TABLE 7 -
REFRIGERANT CHARGE DATA – LSWU060-LSWU105
MODEL #
COMP A
COMP B
COMP C
COMP D
COMP E
COMP F
NORM
HP
410A
CHARGE-
LBS
NORM
HP
410A
CHARGE-
LBS
NORM
HP
410A
CHARGE-
LBS
NORM
HP
410A
CHARGE-
LBS
NORM
HP
410A
CHARGE-
LBS
NORM
HP
410A
CHARGE-
LBS
LSWU025
10
20.0
10
20.0
-
-
-
-
-
-
-
-
LSWU032
15
21.5
11
21.5
-
-
-
-
-
-
-
-
LSWU035
15
23.0
13
23.0
-
-
-
-
-
-
-
-
LSWU040
15
27.0
15
27.0
-
-
-
-
-
-
-
-
LSWU050
15
28.5
11
25.0
11
25.0
-
-
-
-
-
-
LSWU060
15
26.5
15
26.5
15
27.5
-
-
-
-
-
-
LSWU070
15
22.5
15
22.5
15
22.50
15
22.5
-
-
-
-
LSWU080
15
23.25
15
23.25
15
25.3
15
25.3
-
-
-
-
LSWU095
13
19.0
13
19.0
13
23.50
13
23.5
13
23.5
13
23.5
LSWU105
15
19.0
15
19.0
15
23.50
15
23.5
15
27.5
15
27.5