OPTIONAL SHIPMENT IN MULTIPLE SECTIONS
The unit shall be shipped in sections. Assembly in the mechanical room shall not require
interconnection of refrigerant or condenser water piping between sections. All control
wiring connections between sections shall be through connector plugs. Should unit dis-
mantling and reassembly be required, the contractor shall bear the cost for this work and
ensure the manufacturer’s warranty is not voided.
BUILDING AUTOMATION SYSTEM (BAS) INTERFACE
BACnet
®
MS/TP communication protocol shall be available.
Common Alarm Output
This binary output signal is used to indicate an alarm signal. When the unit controller
has processed an alarm condition, the normally closed dry contacts shall open. When the
alarm has been cleared, the contacts shall return to the normal closed position.
Outdoor Air Damper Output
Occupied/Unoccupied output signal on/off signal is used to control the outdoor air damper.
Off corresponds with a closed damper and open with a fully open damper for outdoor air.
VAV Box/Heat
This binary output signal is used to put the VAV box in a heating or cooling mode. When
the normally open contacts are closed, this represents a heating mode, and the VAV box
should be at the maximum position. When the normally open contacts are open, this rep-
resents a cooling mode, and the VAV box should be in the cooling mode and maintaining
the space/zone temperature. Voltage for the device(s) connected to the output needs to be
provided from another source.
External Stop (Fan Stop)
This binary input signal is used to shut the unit down in an emergency. When the signal
is open, the unit is in the shut down emergency mode. Thus, the unit is in the unoccupied
mode. When the signal is closed, the unit shall be operating in the typical. After the unit
has been in the emergency mode, when the signal is closed, the unit shall be controlled in
the normal manner. Reset is not needed unless an alarm condition has occurred.
Cool/Heat Enable
The keypad shall be used to enable or disable cooling and heating and allow the unit to
be in the fan on mode. In the fan on mode for VAV units, the unit shall control duct static
pressure.
OPTIONAL ACCESORIES
Discharge Plenum
Units shall be provided with an optional acoustical discharge plenum shipped loose for
field installation. The duct opening(s) in the discharge plenum shall be located for hori-
zontal duct connection(s). Single [Multiple] duct opening size(s) and location(s) shall be
coordinated with the factory. Duct openings for the discharge plenum shall not require
field cutting or modifications.
The discharge plenum shall be constructed of formed 16-gauge pre-painted galvanized
steel. The exterior panels shall be fabricated from 18-gauge pre-painted galvanized steel.
Guide Specifications (Cont’d)
Summary of Contents for L-Series
Page 1: ...FORM 145 05 EG2 618 ENGINEERING GUIDE Water Cooled Self Contained Units L Series Vertical ...
Page 4: ...FORM 145 05 EG2 618 4 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 14: ...FORM 145 05 EG2 618 14 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...FORM 145 05 EG2 618 JOHNSON CONTROLS 35 OVERVIEW OF SERVICE CLEARANCES LSWU025 040 MODELS ...