background image

Mounting

Location Considerations

Follow these guidelines when mounting an NAE55:

Ensure that the mounting surface can support the
NAE55 and any user-supplied enclosure.

Mount the NAE55 in the proper orientation (

Figure

4

).

Mount the NAE55 on an even surface in wall mount
applications whenever possible. If you must mount
the NAE55 on an uneven surface, be careful not to
crack the wall mount feet or housing when tightening
the screws. Use shims or washers to mount the unit
securely on the mounting surface.

Mount the NAE55 in areas free of corrosive vapors
and observe the environmental limitations listed in
the

Technical Specifications

section.

Do not mount the NAE55 on surfaces that are prone
to vibration, such as duct work, or in areas where
electromagnetic emissions from other devices or
wiring can interfere with NAE55 communication.

Allow sufficient space for running cable and wire,
making terminal connections, and accessing battery
compartment (

Figure 2

).

Do not mount the power supply below the NAE55.

On panel or enclosure mount applications, observe these
additional guidelines:

Do not install the NAE55 in an airtight enclosure.

Mount the NAE55 so that the enclosure wall or the
transformer does not obstruct ventilation of the NAE55
housing.

Figure 2: NAE55 DIN Rail Mount Dimensions and

Mounting Space Requirements, mm (in.)

Each NAE55 application is different, and no general
guidelines can be given about the heat dissipating devices
that may be mounted in an enclosure with the NAE55.
Monitor the NAE55 processor temperature for each
application to determine the acceptable combinations of
devices and proper mounting location for your specific
application.

Important:

Do not add any devices to an enclosure with
an NAE55 that could cause the temperature
of the NAE55 processor to exceed 70˚C
(158˚F). View the NAE55’s CPU
Temperature value on the NAE55’s
Diagnostic tab on the Metasys

®

Site

Management Portal. See

Technical

Specifications

for ambient condition

requirements, and refer to the
Troubleshooting section of the

NAE

Commissioning Guide (LIT-1201519)

for

additional information.

Mounting the NAE55

Wall Mount Applications

To Mount the NAE55 on a vertical surface:

1. Mark the location of the four wall mount feet on the

wall using the dimensions in

Figure 3

and an

orientation shown in

Figure 4

, or hold the NAE55 up

to the wall and mark the hole locations.

Figure 3: Mounting Screw Hole Dimensions,

mm (in.)

2. Drill holes in the wall at the marked locations.

3. Insert appropriate wall anchors in all four holes (if

necessary) and insert the screws into the top two
holes. Leave enough space between the wall surface
and the screw head for the wall mount feet.

4. Hang the NAE55 on the screws with the top wall

mount feet for horizontal wall mount applications. Hold
the NAE55 in place for vertical application.

3

NAE55/NIE55 Installation Instructions

Summary of Contents for NAE55 Series

Page 1: ...stalled and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in which case the users will be required to correct the interference at their own expense Canada This Class A digital apparatus meets all the requirements of the Canadian Interference Causing Equipment Reg...

Page 2: ...cal Features and Mounting Orientation Note The features shown in Figure 1 may or may not be present depending on the NAE55 NIE55 model See Ordering Information for a list of features available on the NAE55 NIE55 models 2 NAE55 NIE55 Installation Instructions ...

Page 3: ...m in Each NAE55 application is different and no general guidelines can be given about the heat dissipating devices that may be mounted in an enclosure with the NAE55 Monitor the NAE55 processor temperature for each application to determine the acceptable combinations of devices and proper mounting location for your specific application Important Do not add any devices to an enclosure with an NAE55...

Page 4: ...E55 See the Installing the Data Protection Battery section In North America use a Class 2 24 VAC power supply with a 50 VA minimum output Outside North America use a 24 VAC Safety Extra Low Voltage SELV transformer at the appropriate rating The minimum input voltage for the NAE55 to operate properly is 20 VAC See the Technical Specifications section Use a dedicated power supply to the NAE55 only D...

Page 5: ... guidelines when wiring the NAE55 Important Do not apply 24 VAC power to the NAE before completing and checking connections Short circuits or improperly connected wires may result in permanent damage to the equipment Important Do not apply 24 VAC power to the NAE55 before installing the data protection battery See the Installing the Data Protection Battery section in this document Important Use co...

Page 6: ...the transformer to the removable power terminal block plug Figure 7 Power supply wire colors may be different on transformers not manufactured by Johnson Controls Follow the transformer manufacturer s instructions and the project installation drawings The 24 VAC power should be connected to all network devices so transformer phasing is uniform across the devices Powering network devices with unifo...

Page 7: ...ble is recommended Stranded 0 6 mm 22 AWG shielded 4 wire two twisted pairs shielded cable is acceptable Note The and bus leads should be a twisted pair On applications using 4 wire two twisted pairs cable isolate and insulate unused conductor Refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for more information Cable Type 1 Two FC devices with End of Line EOL switches in the ...

Page 8: ...bus topology the maximum length stub cable is 3 m 10 ft and the stub lengths must be calculated into the overall segment length Table 5 Guidelines for LONWorks Network Free Topology Maximum Segment Length with FTT10 and or LPT10 11 Devices Maximum Node to Node Distance Cable Type 500 m 1 640 ft 500 m 1 640 ft Belden 85102 Cable 500 m 1 640 ft 500 m 1 640 ft Belden 8471 Cable 500 m 1 640 ft 400 m 1...

Page 9: ...le you to set the NAE55 as a network terminated device on the bus To set an NAE55 as an FC Bus terminated device position the switch on the EOL switch block to the ON position Figure 8 Figure 8 FC Bus EOL Switch in the Factory Default ON Up Position Note The NAE55 is shipped with the EOL switches for both FC Buses in the initial factory position ON Figure 8 If the NAE55 is not a terminated device ...

Page 10: ...epends on the size of the database and can take several minutes Figure 10 NAE55 with LED Designations System Re Boot Switch The System Re Boot switch Figure 1 forces a manual restart of the NAE55 processor All data changes made to the system since the last time the NAE55 saved data are lost on restart including alarm trend and audit trail data Note Press the System Re Boot switch only if the NAE55...

Page 11: ... 1 second NAE55 software is in startup mode On 0 5 seconds Off 0 5 seconds NAE55 software is shutting down Off Steady Operating system is shutting down or software is not running On Steady Run Green On Steady 24 VAC power is present Off Steady Loss of 24 VAC power In the Off Steady condition the NAE55 can be running on battery power Also see the POWER LED On Steady 24 VAC Green On Steady Battery f...

Page 12: ...nks or two BACnet MS TP RS 485 trunks or one N2 trunk and one BACnet MS TP trunk includes an internal modem Supports up to 255 devices on the LONWORKS trunk MS NAE5521 2 Contains ToggleTunnel utility for converting an NAE55 NIE55 to an NAE55 model with the N2 Tunneling features enabled Not for use with MS NAE5510 OU or MS NIE5510 OU MS MULTENGSW 6 1 Some models are also available in a Buy American...

Page 13: ...andard USB connectors support an optional user supplied external modem Options One telephone port for internal modem up to 56 kbps 6 pin RJ 12 connector One LONWORKS port FTT10 78 Kbps pluggable keyed 3 position terminal block LONWORKS port available on NAE552x x models only Network and Serial Interfaces Plastic housing with internal metal shield Plastic material ABS polycarbonate Protection IP20 ...

Page 14: ...3202 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2013 Johnson Controls Inc www johnsoncontrols com Published in U S A 14 NAE55 NIE55 Installation Instructions ...

Reviews: