background image

Table 7: NAE55 LEDs Designation, Normal Status, Description, and Other Conditions

Descriptions/Other Conditions

Normal

LED

On Steady (Green) = Ethernet connection is established at 100 Mbps.

On Steady (Yellow) = Ethernet connection is established at 1,000 Mbps.

On Steady

100/1000 LINK
(Green/Yellow)

On Steady = Controllers are defined to FC A (FC Bus 1 or N2 Trunk 1) in the
NAE55, but none are communicating (NAE55 transmitting only). Flicker = Normal
communications; FC A port is transmitting and receiving data. Flickers are generally
in sync with data transmission but should not be used to indicate specific
transmission times.

Off Steady = No field controllers are defined to FC A (FC Bus 1 or N2 Trunk 1) in
the NAE55.

Flicker

FC A (Green)

(NIE55 models do not
have FC Bus terminals.)

On Steady = Controllers are defined to FC B (FC Bus 2 or N2 Trunk 2) in the
NAE55, but none are communicating. (NAE55 transmitting only) Flicker = Normal
communications; FC B port is transmitting and receiving data. Flickers are generally
in sync with data transmission but should not be used to indicate specific
transmission times.

Off Steady = No field controllers are defined to FC B (FC Bus 2 or N2 Trunk 2) in
the NAE55.

Flicker

FC B (Green)

(NIE55 models do not
have FC Bus terminals.)

Flicker = Data traffic between NAEs. For an NAE55 that is not a Site Director, this
LED indicates regular heartbeat communications with the Site Director. For a Site
Director NAE55, flashes are more frequent and indicate heartbeat communications
from all other NAE devices on the site. For a single NAE55 on a network without
an Application and Data Server (ADS), there is no flicker.

Varies (see next
column)

PEER COMM (Green)

On Steady = NAE55 software is running.

On 1 second, Off 1 second = NAE55 software is in startup mode.

On 0.5 seconds, Off 0.5 seconds = NAE55 software is shutting down.

Off Steady = Operating system is shutting down or software is not running.

On Steady

Run (Green)

On Steady = 24 VAC power is present.

Off Steady = Loss of 24 VAC power. In the Off Steady condition, the NAE55 can
be running on battery power. Also see the POWER LED.

On Steady

24 VAC (Green)

On Steady = Battery fault. Replace the battery. Battery is not connected or cannot
be charged. The BATT FAULT LED may remain On for up to 24 hours after initially
powering on the NAE55. If the BATT FAULT LED remains on longer than 48 hours
after initially powering on the NAE55, check the battery connection or replace the
battery.

Off Steady

BATT FAULT (Red)

On Steady = General Fault. Fault conditions are user configurable in software.
Preconfigured fault conditions include excessive Central Processing Unit (CPU),
flash or memory use, excessive CPU or Printed Wire Board (PWB) temperature,
or Battery Fault. In normal operation, the GENL FAULT LED stays on steady for
the first half of the startup sequence.

Off Steady

GENL FAULT (Red)

Repair Information

If you replace an NAE55 for any reason or add a new
NAE55 to a site, you must update the site registration to
ensure that the new NAE55 is recognized and able to
communicate. Refer to the

Replacing an NAE

section in

the

NAE Commissioning Guide (LIT-1201519)

for

information on replacing an NAE and configuring the new
NAE to communicate in a

Metasys

system site.

Except for replacing the data protection battery, the
NAE55 cannot be repaired in the field. If the NAE55 fails
to operate, it must be replaced.

Batteries removed from this device must be recycled or
disposed of in accordance with local, national, and
regional regulations. Only trained technicians or qualified
building maintenance personnel should service Johnson
Controls products.

11

NAE55/NIE55 Installation Instructions

Summary of Contents for NAE55 Series

Page 1: ...stalled and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in which case the users will be required to correct the interference at their own expense Canada This Class A digital apparatus meets all the requirements of the Canadian Interference Causing Equipment Reg...

Page 2: ...cal Features and Mounting Orientation Note The features shown in Figure 1 may or may not be present depending on the NAE55 NIE55 model See Ordering Information for a list of features available on the NAE55 NIE55 models 2 NAE55 NIE55 Installation Instructions ...

Page 3: ...m in Each NAE55 application is different and no general guidelines can be given about the heat dissipating devices that may be mounted in an enclosure with the NAE55 Monitor the NAE55 processor temperature for each application to determine the acceptable combinations of devices and proper mounting location for your specific application Important Do not add any devices to an enclosure with an NAE55...

Page 4: ...E55 See the Installing the Data Protection Battery section In North America use a Class 2 24 VAC power supply with a 50 VA minimum output Outside North America use a 24 VAC Safety Extra Low Voltage SELV transformer at the appropriate rating The minimum input voltage for the NAE55 to operate properly is 20 VAC See the Technical Specifications section Use a dedicated power supply to the NAE55 only D...

Page 5: ... guidelines when wiring the NAE55 Important Do not apply 24 VAC power to the NAE before completing and checking connections Short circuits or improperly connected wires may result in permanent damage to the equipment Important Do not apply 24 VAC power to the NAE55 before installing the data protection battery See the Installing the Data Protection Battery section in this document Important Use co...

Page 6: ...the transformer to the removable power terminal block plug Figure 7 Power supply wire colors may be different on transformers not manufactured by Johnson Controls Follow the transformer manufacturer s instructions and the project installation drawings The 24 VAC power should be connected to all network devices so transformer phasing is uniform across the devices Powering network devices with unifo...

Page 7: ...ble is recommended Stranded 0 6 mm 22 AWG shielded 4 wire two twisted pairs shielded cable is acceptable Note The and bus leads should be a twisted pair On applications using 4 wire two twisted pairs cable isolate and insulate unused conductor Refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for more information Cable Type 1 Two FC devices with End of Line EOL switches in the ...

Page 8: ...bus topology the maximum length stub cable is 3 m 10 ft and the stub lengths must be calculated into the overall segment length Table 5 Guidelines for LONWorks Network Free Topology Maximum Segment Length with FTT10 and or LPT10 11 Devices Maximum Node to Node Distance Cable Type 500 m 1 640 ft 500 m 1 640 ft Belden 85102 Cable 500 m 1 640 ft 500 m 1 640 ft Belden 8471 Cable 500 m 1 640 ft 400 m 1...

Page 9: ...le you to set the NAE55 as a network terminated device on the bus To set an NAE55 as an FC Bus terminated device position the switch on the EOL switch block to the ON position Figure 8 Figure 8 FC Bus EOL Switch in the Factory Default ON Up Position Note The NAE55 is shipped with the EOL switches for both FC Buses in the initial factory position ON Figure 8 If the NAE55 is not a terminated device ...

Page 10: ...epends on the size of the database and can take several minutes Figure 10 NAE55 with LED Designations System Re Boot Switch The System Re Boot switch Figure 1 forces a manual restart of the NAE55 processor All data changes made to the system since the last time the NAE55 saved data are lost on restart including alarm trend and audit trail data Note Press the System Re Boot switch only if the NAE55...

Page 11: ... 1 second NAE55 software is in startup mode On 0 5 seconds Off 0 5 seconds NAE55 software is shutting down Off Steady Operating system is shutting down or software is not running On Steady Run Green On Steady 24 VAC power is present Off Steady Loss of 24 VAC power In the Off Steady condition the NAE55 can be running on battery power Also see the POWER LED On Steady 24 VAC Green On Steady Battery f...

Page 12: ...nks or two BACnet MS TP RS 485 trunks or one N2 trunk and one BACnet MS TP trunk includes an internal modem Supports up to 255 devices on the LONWORKS trunk MS NAE5521 2 Contains ToggleTunnel utility for converting an NAE55 NIE55 to an NAE55 model with the N2 Tunneling features enabled Not for use with MS NAE5510 OU or MS NIE5510 OU MS MULTENGSW 6 1 Some models are also available in a Buy American...

Page 13: ...andard USB connectors support an optional user supplied external modem Options One telephone port for internal modem up to 56 kbps 6 pin RJ 12 connector One LONWORKS port FTT10 78 Kbps pluggable keyed 3 position terminal block LONWORKS port available on NAE552x x models only Network and Serial Interfaces Plastic housing with internal metal shield Plastic material ABS polycarbonate Protection IP20 ...

Page 14: ...3202 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2013 Johnson Controls Inc www johnsoncontrols com Published in U S A 14 NAE55 NIE55 Installation Instructions ...

Reviews: