Position Note The NAE55 is shipped with the EOL switches for both FC Buses in the initial factory position ON Figure 8 If the NAE55 is not a terminated device ...

Page 10: ...epends on the size of the database and can take several minutes Figure 10 NAE55 with LED Designations System Re Boot Switch The System Re Boot switch Figure 1 forces a manual restart of the NAE55 processor All data changes made to the system since the last time the NAE55 saved data are lost on restart including alarm trend and audit trail data Note Press the System Re Boot switch only if the NAE55...

Page 11: ... 1 second NAE55 software is in startup mode On 0 5 seconds Off 0 5 seconds NAE55 software is shutting down Off Steady Operating system is shutting down or software is not running On Steady Run Green On Steady 24 VAC power is present Off Steady Loss of 24 VAC power In the Off Steady condition the NAE55 can be running on battery power Also see the POWER LED On Steady 24 VAC Green On Steady Battery f...

Page 12: ...nks or two BACnet MS TP RS 485 trunks or one N2 trunk and one BACnet MS TP trunk includes an internal modem Supports up to 255 devices on the LONWORKS trunk MS NAE5521 2 Contains ToggleTunnel utility for converting an NAE55 NIE55 to an NAE55 model with the N2 Tunneling features enabled Not for use with MS NAE5510 OU or MS NIE5510 OU MS MULTENGSW 6 1 Some models are also available in a Buy American...

Page 13: ...andard USB connectors support an optional user supplied external modem Options One telephone port for internal modem up to 56 kbps 6 pin RJ 12 connector One LONWORKS port FTT10 78 Kbps pluggable keyed 3 position terminal block LONWORKS port available on NAE552x x models only Network and Serial Interfaces Plastic housing with internal metal shield Plastic material ABS polycarbonate Protection IP20 ...

Page 14: ...3202 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2013 Johnson Controls Inc www johnsoncontrols com Published in U S A 14 NAE55 NIE55 Installation Instructions ...

Reviews: