Replacing a TE-700 Series sensor
Replace a TE-700 Series Sensor with a TE-730 Series Sensor. No cable adapters are required for this
scenario.
Note:
Refer to the
TE-730 Series Sensor Installation Instructions (Part No. 24-10674-0)
to install
the TE-730 Series Sensor.
Reusing a TE-700 Series sensor
See the instructions in this section to reuse a TE-700 Series Sensor when connected to an FX-PCV18
controller.
1. Disconnect the 8-pin male jack plugged into the FX-PCV controller.
2. Plug the 8-pin male jack on the Y adapter (Figure 9) provided with the FX-PCV controller into
the 8-pin female socket labeled TSTAT on the FX-PCV18 controller.
3. Plug the 8-pin male jack that was plugged into the FX-PCV controller into the 8-pin female
socket of the Y adapter.
Note:
The 6-pin connection is not used for this scenario and it should remain
unconnected.
4. Refer to the
TE-730 Series Sensor Installation Instructions (Part No. 24-10674-0)
to install the
TE-730 Series Sensor.
Figure 11: Y adapter at Controller location
Input and Output wiring guidelines tables
Table 4: I/O terminal blocks, functions, ratings, requirements, and cables
Terminal block
label
Terminal
labels
Function, ratings, and
requirements
To determine wire size
and maximum cable
length
1
UNIVERSAL
(Inputs)
+15 V
15 VDC Power Source
for active (3-
wire) input devices connected to the
Universal IN
n
terminals.
Provides 35 mA total current.
Same as (Universal)
IN
n
.
Note:
Use 3-wire
cable for devices
that source power
from the +15 V
terminal.
19