controller and connect to the device with either a
MAP Gateway or MS-DIS1710-0 Local Display to view
the points in the controller. The CGM controller will
report an Operational status even though there is
no true application loaded. CCT will not be able to
commission or upload the device as a result until
a true application is downloaded. The application
name displayed will be the address of the controller
followed by the model of the controller and “Default
State”.
For example, a CGM09090 controller whose rotary
switches are set to 8 would have the default state
application name of “8-CGM09090 Default State”.
The default state creates I/O points for all
connections on the input and output terminals.
It assumes all Universal Inputs (UIs) are Nickel
temperature sensors. All Configurable Outputs
(COs) are treated as Binary Outputs (BOs) with an
initial value of 0. The default state also takes input
from a Network Sensor at address 199. If there is
no connected Network Sensor, the startup of this
default state will be delayed by 30 seconds as the
controller attempts to establish connection with the
sensor.
Commissioning equipment
controllers
You commission MS/TP equipment controllers with
the CCT software using either MAP Gateway , a
BTCVT, a ZFR wireless dongle, or in passthrough
mode when connected to an NAE or NCE. For
detailed information about commissioning
field controllers, refer to
Controller Tool Help
(LIT-12011147)
.
Note:
You can use the Bluetooth connection
to Transfer to Computer (Upload) and
commission the controller, but you cannot use
the Bluetooth connection to Transfer to Device
(Download).
Note:
The MAP Gateway serves as a
replacement for the BTCVT, which is no longer
available for purchase, but continues to be
supported.
Troubleshooting equipment
controllers
Observe the Status LEDs on the front of the
equipment controller. Table 11 provides LED
status indicator information for troubleshooting
the controller. To troubleshoot an integral or
local controller display, refer to the
DIS1710 Local
Controller Display Technical Bulletin (LIT-12011666)
.
M4-CGM General Purpose Application Controllers Installation Guide
21