3. Plug the 6-pin male jack on the single socket adapter into the modular jack connection on the
back of the NS Series Network Sensor.
4. Mount the NS Series Network Sensor in the same location the AP-TMZ1600-0 Sensor was
previously mounted, concealing the adapter assembly in the existing wall opening behind the
sensor. Refer to the installation instructions for the applicable NS Series Sensor model.
5. Plug the BTCVT into the 6-pin socket on the NS Series Network Sensor.
Note:
When using an NS Series Network Sensor with screw terminal block terminations, see
the wiring diagram in the installation instructions for the applicable NS Series Sensor model.
Replacing a TE-7710-0 Series Wireless Transmitter and
TE-7720-0 Wireless Receiver connected to an FX-PCV
Controller
To replace a TE-7710-0 Series Wireless Transmitter and TE-7720-0 Wireless Receiver connected to
an FX-PCV controller, or to convert the wired sensors used with the FX-PCV18 controller to wireless,
complete the following instructions.
Note:
The TE-7710-0 Series Wireless Transmitter and TE-7720-0 Wireless Receiver must both
be replaced with an FX-WRZ Series Wireless Sensor and an FX-WRZ7860-0 Series One-to-One
Receiver. Refer to the
FX-ZFR Series Wireless Field Bus System Product Bulletin (LIT-12011686)
for a
complete list of available FX-WRZ Series Wireless Room Sensors.
1. Disconnect the 6-foot interface cable connecting the FX-PCV controller and the TE-7720-0
Wireless Receiver.
2. Plug one end of the 6-foot interface cable into the FX-PCV18 socket labeled TSTAT.
3. Plug the other end of the 6-foot interface cable into the 8-pin female socket of the single-
socket adapter.
4. Plug the male end of the single-socket adapter directly into the BTCVT.
5. Complete commissioning of the FX-PCV18 controller and disconnect the BTCVT.
Note:
Sensor point information such as temperature, setpoint, and occupancy is not
available during commissioning.
6. Install the FX-WRZ Series Wireless Sensor and an FX- WRZ7860-0 Series One-to-One Receiver
in the same locations as the previous sensor and receiver. Refer to the
FX-WRZ Series Wireless
Room Sensors Installation Instructions (Part No. 24-10332-37)
and the
FX-WRZ7860 Receiver for
One-to-One Wireless Room Sensing Systems (Part No. 24-10563-63)
.
7. Plug the 6-pin male jack on the adapter into the FX-WRZ7860-0 receiver.
Note:
When using an FX-WRZ Series Sensor with screw terminal block terminations, refer to
the wiring diagram in the installation instructions for the applicable FX-WRZ Series Sensor
model.
TE-700 Series Sensor connected to an FX-PCV Controller
To replace a TE-700 Series Sensor with a TE-730 Series Sensor, follow the instructions in
.
To reuse a TE-700 Series Sensor connected to an FX-PCV controller, follow the instructions in
.
FX-PCV1826/1832 Programmable VAV Box Controller Installation Instructions
18