Johnson Controls JRE Series Installation Operation & Maintenance Download Page 34

W A T E R - S O U R C E   H E A T   P U M P S

JRE-Series

R e v. :   A u g u s t   1 9 ,   2 0 2 0

I n s t a l l a t i o n ,   O p e r a t i o n ,   M a i n t e n a n c e

34

Unit Commissioning & Operating Conditions

Commissioning Conditions -

 Consult Table 4b

Notes:

1.  Conditions on Table 4b are not normal or 

continuous operating conditions. Minimum/

Maximum limits are commissioning conditions 

to bring the building up to normal occupancy 

temperatures. Units are not designed/intended 

to operate under these conditions on a regular or 

ongoing basis.

2.  Voltage utilization range complies with AHRI 

 

Standard 110.

Table 4b: Building Commissioning Limits

Air Temperature Limits

Cooling

Heating

Minimum Entering Air

40

°

F [4.4

°

C]

40

°

F [4

°

C]

Maximum Entering Air db

110

°

F [43

°

C]

80

°

F [27

°

C]

Water Temperature Limits

Cooling

Heating

Minimum Entering Fluid

40

°

F [4

°

C]

20

°

F [-6.7

°

C]

Maximum Entering Fluid

120

°

F [48.9

°

C] 90

°

F [32.2

°

C]

Operating Limits -

 Environment - Units are designed for 

roof mount or indoor installation. 

Power Supply -

 A voltage variation of +/- 10% of 

nameplate utilization voltage is acceptable.

Determination of operating limits is dependent primarily 

on three factors: 1) Return Air Temperature, 2) Entering 

Water Temperature, and 3) Ambient Temperature. When 

any one of these factors is at minimum or maximum 

levels, the other two factors must be at normal levels 

to ensure proper unit operation. Extreme variation in 

temperature and humidity and/or corrosive water or air 

will adversely affect unit performance, reliability, and 

service life. Consult Table 4a for operating limits.

Table 4a: Building Operating Limits

Air Temperature Limits

Cooling

Heating

Minimum Entering Air

60

°

F [15.5

°

C]

50

°

F [10

°

C]

Maximum Entering Air db

90

°

F [32.2

°

C]

80

°

F [27

°

C]

Water Temperature Limits

Cooling

Heating

Minimum Entering Fluid

40

°

F [4

°

C]

20

°

F [-6.7

°

C]

Maximum Entering Fluid

120

°

F [48.9

°

C] 90

°

F [32.2

°

C]

Summary of Contents for JRE Series

Page 1: ...Water Source Heat Pumps Installation Operation Maintenance Supersedes Form 14808 NOM1 0820 97B0081N06 Issue Date August 19 2020 JRE Series Water Source Heat Pump MODELS JRE 3 20 Tons...

Page 2: ...orized Water Valve 18 Electrical Data 20 Electrical Data Reheat or Internal Secondary Pump 21 TWD Units with MPC DDC Auxiliary Diagram 22 TWD Units with LON DDC Auxiliary Diagram 23 TWD Units with Eco...

Page 3: ...EXTENDED RANGE STANDARD RANGE YES NO NO NO YES NO NO NO YES YES NO NO NO YES NO NO NO YES F MODULATING ENTHALPY ECONOMIZER F HOT GAS BYPASS REHEAT COIL 3 WAY MOTORIZED VALVE PROPORTIONAL CONTROL CIRCU...

Page 4: ...uipment from pallets until equipment is required for installation Unit Protection Cover rooftop units on the job site Cap the open ends of pipes In areas where painting plastering roofing or the spray...

Page 5: ...JRE036 072 Dimensional Data Optional Rain Hood Optional Rain Hood Pipe Chase Top View of Base S e r v i c e A c c e s s 3 5 1 1 m e t e r s Service Access 3 5 1 1 m eters Size Outdoor Air Opening Wate...

Page 6: ...96 144 Dimensional Data Top View of Base Optional Rain Hood Optional Rain Hood S e r v i c e A c c e s s 3 5 1 1 m e t e r s Service Access 3 5 1 1 m eters Size Outdoor Air Opening Water In Out IPT JR...

Page 7: ...tion Maintenance 7 JRE168 240 Dimensional Data Pipe Chase Optional Rain Hood Optional Rain Hood S e r v i c e A c c e s s 3 5 1 1 m e t e r s S e r v i c e A c c e s s 3 5 1 1 m e t e r s Top View of...

Page 8: ...0 Installation Operation Maintenance 8 Standard Roof Curb Model A B C D E F JRE036 48 60 72 72 25 18 35 25 72 25 35 25 14 or 24 JRE096 120 144 82 25 21 41 25 82 25 41 25 14 or 24 JRE168 240 82 25 21 7...

Page 9: ...ntenance 9 Standard Curb with Vibration Isolation Model A B C D E F JRE036 48 60 72 72 25 18 35 25 72 25 35 25 14 or 24 JRE096 120 144 82 25 21 41 25 82 25 41 25 14 or 24 JRE168 240 82 25 21 78 88 82...

Page 10: ...T PUMPS JRE Series Rev Au gu st 19 2020 Installation Operation Maintenance 10 Side Discharge Supply Return Roof Curb Model A B C JRE036 48 60 72 72 25 18 35 25 JRE096 120 144 82 25 21 41 25 JRE168 240...

Page 11: ...RGY EFFI C I E NC Y Installation Operation Maintenance 11 Side Discharge Supply Roof Isolation Curb Model A B C JRE036 48 60 72 72 25 18 35 25 JRE096 120 144 82 25 21 41 25 JRE168 240 82 25 21 78 88 N...

Page 12: ...ss to the unit side panels and all electrical connections Follow these guidelines when installing the curb 1 Set unit on curb 2 Align unit so that return air and supply air in the unit match return an...

Page 13: ...osed geothermal loop GLHP GWHP Pipe joint compound is not necessary when Teflon threaded tape is pre applied to hose assemblies or when flared end connections are used If pipe joint compound is prefer...

Page 14: ...de Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion and Clogging Particulate...

Page 15: ...accept other types of conductors Figure 2 illustrates a typical trap used with JRE Heat Pumps Multiple units within the same zone should be operated from a common temperature control Thermostat Wirin...

Page 16: ...eratures below 60 F 15 6 C must include the optional water refrigerant circuit insulation package to prevent internal condensation Figure 3 LT1 Limit Setting Alarm Relay Comp Relay O Y2 W G C R AL1 24...

Page 17: ...ing OFF OFF ON Humidifier ON ON OFF Outside air damper All other DIP combinations are invalid A slow closing valve may be required to help reduce water hammer Figure 4 shows typical wiring for a 24VAC...

Page 18: ...5 Valve Wiring Figure 6 Typical Valve Wiring From Water Source IN OUT NOTE Shut off valves strainers and other required components not shown Solenoid Valve Flow Regulator To Discharge Stage 1 Stage 2...

Page 19: ...Thermostat wire must be 18 AWG wire Representative thermostat wiring is shown in Figure 8 however actual wiring connections should be determined from the thermostat IOM and or unit wiring diagram Pra...

Page 20: ...D E 2 13 7 83 1 1 9 2 3 0 36 6 N A N A 40 0 50 F 460 3 60 414 506 A B C 2 6 2 41 0 1 3 1 2 0 15 5 N A N A 17 0 20 F 460 3 60 414 506 D E 2 6 2 41 0 1 4 3 3 0 16 7 N A N A 18 3 20 N 575 3 60 518 633 A...

Page 21: ...N 575 3 60 518 633 A B C 2 4 8 33 0 1 2 3 2 0 1 0 44 12 3 N A N A 13 5 15 N 575 3 60 518 633 D E 2 4 8 33 0 1 3 4 3 0 1 0 44 13 4 N A N A 14 6 15 JRE120 H 208 3 60 197 254 A B C 2 15 6 110 0 1 9 2 3...

Page 22: ...WATER SOURCE HEAT PUMPS JRE Series Rev Au gu st 19 2020 Installation Operation Maintenance 22 Typical Wiring Diagram Units with MPC DDC Option Auxillary Diagram...

Page 23: ...JRE Series Rev Au g u st 19 2020 THE SMART SOLUTION FOR ENERGY EFFI C I E NC Y Installation Operation Maintenance 23 Typical Wiring Diagram Units with LON DDC Option Auxillary Diagram...

Page 24: ...WATER SOURCE HEAT PUMPS JRE Series Rev Au gu st 19 2020 Installation Operation Maintenance 24 Typical Wiring Diagram Units with Economizer Auxillary Diagram...

Page 25: ...OLUTION FOR ENERGY EFFI C I E NC Y Installation Operation Maintenance 25 Typical Wiring Diagram Single Compressor DXM2 PMP3 460 volt units with Internal Secondary or Circulating Pump for Condenser Hot...

Page 26: ...WATER SOURCE HEAT PUMPS JRE Series Rev Au gu st 19 2020 Installation Operation Maintenance 26 Typical Wiring Diagram Typical Two Compressor Unit DXM2...

Page 27: ...ion modes Minimum entering air temperature while operating in the heating mode not continuous fan is the minimum entering air temperature for the standard model without the reheat option in the heatin...

Page 28: ...t does not impact room temperature Competitors without hydronic reheat typically use an on off non modulating refrigeration based reheat circuit typically referred to as Hot gas reheat HGR HGR needs h...

Page 29: ...2 13 24 145 6 7 6 22 5 0 3 0 7 104 8 78 4 12 40 147 1 8 5 30 0 1 4 3 2 107 2 79 1 12 00 148 1 8 9 120 15 0 0 1 0 1 94 8 76 6 14 59 144 6 6 5 22 5 0 3 0 7 98 5 76 9 13 67 145 1 7 2 30 0 1 3 3 0 100 5 7...

Page 30: ...ith the compressor contactor s and blower relay In the heating mode the reversing valve is de energized Almost any thermostat will activate the heat pump in heating or cooling modes The DXM2 microproc...

Page 31: ...tional control to drive the motorized valve during the reheat mode of operation The Motorized Valve is a proportional actuator three way valve combination used to divert the condenser water from the c...

Page 32: ...26 425 0 30 0 28 0 30 0 28 450 0 31 0 29 0 32 0 29 475 0 33 0 31 500 0 35 0 32 525 0 37 550 0 38 575 0 40 Example Reheat coil loss can be determined from the above table Coil velocity FPM Airflow CFM...

Page 33: ...from the coil Note If the reheat sensor located in the supply air stream is above 70 F it must be disabled to allow the modulating valve to shift Disable this sensor by removing the white wire from th...

Page 34: ...tering Fluid 120 F 48 9 C 90 F 32 2 C Operating Limits Environment Units are designed for roof mount or indoor installation Power Supply A voltage variation of 10 of nameplate utilization voltage is a...

Page 35: ...l the system and bleed off all air 10 Add antifreeze to the system in climates where ambient temperature falls below freezing using the proportion of antifreeze shown in Table 5 The volume of antifree...

Page 36: ...able sheave on fan motor and open sheave to desired position Retighten set screw and replace belt and set belt tension as below Belt Tensioning An overly loose belt will upon motor start produce a sli...

Page 37: ...emove the tension checker and read the forct applied from the bottom of the small O ring on the deflection force scale 6 Compare the force you have applied with the values given in the table below The...

Page 38: ...orrosion in the system piping Unit Filters To avoid system damage ensure that the unit filter is clean Unit Fans Manually rotate fans to assure free rotation Ensure that fans are properly secured to t...

Page 39: ...ifreeze solution Table 6 Operating Temperatures and Pressures 3 Operate each heat pump in the heating cycle imme diately after checking cooling cycle operation A time delay will prevent the compressor...

Page 40: ...y system failures complete the following checks and data entries before the system is put into full operation External Static Sheave Setting Turns Temperatures F or C Antifreeze Pressures PSIG or kPa...

Page 41: ...ION To avoid fouled machinery and extensive unit cleanup do not operate units without filters in place Do not use equipment as a temporary heat source during construction WARNING WARNING When replacin...

Page 42: ...WATER SOURCE HEAT PUMPS JRE Series Rev Au gu st 19 2020 Installation Operation Maintenance 42 Notes...

Page 43: ...JRE Series Rev Au g u st 19 2020 THE SMART SOLUTION FOR ENERGY EFFI C I E NC Y Installation Operation Maintenance 43 Notes...

Page 44: ...improve its products As a result the design and specifications of each product at the time for order may be changed without notice and may not be as described herein Please contact Johnson Controls C...

Reviews: