![Johnson Controls L-Series Engineering Manual Download Page 19](http://html.mh-extra.com/html/johnson-controls/l-series/l-series_engineering-manual_2023362019.webp)
FORM 145.05-EG2 (618)
JOHNSON CONTROLS
19
Physical Data
TABLE 5 -
LSWU025-LSWU060
Model Nominal Tons
025
032
035
040
050
060
Air Flow Range
Maximum Design Air Flow -
Standard - CFM
10,500
13,300
15,500
16,000
20,000
24,000
Maximum Design Air Flow- High
Efficiency - CFM
8,600
11,000
13,200
13,200
20,000
20,000
Minimum Design Air Flow -
Standard - CFM
7,200
9,000
10,800
10,800
16,000
16,000
Minimum Design Air Flow - High
Efficiency CFM
6,300
7,800
9,400
9,400
14,100
14,100
Cabinet Dimensions
Depth (Excluding Filter Section)
- Inches
70
70
70
70
76
76
Length - Inches
78
78
78
78
100
100
Height - Inches
79.5
79.5
79.5
79.5
90
90
EER
14.3
13.6
13.3
13.1
14.2
13.3
EER - High Efficiency
15.3
14.2
14.2
13.6
14.9
13.8
Cooling Coil 3/8" OD
Face Area - Square Feet
17.8
22.2
26.7
26.7
40.1
40.1
Rows
4
4
4
6
5
6
Fins Per Inch (Standard/High
Efficiency)
12/17
12/17
12/17
12/17
12/17
12/17
Supply Fan
Fan Type
Airfoil Plenum Fan (SWSI)
Diameter - Inches/Class -
Standard
25/Class
II
25/Class
II
28/Class
II
28/Class
II
32/Class
II
36/Class
II
Diameter - Inches/Class - High
Capacity Fan
None
None
None
None
Fan Motor HP
5 - 20
10 - 25
10 - 25
10 - 25
15 - 40
15 - 40
Filters
4 Inch Deep - MERV 8
20X20X4 / 24X20X4 / 24X24X4
3 / 6 / 0
3 / 6 / 0
3 / 6 / 0
3 / 6 / 0
0 / 6 / 6
0 / 6 / 6
4 Inch Deep - MERV 13
20X20X4 / 24X20X4 / 24X24X4
3 / 6 / 0
3 / 6 / 0
3 / 6 / 0
3 / 6 / 0
0 / 6 / 6
0 / 6 / 6
Compressors
Type
Scroll / *Scroll with Capacity Modulation
Compressor Quantity / Nominal
HP
10* + 10 15* + 11 15* + 13 15* + 15 15*+2-11 15*+2-15
Number of Capacity Steps
6
6
6
6
9
9
Condensers
Type
Shell and Tube
Quantity (2 refrigerant circuits
per condenser)
1
1
1
1
2
2
Condenser Water
Connections
Water In and Out Copper
Victaulic Connections - Inches
2.625
2.625
2.625
2.625
2.625
2.625
Waterside Economizer
Coil 1/2" OD
Face Area - Square Feet
17.8
22.2
26.7
26.7
40.1
40.1
Rows/Fins Per Inch
4/11
4/11
4/11
4/11
4/11
4/11
Heating
Hot Water Coil Face Area -
Square Feet
8.8
12.0
15.2
15.2
23.3
23.3
Hot Water Coil Rows/Fins Per
Inch
1/12
1/12
1/12
1/12
1/12
1/12
Steam Coil
Consult Factory
Electric Heat - KW - 240/3/60
Nominal
17.5
17.5/35.0 17.5/35.0 17.5/35.0 35.0/52.5 35.0/52.5
Electric Heat - KW - 480/3/60
Nominal
17.5
17.5/35.0 17.5/35.0 17.5/35.0 35.0/52.5 35.0/52.5
Electric Heat - KW - 600/3/60
Nominal
17.5
17.5/35.0 17.5/35.0 17.5/35.0 35.0/52.5 35.0/52.5
Summary of Contents for L-Series
Page 1: ...FORM 145 05 EG2 618 ENGINEERING GUIDE Water Cooled Self Contained Units L Series Vertical ...
Page 4: ...FORM 145 05 EG2 618 4 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 14: ...FORM 145 05 EG2 618 14 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...FORM 145 05 EG2 618 JOHNSON CONTROLS 35 OVERVIEW OF SERVICE CLEARANCES LSWU025 040 MODELS ...