FORM 145.05-EG2 (618)
JOHNSON CONTROLS
17
TABLE 3 -
HOT WATER HEATING CORRECTION FACTORS
AIR FLOW PERCENT
TOTAL CAPACITY
80
0.903
85
0.929
90
0.953
95
0.977
100
1.000
105
1.020
110
1.042
115
1.061
120
1.082
TABLE 1 -
DX COOLING CORRECTION FACTORS
AIR FLOW PERCENT
TOTAL CAPACITY
SENSIBLE
CAPACITY
COMPRESSOR
POWER
80
0.967
0.900
0.980
85
0.976
0.926
0.985
90
0.984
0.951
0.990
95
0.991
0.976
0.995
100
1.000
1.000
1.000
105
1.006
1.024
1.003
110
1.013
1.047
1.007
115
1.019
1.070
1.012
120
1.025
1.093
1.016
TABLE 2 -
WATERSIDE ECONOMIZER CORRECTION FACTORS
AIR FLOW PERCENT
TOTAL CAPACITY
SENSIBLE CAPACITY
80
0.883
0.863
85
0.914
0.899
90
0.944
0.934
95
0.973
0.968
100
1.000
1.000
105
1.026
1.031
110
1.052
1.061
115
1.076
1.090
120
1.100
1.118